Plan Review Details - Permit 02041775
Plan Review Stops For Permit 02041775
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-18 Cont ID  
Sent By btrobaug Date 2002-06-18 Time 12:53 Rev Time 0.00
Received By btrobaug Date 2002-06-18 Time 12:02 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-16 Cont ID  
Sent By dpalmer Date 2002-05-16 Time 15:51 Rev Time 0.00
Received By dpalmer Date 2002-05-16 Time 15:51 Sent To B
Notes
2002-05-16 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE PLANS STILL REFER.
 96 NECNEEDS 99 NEC.
  
 2)NOTE: PLEASE SHOW ARC PROTECTION PER
 210-12 PLEASE LIST.
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4)NOTE: PLEASE NOTE MISPRINT ON AIC
 RATING. SHOWN AS 22.00?
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-04 Cont ID  
Sent By pkrauss Date 2002-12-04 Time 11:03 Rev Time 0.30
Received By pkrauss Date 2002-12-04 Time 10:45 Sent To  
Notes
2002-12-04 00:00:00MECH REV PERMIT 02041790

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 08:45 Rev Time 0.40
Received By pkrauss Date 2002-06-22 Time 08:45 Sent To R
Notes
2002-06-22 00:00:00APPROVED PER H. MOSER 6-22-02
 MECHANICAL PERMIT 02041790

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-11 Cont ID  
Sent By btrobaug Date 2002-06-18 Time 12:53 Rev Time 0.50
Received By hmoser Date 2002-05-11 Time 13:43 Sent To  
Notes
2002-05-11 00:00:00PLAN DENIED
 #1 CFM.DO NOT MATCH TOTAL CFM.NO PLANS
 #2 NEED DUCT SIZE MAIN TRUNT TO GUEST
 BEDROOMS
 #3 CHANGE EQUIPMENT SIZE TO 5 TON ON
 PLAN
 #4 COPPER SIZE PER MANUFACTURER
 INSTRUCTIONS
 #5 VENTILATION CALCULATIONS

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-08 Cont ID  
Sent By jleech Date 2002-05-08 Time 18:56 Rev Time 0.33
Received By jleech Date 2002-05-08 Time 18:56 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-07-30 Cont ID  
Sent By rmcdouga Date 2002-07-30 Time 11:18 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-30 00:00:00************BUILDING PROVISO************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 TESTING SHALL BE DETERMINED BY ACCEPTED
 ENGINEERING STANDARDS AND PRACTICE.
 TESTS SHALL BE CERTIFIED BY AN ENGINEER
 REGISTERED IN THE STATE OF FLORIDA.
 SUBMIT SOIL BEARING TESTS PRIOR TO
 POURING THE FOUNDATION.
  
 4) SUBMIT (2) STORM PANEL INSTALLATION
 SCHEDULES LISTING ALL OF THE OPENINGS TO
 BE SHUTTERED. THE ONES THAT WERE
 SUBMITTED ONLY LIST 7 OF 10 OPENINGS.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 EVALUATION REPORTS FOR GLASS BLOCK. ONLY
 PORTIONS OF THE REPORT WAS SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-06-25 Cont ID  
Sent By rmcdouga Date 2002-06-25 Time 08:56 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-25 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT ON THE PLANS AS
 REQUIRED BY THE 2001 FBC SEC. 1606.1.7.
  
 3) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 4) PROVIDE SOIL BEARING TEST REPORT PER
 CITY OF WPB AMENDMENTS TO 2001 FBC SEC.
 1804.2.2.
  
 5) PROVIDE (2) COPIES OF INSTALLATION
 SCHEDULE FOR STORM PANELS. THESE ITEMS
 ARE REQUIRED AT TIME OF PERMIT OR YOU
 WILL BE REQUIRED TO PULL A SEPARATE
 PERMIT WITH ADDITIONAL FEES.
  
 6) PROVIDE ADDITIONAL COPIES OF PRODUCT
 APPROVALS FOR THE FRONT DOOR AND GLASS
 BLOCK. TWO COPIES ARE REQUIRED.
  
 7) PROVIDE TESTING INFORMATION WHICH
 INDICATES THAT THE GLASS BLOCK HAS A
 FIRE RATING OF ONE HOUR.
  
 8) PLEASE CHANGE THE CALL SIZE OF THE
 EGRESS WINDOW (I) IN THE WINDOW SCHEDULE
 TO 24/5 SH WHICH CORRESPONDS TO THE
 DIMENSIONS GIVEN.
  
 9) PLEASE CHANGE NOTE #6 UNDER GENERAL
 NOTES ON A2 TO REFERENCE THE 2001
 FLORIDA PLUMBING CODE.
  
 10) PROVIDE A DETAIL INDICATING ONE HOUR
 FIRE RATED ASSEMBLY BASED ON BOTH
 INTERIOR AND EXTERIOR FIRE EXPOSURE FOR
 THE GABLE END ON THE ZERO LOT LINE.
  
 11) PLEASE INSERT THE REVISED SHEETS
 INTO THE PLANS. SUBMIT THE OLD SHEETS
 ALONG WITH THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-05-30 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 08:45 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-05-30 00:00:00BUILDING DENIED
 SAME COMMENTS AS PERMIT # 02040521

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-03 Cont ID  
Sent By sgraham Date 2002-05-03 Time 14:04 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***