Plan Review Details - Permit 02041858
Plan Review Stops For Permit 02041858
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-11 Cont ID  
Sent By jwitmer Date 2002-07-11 Time 09:05 Rev Time 3.50
Received By jwitmer Date 2002-07-11 Time 09:05 Sent To  
Notes
2002-07-11 00:00:00 
 ********BUILDING PROVISO*******
  
 BUILDING PLAN REVIEW
 PERMIT: 02041858
 ADD: 1501 N AUSTRALIAN AV
 CONT: WHITING-TURNER
 TEL: 832-4995
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
  
 SHEET AD-1 INDICATES THAT THE PLAYGROUND
 EQUIPMENT WILL BE "BY OTHERS". A SEPER-
 ATE PERMIT WILL BE REQUIRED, DRAWINGS
 OTHER THAN PLAYBOOSTER DR # 15224 SHALL
 BE REQUIRED,INDICATING THE VARIETY OF EX
 PERIENCES FOR INDIVIDUALS WHO CHOOSE TO
 REMAIN WITH THEIR MOBILITY AIDS, OR
 CHOOSE NOT TO TRANSER TO ELEVATED PLAY
 ELEMENTS PER ADA TABLE 15.6.2.2. THIS
 SHEET DOES INDICATE HOW MANY ELEMENTS
 SHALL BE CONSIDERED IN THIS PLAY AREA.
 REP INDICATES THERE IS 12 ELEVATED PLAY
 COMPONENTS, THIS DOES NOT INCLUDE THE
 OVERLOOK TOWER. THE ADA GUIDELINE FOR
 ACCESSIBILITY FOR PLAY AREAS, TABLE
 15.6.2.2 GIVES THE RATIOS REQUIRED FOR
 ELEVATED PLAY COMPONENTS, THE ADDITIONAL
 PLAY ELEMENT OF THE OVERLOOK TOWER WILL
 STILL STAY IN THE SAME RATIO (11-13 ELE-
 MENTS). BEFORE C/O CAN BE ISSUED, A
 SEPERATE PERMIT SHALL BE OBTAINED FOR
 THE PLAY AREA COMPONENTS,TO BE REVIEWED
 FOR CODE COMPLIANCE.
 BUILD PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-30 Cont ID  
Sent By jwitmer Date 2002-04-30 Time 09:51 Rev Time 3.33
Received By jwitmer Date 2002-04-30 Time 09:51 Sent To  
Notes
2002-04-30 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02041858
 1501 N AUSTRALIAN AV
 CONT: WHITING- TURNER
 TEL: 718-2367
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)- PLANS SUBMITTED AFTER FEB. 28,2002
 SHALL BE DESIGNED & REVIEWED UNDER THE
 2001 FL. BUILDING CODE, NOT THE 97 SBC.
  
 2)- FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3)- FOOT BRIDGE- TABLE 1604.1 LIVE LOADS
 INDICATE WHAT LOADS THE FOOT BRIDGE IS
 DESIGNED TO?
  
 4)- FL BLD CODE 1604.9 SIDEWLKS SHALL BE
 DESIGNED TO CARRY EITHER A UNIFORM DIS-
 TRIBUTED LOAD OF 200LBS OR A CONCENTRA-
 TED LOAD OF 8,000 LBS ON A SPACE 2 1/2
 SQ FT AND PLACED IN ANY POSITION, WHICH-
 EVER WILL PRODUCE THE GREATER STRESS.
  
 5)- SHEET P-1 INDICATES MONUMENTAL
 STAIRS ENTERING THE POOL PAVILION, TWO
 ISSUES ARE TO BE CLARIFIED, HANDICAPPED
 EGRESS? SINCE A SITE PLAN WAS NOT ENCLUD
 ED WE ARE ASSUMING THAT THE 6"-0" WALK-
 WAY MEETS THE FL. ACCESSIBILITY REQUIRE-
 MENTS. THE SECOND ISSUE WILL BE THE RE-
 QUIREMENT FOR INTERMEDIATE HANDRAILS. FL
 BLD CODE 1007.5.7 HANDRAILS SHALL BE PRO
 VIDED WITHIN 30" OF ALL PORTIONS OF THE
 STAIR WIDTH REQUIRED FOR EGRESS CAPACITY
 IN ACCORDANCE WITH TABLE 1004. THE
 REQUIRED EGRESS WIDTH SHALL BE ALONG THE
 NATURAL PATH OF TRAVEL. THE CODE COMMEN
 TARY DOES GIVE SOME LATITUDE IN THE RE-
 QUIRED DIMENSIOIN BETWEEN HANDRAILS. THE
 MAIN CRITERIA IS WHAT IS THE OCCUPANT
 LOAD FOR THIS STAIRWAY? WILL THE (2)
 NEW HANDRAILS GIVE US ADEQUATE ACCESS
 AS REQUIRED UNDER TABLE 1004? SEE ATTACH
 MENT.
  
 6)- MISSING INFORMATION ON SHELTER TO
 BE MOVED?
  
 SHEET AD-2
 7)- 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
 11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
 THE AREAS IN AND AROUND THE PLAY-
 GROUND ARE TO BE ACCESSIBLE FOR WHEEL-
 CHAIRS, AD-4 SEC 5 INDICATES THE USE OF
 MULCH AS A FIRM SURFACE, PLEASE PROVIDE
 ADDITIONAL DATA. THE FLORIDA ACCESSIBL-
 ITY CODE GIVES THE LAW AS TO WHAT CAN &
 CAN'T BE USED. THERE IS FEDERAL GUIDE-
 LINE ADA ACCESSIBILITY GUIDELINES FOR
 PLAY AREAS. IN THE GUIDELINE IT GIVES
 TERMS, AND STANDARDS. FOR EXAMPLE,"USE
 ZONE" THE GROUND LEVEL BENEATH AND IMMED
 IATELY ADJACENT TO A PLAY STRUCTURE OR
 PIECE OF EQUIPMENT THAT IS DESIGNED BY
 ASTM F 1487 STANDARD CONSUMER SAFETY
 PERFORANCE SPECIFICATION FOR PLAYGROUND
 EQUIPMENT FOR PUBLIC USE FOR UNRESTRICT-
 ED CIRCULATION.
 THIS GUIDELINE ALSO SHALL INDICATE
 THE RATIO OF PLAYGROUND EQUIPMENT THAT
 NEEDS TO BE ACCESSIBILE.
 PLANS STATE THAT THE PLAYGROUND
 EQUIPMENT WILL BE PERMITED SEPERATELY,
 THESE ELEMENTS SHALL BE ADDRESSED.
  
 8) SHEET AD-6 OVERLOOK TOWER NOT ACCESSI
 BLE 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
 S
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-07-26 Cont ID  
Sent By dpalmer Date 2002-07-26 Time 07:12 Rev Time 0.00
Received By dpalmer Date 2002-07-26 Time 07:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-06-27 Cont ID  
Sent By dpalmer Date 2002-06-27 Time 15:21 Rev Time 0.00
Received By dpalmer Date 2002-06-27 Time 15:20 Sent To  
Notes
2002-06-27 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE NOTE AS ASKED FOR ON
 FIRST REVIEW. WE NEED A SIGNED COPY OF
 CONTRACT FOR ENTIRE JOB. PLEASE NOTE ALL
 LABOR AND MATERIALS. PLEASE NOTE THAT
 A COPY OF ELECTRICAL PROPOSAL WAS SUB-
 -MITTED WHICH ONLY INCLUDES ELECTRICAL
 FROM CERTAIN PAGESOF PLANS???
 PLEASE NOTE IF THERE IS ELECTRICAL WORK
 TO BE DONE THAT IS SEPARATE THEN PLEASE
 PULL THOSE PLANS OUT AND SUBMIT SEPARAT-
 -LY.
 PLEASE NOTE THAT THERE IS OTHER ELEC
 SHOWN THAT IS NOT ON PROPOSAL??
 PLEASE SUBMIT AND VERIFY ALL OF THE
 ABOVE INFORMATION FOR REVIEW.
 104.6.5
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-30 Cont ID  
Sent By dpalmer Date 2002-04-30 Time 17:40 Rev Time 0.00
Received By dpalmer Date 2002-04-30 Time 17:40 Sent To  
Notes
2002-04-30 00:00:00******************** UNSAT ************
  
 1)NOTE: PLEASE PROVIDE CLARIFICATION ON
 "RECESSED" PANEL "LP". DIRECT BURIAL
 IN CONCRETE OR IS IT PLACED INTO A
 RECESS??
  
 2)NOTE: PLEASE PROVIDE INFORMATION AND/
 OR UL LISTING FOR ROPE LIGHTING AS A
 PERMANENT INSTALLATION.PLEASE PROVIDE
 PRODUCT SPECS FOR FIXTURES THAT SHOW
 LISTINGS.
  
 3)NOTE: PLEASE PROVIDE COPY OF CONTRACT
 TO VERIFY VALUE OF SCOPE OF WORK SHOWN
 ON PLANS. PLEASE NOTE THAT ALL LABOR,
 AND MATERIALS. PER 104.6.5 ADMIN CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-07-11 Cont ID  
Sent By jwitmer Date 2002-07-11 Time 09:00 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-07-25 Cont ID  
Sent By mcarsill Date 2002-07-25 Time 10:06 Rev Time 0.00
Received By mcarsill Date 2002-07-25 Time 10:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-06-28 Cont ID  
Sent By mcarsill Date 2002-06-28 Time 09:41 Rev Time 0.00
Received By mcarsill Date 2002-06-28 Time 09:41 Sent To  
Notes
2002-06-28 00:00:001) HANDRAIL SHOWN FOR AD-6 IS INCORRECT.
 PLEASE REVIEW FLORIDA BUILDING AND
 FIRE CODES. PLEASE SHOW BOTH SIDES
 OF STAIR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 16:20 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 16:20 Sent To  
Notes
2002-05-17 00:00:001) STAIRS OF OVERLOOK TOWER ARE TO BE
 PROVIDED WITH HANDRAILS.
  
 2) A SITE PLAN IS NEEDED.
  
 3) PLEASE PROVIDE DETAILS ON FLAME
 SPREAD OF PLASTIC RECYCLED LUMBER.
  
 4) HANDRAIL DETAIL ON AD-6 IS INCORRECT.
 SHOULD BE 1" 1/2 FROM CBS OR CONCRETE
 WALL.
  
 5) ARE GUARDS PLANNED FOR STEP AND
 LANDING DETAIL SHOWN ON PAGE P-1.
  
 6) ARE ANY WARNING SIGNS PLANNED FOR
 ANY LOCATIONS.
  
 7) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR BOARDWALK ELEVATION
 DETAIL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-07-11 Cont ID  
Sent By jwitmer Date 2002-07-11 Time 08:59 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-05-24 Cont ID  
Sent By kstevens Date 2002-05-24 Time 17:17 Rev Time 0.00
Received By kstevens Date 2002-05-24 Time 17:17 Sent To  
Notes
2002-05-24 00:00:00NO PLUMBING OR IRRIGATION SHOWN ON PLANS