Plan Review Stops For Permit 02050252 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-05-09 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-09 |
Time |
07:54 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-05-09 |
Time |
07:46 |
Sent To |
|
|
Notes |
2002-05-09 00:00:00 | PROVISO: | | | | BALANCED RETURN AIR - PRESSURE | | DIFFERENTIALS ACROSS CLOSED DOORS WHERE | | RETURNS ARE CENTRALLY LOCATED SHALL BE | | LIMITED TO .001" WC OR LESS.PROVIDE | | AIR DUCT PATHWAYS OR AIR TRANSFER | | PATHWAYS FROM THE HIGH PRESSURE ZONE TO | | THE LOW ZONE.2001 FBC(M) 601.4. | | | | BALANCING DAMPERS OR OTHER MEANS OF | | SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED | | IN THE BRANCH DUCTS OR AT EACH | | INDIVIDUAL DUCT REGISTER, GRILLE OR | | DIFFUSER.2001 FBC(M) 603.15. | | | | CONDENSATE SHALL DISCHARGE 12" AWAY FROM | | THE BUILDING STRUCTURE AS PER 2001 FBC | | 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
|