Plan Review Details - Permit 02041630
Plan Review Stops For Permit 02041630
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-08-06 Cont ID  
Sent By btrobaug Date 2002-08-06 Time 14:20 Rev Time 0.00
Received By btrobaug Date 2002-08-06 Time 13:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-07-23 Cont ID  
Sent By dpalmer Date 2002-07-23 Time 06:46 Rev Time 0.00
Received By dpalmer Date 2002-07-23 Time 06:46 Sent To B
Notes
2002-07-23 00:00:00****************** UNSAT **************
  
 ********** NOTE ************
 3RD TIME UNSAT, PLEASE SEE ATTACHED
 SHEET FOR FS.553.802B. PLANS BEING SENT
 BACK FOR THE SAME COMMENTS.
 PLEASE SEE ATTACHED SHEETS FOR PREVIOUS
 TWO REVIEWS AND COMMENTS.
  
 1)NOTE: PLEASE NOTE AN EQUIPMENT GROUND-
 -ING CONDUCTOR IS STILL BEING SHOWN
 BETWEEN METER AND MAIN?? THIS IS PARA-
 LLELING THE NEUTRAL WHICH IS NOT
 PERMITTED. PLEASE NOTE THAT THE NEUTRAL
 IS BONDED WITH THE GRND SCREW AT THE
 FIRST MEANS OF DISC.
  
 2)NOTE: PLEASE NOTE THAT THE TWO SMALL
 APPLIANCE CIRCUITS REQ`D PER 210-52B
 210-11-C-1 ARE STILL NOT SHOWN IN LOAD
 CALCULATIONS?? PLEASE NOTE MICROWAVE IS
 SHOWN ON LOAD CALCS BUT NOT PANEL
 SCHEDULE?
  
 3)NOTE: PLEASE VERIFY LOAD SHOWN FOR
 RANGE AT 5KW?
  
 4)NOTE: PLEASE NOTE SD IS SHOWN IN BATH,
 SD`S ARE NOT PERMITTED IN BATHS PER
 NFPA-72, 2-5.2.1.6
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW AND
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 BILL TROBAUGH
 X-8392

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-07-09 Cont ID  
Sent By btrobaug Date 2002-07-09 Time 14:33 Rev Time 0.00
Received By btrobaug Date 2002-07-09 Time 06:37 Sent To FIRE
Notes
2002-07-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING
 DISCREPANCIES,CORRECT PLANS AND
 RESUBMIT FOR REVIEW:
  
 1} RISER STILL HAS THE EQUIPMENT GROUND
 FROM THE METER TO THE DISCONNECT.PLEASE
 REMOVE.
  
 2} THE SMALL APPLIANCE CIRCUITS NEED TO
 BE INCLUDED IN THE LOAD CALCULATIONS AS
 INDICATED ON THE PREVIOUS REVIEW.
  
 3} SHEET E-1.0 HAS AN ARCHITECTURAL
 TITLE BLOCK BUT IS NOT SEALED PER
 61G1-16.001 FAC.
  
  
 IF THERE ARE ANY QUESTION PLEASE CALL:
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-15 Cont ID  
Sent By btrobaug Date 2002-05-15 Time 15:58 Rev Time 0.00
Received By btrobaug Date 2002-05-15 Time 15:07 Sent To R
Notes
2002-05-15 00:00:00~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING
 DISCREPANCIES,CORRECT PLANS AND
 RESUBMIT FOR REVIEW.
  
 1} THE RISER DIAGRAM INDICATES THE
 EQUIPMENT GROUND BEING RAN FROM THE
 METER TO THE DISCONNECT.PLEASE REMOVE
 SAME TO AVOID A PARALLEL GROUND/NEUTRAL
 PATH.
  
 2} INCLUDE SMALL APPLIANCE CIRCUITS IN
 LOAD CALC. PER 220-30.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 4} LIST KITCHEN CIRCUITS ON PANEL
 SCHEDULE.
  
 5} A/C #1 AHU @ 10K,BREAKER AND BRANCH
 CIRCUIT CONDUCTORS ARE UNDERSIZED.
  
 6} THE WASHER IS LISTED AT 3000W IN THE
 LOAD CALCS AND SHOWN ON A 20 AMP BREAKER
 WITH #12 WIRE ON THE PANEL SCHEDULE,
 PLEASE CLARIFY.
  
 7} OVEN SHOWN ON PANEL SCHEDULE, BUT NOT
 IN LOAD CALCS,PLEASE CLARIFY.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-16 Cont ID  
Sent By mcarsill Date 2002-07-16 Time 10:50 Rev Time 0.00
Received By mcarsill Date 2002-07-16 Time 10:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-13 Cont ID  
Sent By rmcdouga Date 2002-07-10 Time 13:22 Rev Time 0.00
Received By mcarsill Date 2002-06-13 Time 14:26 Sent To  
Notes
2002-06-13 00:00:001) PLEASE CLEARLY INDICATE LOCATIONS
 OF FIRE HYDRANTS FOR THE DEVELOPMENT.
  
 2) PORTABLE FIRE EXTINGUISHERS REQUIRED.
  
 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
  
 4) ANY ROADS MORE THAN 150 FEET ARE
 REQUIRED TO HAVE APPROVED TURN-AROUNDS
 AT 50 FEET OF CENTERLINE.
  
 5) ELECTRIC POWERED SMOKE DETECTORS
 ARE REQUIRED.
  
 6) TENANT SEPARATIONS ARE REQUIRED.
  
 7) PLEASE CLEARLY IDENTIFY ALL EGRESS
 WINDOWS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-18 Cont ID  
Sent By pkrauss Date 2002-12-18 Time 16:28 Rev Time 0.15
Received By pkrauss Date 2002-12-18 Time 16:28 Sent To  
Notes
2002-12-18 00:00:00MECH PERMIT 02041634
 REVISED ENERGY CALCS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-11 Cont ID  
Sent By hmoser Date 2002-05-11 Time 11:40 Rev Time 0.33
Received By hmoser Date 2002-05-11 Time 11:40 Sent To  
Notes
2002-05-11 00:00:00PROVISO
 SHOW TYPE OF VENTILATION USED.
 NEED CALCULATIONS FOR TYPE OF
 VANTILATION USED
 HAROLD MOSER [561]659-8096 EXE 8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-18 Cont ID  
Sent By kstevens Date 2002-12-18 Time 08:00 Rev Time 0.10
Received By kstevens Date 2002-12-18 Time 07:59 Sent To  
Notes
2002-12-18 00:00:00SUBMITTAL LETTER - DELETE REQUIREMENT TO
 INSULATE HOT WATER PIPE.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-08 Cont ID  
Sent By jleech Date 2002-05-08 Time 18:22 Rev Time 0.33
Received By jleech Date 2002-05-08 Time 18:22 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-07-25 Cont ID  
Sent By rmcdouga Date 2002-07-25 Time 13:52 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-25 00:00:00************BUILDING PROVISO************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) PLEASE REVISE THE ORIGINAL MYLAR TO
 CORRECT THE INFORMATION FOR THE SPACING
 OF SUPPORTS FOR THE WELDED WIRE MESH.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-07-10 Cont ID  
Sent By rmcdouga Date 2002-07-10 Time 11:35 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To FIRE
Notes
2002-07-10 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE NEGATIVE WINDLOAD PRESSURE GIVEN
 ON THE PLANS (-118.40 PSF ) FOR THE 1/2
 33SH BATHROOM WINDOW,EXCEEDS THE MAXIMUM
 NEGATIVE DESIGN PRESSURE LISTED IN THE
 KDI WINDOW COMPARATIVE ANALYSIS CHART
 FOR THAT SIZE WINDOW (-109 PSF).
 PLEASE CORRECT.
  
 3) THE MAXIMUM SPACING FOR WELDED WIRE
 MESH SUPPORTS SHALL NOT EXCEED 3 FEET OR
 MANUFACTURERS' SPECIFICATIONS PER FBC
 SECTION 1909.3 (2). PLEASE REVISE THE
 NOTES ON SHEETS S1 AND S4 TO REFLECT
 THIS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-04 Cont ID  
Sent By btrobaug Date 2002-07-09 Time 14:33 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-04 00:00:00BUILDING DENIED
  
 SAME COMMENTS AS PERMIT # 02041683.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-05 Cont ID  
Sent By sgraham Date 2002-06-05 Time 08:40 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***