Plan Review Details - Permit 02041948
Plan Review Stops For Permit 02041948
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-09-26 Cont ID  
Sent By btrobaug Date 2002-09-26 Time 16:42 Rev Time 1.00
Received By jwitmer Date 2002-09-26 Time 15:47 Sent To  
Notes
2002-09-26 00:00:0009/26/02 REVISION # 2 OK JW

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-10-03 Cont ID  
Sent By btrobaug Date 2002-10-03 Time 14:34 Rev Time 0.25
Received By btrobaug Date 2002-10-03 Time 13:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-09-26 Cont ID  
Sent By btrobaug Date 2002-09-26 Time 16:42 Rev Time 0.50
Received By btrobaug Date   Time   Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-08-26 Cont ID  
Sent By btrobaug Date 2002-08-26 Time 14:41 Rev Time 0.50
Received By btrobaug Date 2002-08-26 Time 13:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-08-09 Cont ID  
Sent By btrobaug Date 2002-08-09 Time 16:36 Rev Time 0.00
Received By btrobaug Date 2002-08-09 Time 15:18 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-05 Cont ID  
Sent By btrobaug Date 2002-06-05 Time 07:59 Rev Time 0.00
Received By btrobaug Date 2002-05-20 Time 07:54 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-10 Cont ID  
Sent By dpalmer Date 2003-02-10 Time 10:33 Rev Time 0.00
Received By dpalmer Date 2003-02-10 Time 10:33 Sent To M
Notes
2003-02-10 00:00:00TO MECH INBOX
 TO MECH INBX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-02-10 Time 10:33 Rev Time 0.35
Received By pkrauss Date 2003-01-24 Time 13:55 Sent To  
Notes
2003-01-27 00:00:00MECH REV PERMIT 02081287

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-20 Cont ID  
Sent By hmoser Date 2002-07-20 Time 11:58 Rev Time 0.33
Received By hmoser Date 2002-07-20 Time 11:58 Sent To  
Notes
2002-07-20 00:00:00PASS/PRIVISO
 1) NEED FRESH AIR CALCULATIONS FOR ROUGH
 INSPECTION
 PLAN REVIEW BY HAROLD MOSER 7/20/02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-16 Cont ID  
Sent By hmoser Date 2002-05-16 Time 14:44 Rev Time 0.33
Received By hmoser Date 2002-05-16 Time 14:44 Sent To  
Notes
2002-05-16 00:00:00PLAN DENIED
 NO ENERGY CALCS OR MANUAL J
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-11 Cont ID  
Sent By jleech Date 2002-05-11 Time 07:43 Rev Time 0.33
Received By jleech Date 2002-05-11 Time 07:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2002-08-10 Cont ID  
Sent By jwitmer Date 2002-08-10 Time 14:55 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-08-10 Cont ID  
Sent By jwitmer Date 2002-08-10 Time 14:16 Rev Time 1.00
Received By jwitmer Date 2002-08-10 Time 14:16 Sent To  
Notes
2002-08-10 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02041948
 ADD: LOT 34 SEC 6 RENAISSANCE
 CONT: HOME DYNAMICS
 TEL: (954)520-1698
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 *****PROVISO*****
  
 1) PLEASE PROVIDE THE ORIGINAL PERMIT
 APPLICATION FORM.
  
 2) PROVIDE COPIES OF BOTH BZ RECEIPTS,
 THE ORIGINAL & TH UPPED VALUE PLUS
 RADON CHARGE.
  
 3) PROVIDE A RECORDED NOTICE OF
 COMMENCEMENT.
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-04 Cont ID  
Sent By btrobaug Date 2002-08-09 Time 16:36 Rev Time 0.00
Received By jwitmer Date 2002-06-04 Time 14:16 Sent To  
Notes
2002-06-04 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02041948
 ADD:RENAISSANCE/ SEC6 LOT 34
 CONT: HOME DYNAMICS CONSTRUCTION
 TEL: (954) 484-4800
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)- FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 2)- 1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE. THE SECTION QUOTED
 ON SHEET A-3 WALL SECTION 8" MIN. PER
 FBC 1821.1.1 IS A HIGH WIND SECTION OF
 THE CODE THAT DEALS WITH DADE & BROWARD
 COUNTIES.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 FL STATE STAT. 61G 15-23.002 A PROFESS-
 IONAL ENGINEER SHALL SIGN HIS NAME AND
 AFFIX HIS SEAL TO ALL PLANS, REPORTS FOR
 PUBLIC RECORD.
 IN REGARDS TO THE REPORT SUBMITTED
 PAGE 2 OF 9 INDICATES THAT "THE INFORMAT
 ION PROVIDED IN THIS REPORT IS NOT SUFF-
 ICIENT FOR A FINAL DESIGN OF THE FOUNDA-
 TION SYSTEM. PAGE 9 OF 9, LIMITATIONS,
 RESTATES NOT SUFFICIENT FOR A FINAL
 DESIGN OF THE FOUNDATION SYSTEM.
  
 4)- SHEET A-1 LOWER LEFT DISCREPANCY,
 PLANS CONFORM TO 2001 FLB/ ASCE 5-95
 SHOULD READ ASCE 7-98
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
 A) DESIGNATE AS TO WHICH MODEL OVER-
 HEAD CLOSPAY GARAGE DOOR SHALL BE USED
 AND THE DESIGN LOADS OF THE UNIT.
 INDICATE HOW PRODUCT TESTING ACCOMPLISH-
 ED WITH 60 " SQ VENT?
 B) MISSING REPORT FOR THE FRONT ENTRY
 DOOR. DADE COUNTY OR SBCCI REPORT, (2)
 COPIES, (3) FOR RESIDENT INSPECTOR
 PROGRAM.
 C) MISSING REPORT FOR ROOFING ASSEMB-
 LIES, DADE COUNTY OR SBCCI REPORTS.
 D)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.DADE COUNTY
 OR SBCCI REPORTS.
  
 6) 1707.4.4.1 ANCHORING REQUIREMENTS,
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THE DESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEMS USED FOR
 THE SUBSTRATES NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 7) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 8) PROVIDE INFORMATION FRONT GABLE, IS
 THW GABLE WALL FRAME OR BLOCK?
  
 9) SHEET A-3 INDICATES THE USE OF A
 SEMCO STRAP, NO LONGER IN BUSINESS!
  
 10)SHEET A-1 INDICATES THE UPLIFT VALUES
 OF THE TRUSSES & GIRDERS, NO MANUFAC-
 TUER OR MODEL NUMBER IS SPECIFIED.
  
 11) 2309.7.1 VENTILATION OF ATTIC SPACE
 PROVIDE INFO.
  
 12)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 13)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-03 Cont ID  
Sent By sgraham Date 2002-05-03 Time 14:09 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***