2002-06-25 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) INDICATE THE APPLICABLE INTERNAL |
| PRESSURE COEFFICIENT ON THE PLANS AS |
| REQUIRED BY THE 2001 FBC SEC. 1606.1.7. |
| |
| 3) THE STRUCTURE IS LOCATED IN AN "A8" |
| FLOOD ZONE AN ELEVATION CERTIFICATE IS |
| REQUIRED. |
| |
| 4) PROVIDE SOIL BEARING TEST REPORT PER |
| CITY OF WPB AMENDMENTS TO 2001 FBC SEC. |
| 1804.2.2. |
| |
| 5) PROVIDE (2) COPIES OF INSTALLATION |
| SCHEDULE FOR STORM PANELS. THESE ITEMS |
| ARE REQUIRED AT TIME OF PERMIT OR YOU |
| WILL BE REQUIRED TO PULL A SEPARATE |
| PERMIT WITH ADDITIONAL FEES. |
| |
| 6) PROVIDE ADDITIONAL COPIES OF PRODUCT |
| APPROVALS FOR THE FRONT DOOR AND GLASS |
| BLOCK. TWO COPIES ARE REQUIRED. |
| |
| 7) PROVIDE TESTING INFORMATION WHICH |
| INDICATES THAT THE GLASS BLOCK HAS A |
| FIRE RATING OF ONE HOUR. |
| |
| 8) PLEASE CHANGE THE CALL SIZE OF THE |
| EGRESS WINDOW (I) IN THE WINDOW SCHEDULE |
| TO 24/5 SH WHICH CORRESPONDS TO THE |
| DIMENSIONS GIVEN. |
| |
| 9) PLEASE CHANGE NOTE #6 UNDER GENERAL |
| NOTES ON A2 TO REFERENCE THE 2001 |
| FLORIDA PLUMBING CODE. |
| |
| 10) PROVIDE A DETAIL INDICATING ONE HOUR |
| FIRE RATED ASSEMBLY BASED ON BOTH |
| INTERIOR AND EXTERIOR FIRE EXPOSURE FOR |
| THE GABLE END ON THE ZERO LOT LINE. |
| |
| 11) PLEASE INSERT THE REVISED SHEETS |
| INTO THE PLANS. SUBMIT THE OLD SHEETS |
| ALONG WITH THE PLANS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |