Plan Review Stops For Permit 02050359 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-05-09 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-09 |
Time |
13:29 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-05-09 |
Time |
12:34 |
Sent To |
|
|
Notes |
2002-05-09 00:00:00 | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | PRESSURE DIFFERNTIALS ACROSS CLOSED | | DOORS WHERE RETURNS ARE CENTRALLY | | LOCATED SHALL BE LIMITED TO .001" WC OR | | LESS. PROVIDE AIR DUCT PATHWAYS OR AIR | | TRANSFER PATHWAYS FROM THE HIGH PRESSURE | | ZONE TO THE LOW ZONE. | | | | 2001 FBC(M) 603.15 - BALANCING DAMPERS | | OR OTHER MEANS OF SUPPLY AIR ADJUSTMENT | | SHALL BE PROVIDED IN THE BRANCH DUCTS OR | | AT EACH INDIVIDUAL DUCT REGISTER, GRILLE | | OR DIFFUSER. | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
|