Plan Review Details - Permit 02050467
Plan Review Stops For Permit 02050467
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-28 Cont ID  
Sent By btrobaug Date 2002-05-28 Time 11:22 Rev Time 0.00
Received By btrobaug Date 2002-05-28 Time 11:09 Sent To R
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-21 Cont ID  
Sent By hmoser Date 2002-05-21 Time 17:33 Rev Time 0.50
Received By hmoser Date 2002-05-21 Time 17:33 Sent To  
Notes
2002-05-21 00:00:00PRIVISO
 #1 VARIFY TYPE OF VENTLATION USED FOR
 FRESH AIR.NATURAL VENTILATION 402,OR
 MECHANICAL VENTILATION 403
 #2 NEED CALCULATIONS FOR TYPE OF
 VENTILATION USED
 #3 NEED FAN SHUTDOWN FOR FINIAL
 INSPECTION SECTION 606.2.1
 #4 CONDENSATE DRAIN MUAT TERMINATE
 12IN FROM BUILDING 1503.4.4
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-24 Cont ID  
Sent By kstevens Date 2002-07-24 Time 11:59 Rev Time 0.00
Received By kstevens Date 2002-07-24 Time 11:59 Sent To  
Notes
2002-07-24 00:00:00REVISION OK - SANT RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-29 Cont ID  
Sent By jleech Date 2002-05-29 Time 08:59 Rev Time 0.33
Received By jleech Date 2002-05-13 Time 18:15 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-08-19 Cont ID  
Sent By rmcdouga Date 2002-08-19 Time 09:50 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-19 00:00:00SURVEY WITH CORRECTED ADDRESS, SOIL
 LETTER, PRODUCT APPROVAL FOR EYEBROW
 WINDOWS AND VERTICAL MULLIONS, ENGINEER-
 ING FOR ONE HOUR RATED GLASS BLOCK WHICH
 MEETS THE THICKNESS REQUIREMENTS FOR
 HAZARDOUS LOCATIONS,ARE OK 8-19-02

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-06-10 Cont ID  
Sent By btrobaug Date 2002-05-28 Time 11:22 Rev Time 3.00
Received By jgomez Date 2002-06-10 Time 17:14 Sent To  
Notes
2002-06-10 00:00:00APPROVED WITH PROVISO:
 1-SURVEY PROPERTY ADDRESS IS WRONG.
 REVISE AND RESUBMIT SURVEY.
 2-UPDATE DENSITY TEST RESULTS. USE FBC
 2001 REQUIREMENTS. NOT SBC 1997.
 3-PROVIDE PRODUCT APPROVAL FOR:
 A)WINDOW MULLIONS: MISSING SHEET ONE OF
 TWO OF THE APPROVED DRAWINGS.
 B)EYEBROW WINDOWS AS SHOWN ON EXTERIOR
 ELEVATIONS.
  
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN .25". AS REQ'D
 BY SECTION 2405.2.2 FBC 2001.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By sgraham Date 2002-06-18 Time 07:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***