Plan Review Details - Permit 02041773
Plan Review Stops For Permit 02041773
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-31 Cont ID  
Sent By dpalmer Date 2002-05-31 Time 05:32 Rev Time 0.00
Received By dpalmer Date 2002-05-31 Time 05:32 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-15 Cont ID  
Sent By dpalmer Date 2002-05-15 Time 07:03 Rev Time 0.00
Received By dpalmer Date 2002-05-15 Time 07:00 Sent To B
Notes
2002-05-15 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE PLANS REFERENCES
 CODES FROM 96 NEC. PLEASE NOTE CODES
 FROM 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT FOR 22.00
 AIC RATING ON RISER DIAGRAM.
  
 3)NOTE: PLEASE NOTE MISSINGARC FAULT
 PROTECTION PER 210-12.
  
 4 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-06 Cont ID  
Sent By pkrauss Date 2002-12-06 Time 12:49 Rev Time 0.25
Received By pkrauss Date 2002-12-06 Time 12:32 Sent To  
Notes
2002-12-06 00:00:00MECH REV PERMIT 02041797

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-20 Cont ID  
Sent By hmoser Date 2002-06-20 Time 18:31 Rev Time 0.25
Received By hmoser Date 2002-06-20 Time 18:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-11 Cont ID  
Sent By hmoser Date 2002-05-11 Time 13:07 Rev Time 0.50
Received By hmoser Date 2002-05-11 Time 13:06 Sent To  
Notes
2002-05-11 00:00:00PLAN DENIED
 #1 DUCT SIZE FROM 1ST & 2ED FLOOR DO NOT
 MATCH
 #2 CHANGE AIRCONDITIONING EQUIPMENT
 ON PLAN TO 5 TON
 #3 CHANGE COPPER SIZE TO MANUFACTURER'S
 INSTALLATIONS INSTURCTIONS
 #4 SHOW TYPE OF VENTILATION
 #5 NEED CALCULATIONS FOR VENTILATION
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-08 Cont ID  
Sent By jleech Date 2002-05-08 Time 20:03 Rev Time 0.33
Received By jleech Date 2002-05-08 Time 20:03 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-06-03 Cont ID  
Sent By lhatten Date 2002-06-03 Time 10:13 Rev Time 2.50
Received By lhatten Date 2002-06-02 Time 10:11 Sent To  
Notes
2002-06-03 00:00:00REVIEW & STAMPED PLANS 06/02/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-03 Cont ID  
Sent By sgraham Date 2002-05-03 Time 14:04 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***