2002-06-10 00:00:00 | BUILDING DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) THE AREA OF THE WALL OPENINGS AT THE |
| FRONT ELEVATION EXCEEDS THE PERCENTAGE |
| ALLOWED BY TABLE 600. THE CALCULATIONS |
| ARE INCORRECT. THE PERCENTAGE ALLOWED IS |
| 20% FROM OVER 3 FEET TO 10 FEET AND IS |
| 40% FROM OVER 10 FEET TO 20 FEET. PLEASE |
| CORRECT. |
| |
| 3) THE 2001 FBC SECTION 1606.1.7 |
| REQUIRES THE FOLLOWING INFORMATION TO BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS: |
| - BASIC WIND SPEED, MPH. |
| - WIND IMPORTANCE FACTOR(1) AND BUILDING |
| CATEGORY. |
| - WIND EXPOSURE- IF MORE THAN ONE WIND |
| EXPOSURE IS USED THE WIND EXPOSURE AND |
| APPLICABLE WIND DIRECTION SHALL BE |
| INDICATED. |
| - THE APPLICABLE INTERNAL PRESSURE |
| COEFFICIENT |
| - COMPONENTS AND CLADDING. THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF, TO BE |
| USED FOR THE DESIGN OF EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT |
| SPECIFICALLY DESIGNED BY THE REGISTERED |
| DESIGN PROFESSIONAL. |
| PLEASE UPDATE THE DESIGN INFORMATION ON |
| S1. |
| |
| 4) INDICATE THE POSITIVE AND NEGATIVE |
| WINDLOAD PRESSURES FOR THE SKYLIGHT AND |
| THE 25 SH WINDOW IN THE GARAGE. |
| |
| 5) REVISE NOTE #2 ON A1 TO REFERENCE THE |
| FLORIDA BUILDING CODE. |
| |
| 6) REVISE THE BUCK DETAIL #2 ON A4 TO |
| COMPLY WITH FBC SEC. 1707.4.4.2. |
| |
| 7) PLEASE UPDATE THE FOLLOWING NOTES ON |
| S4 TO REFERENCE THE 2001 FBC: |
| - #3 & #4 UNDER GENERAL NOTES |
| - #9 UNDER GENERAL NOTES TO ASCE 7-98 & |
| 140 MPH (3 SEC. GUST) |
| - #1 UNDER SAFEGUARDS |
| - #1 UNDER REINFORCED CONCRETE |
| - #2 UNDER TRUSSES |
| - #5 UNDER ROOF SHEATHING |
| |
| 8) PLEASE REVISE NOTE #7, THE CORRECT |
| REFERENCE IS ASTM A 185. THE WELDED WIRE |
| FABRIC IS REQUIRED TO BE SUPPORTED PER |
| FBC SEC. 1909.3. |
| |
| 9) THE NEGATIVE PRESSURE FOR THE 1/2- 36 |
| SH KDI WINDOWS IN THE DEN AND LIVING |
| ROOM EXCEED THE VALUE IN THE SBCCI |
| PRODUCT EVALUATION REPORT. THE |
| COMPARATIVE ANALYSIS REPORT SUBMITTED IS |
| NOT VALID UNLESS IT IS AN ORIGINAL |
| SIGNED AND SEALED COPY. |
| |
| 10) PLEASE SUBMIT KEY PLANS AND |
| INSTALLATION SCHEDULE FOR THIS MODEL. |
| |
| 11) THE PRODUCT APPROVAL FOR ENTEGRA |
| ROOF TILE IS EXPIRED. |
| |
| 12) PROVIDE THE CORRECT GARAGE DOOR |
| DRAWING. THE ONE ATTACHED TO THE PRODUCT |
| APPROVAL IS FOR A 9 FOOT DOOR. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |