Plan Review Details - Permit 02041825
Plan Review Stops For Permit 02041825
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-20 Cont ID  
Sent By lsmith Date 2002-06-20 Time 16:49 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-10 Cont ID  
Sent By btrobaug Date 2002-06-17 Time 07:38 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2002-05-10 00:00:00*****************FAILED*************
  
 1. ALL CODES MUST BE PER FBC 2001
 POOLS ARE CHA. 424.
  
 2. POOL SLABFOR EQUIPMENT MUST BE
 DRAWN ON PLANS SHOWING ANCHORING DETAIL
 PER FBC2001 SEC. 424
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-17 Cont ID  
Sent By btrobaug Date 2002-06-17 Time 07:38 Rev Time 0.00
Received By btrobaug Date 2002-06-17 Time 06:59 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-08 Cont ID  
Sent By kstevens Date 2002-05-07 Time 08:01 Rev Time 0.00
Received By btrobaug Date 2002-05-08 Time 07:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-15 Cont ID  
Sent By kstevens Date 2002-06-15 Time 15:16 Rev Time 0.00
Received By kstevens Date 2002-06-15 Time 15:16 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-07 Cont ID  
Sent By kstevens Date 2002-05-07 Time 08:01 Rev Time 0.00
Received By kstevens Date 2002-05-07 Time 08:00 Sent To E
Notes
2002-05-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS.
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92. AND NSPI-5 (SEE NOTE 14)
 3) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 4) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 5) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 6) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-06 Cont ID  
Sent By sgraham Date 2002-05-06 Time 12:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***