Plan Review Details - Permit 02041769
Plan Review Stops For Permit 02041769
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-13 Cont ID  
Sent By btrobaug Date 2002-05-13 Time 07:00 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-13 Cont ID  
Sent By kstevens Date 2002-05-11 Time 15:50 Rev Time 0.00
Received By btrobaug Date 2002-05-13 Time 06:39 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-21 Cont ID  
Sent By kstevens Date 2002-05-21 Time 13:29 Rev Time 0.00
Received By kstevens Date 2002-05-21 Time 13:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-11 Cont ID  
Sent By kstevens Date 2002-05-11 Time 15:44 Rev Time 0.00
Received By kstevens Date 2002-05-11 Time 15:44 Sent To E
Notes
2002-05-11 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS.
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 3) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) DETAILS ON PLANS ARE VERY HARD TO
 READ AND ARE UNCLEAR. PLEASE SUBMIT
 PLANS THAT ARE CLEAR.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-09 Cont ID  
Sent By sgraham Date 2002-05-09 Time 08:35 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***