Plan Review Details - Permit 02050252
Plan Review Stops For Permit 02050252
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-09 Cont ID  
Sent By pkrauss Date 2002-05-09 Time 07:54 Rev Time 0.35
Received By pkrauss Date 2002-05-09 Time 07:46 Sent To  
Notes
2002-05-09 00:00:00PROVISO:
  
 BALANCED RETURN AIR - PRESSURE
 DIFFERENTIALS ACROSS CLOSED DOORS WHERE
 RETURNS ARE CENTRALLY LOCATED SHALL BE
 LIMITED TO .001" WC OR LESS.PROVIDE
 AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO
 THE LOW ZONE.2001 FBC(M) 601.4.
  
 BALANCING DAMPERS OR OTHER MEANS OF
 SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED
 IN THE BRANCH DUCTS OR AT EACH
 INDIVIDUAL DUCT REGISTER, GRILLE OR
 DIFFUSER.2001 FBC(M) 603.15.
  
 CONDENSATE SHALL DISCHARGE 12" AWAY FROM
 THE BUILDING STRUCTURE AS PER 2001 FBC
 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.