Plan Review Details - Permit 02041882
Plan Review Stops For Permit 02041882
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-06-10 Cont ID  
Sent By btrobaug Date 2002-06-10 Time 17:21 Rev Time 0.00
Received By btrobaug Date 2002-06-10 Time 17:20 Sent To FIRE
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-06-18 Cont ID  
Sent By mcarsill Date 2002-06-18 Time 16:53 Rev Time 0.00
Received By mcarsill Date 2002-06-18 Time 16:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-05-16 Cont ID  
Sent By btrobaug Date 2002-06-10 Time 17:22 Rev Time 0.00
Received By mcarsill Date 2002-05-16 Time 12:17 Sent To  
Notes
2002-05-16 00:00:001) PERMIT APPLICATION INDICATES A
 VALUE OF 1,200.00 DOLLARS. PLEASE
 PROVIDE A COPY OF CONTRACT OR ADJUST
 PERMIT VALUE TO CORRECT AMOUNT.
  
 2) PLEASE INDICATE ON THE PLANS THAT
 SMOKE DETECTORS ARE TO BE INSTALLED A
 MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
  
 3) NO ALARMS SHOWN IS MEETING ROOMS
 200 B AND 200C. IT APPEARS THESE ROOMS
 CAN BE SEPARATED FROM THE MAIN TRAINING
 ROOMS.
  
 4) ARE ALL FLOW AND TAMPER SWITCHES
 SHOWN ON THE PLANS.
  
 5) FIRE ALARM NOTES # 16 INDICATES
 SECURITY DEVICES ON DOORS WILL BE TIED
 INTO THE FIRE ALARM SYSTEM. ALL LOCKING
 DEVICES ARE MEET THE REQUIREMENTS OF
 EITHER DELAYED EGRESS OR ACCESS
 CONTROLLED EGRESS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910