Plan Review Details - Permit 02041552
Plan Review Stops For Permit 02041552
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-10 Cont ID  
Sent By dpalmer Date 2002-06-11 Time 12:11 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-17 Cont ID  
Sent By hpiskura Date 2002-05-17 Time 09:20 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-17 00:00:00THE NORANDEX WINDOW DESIGN SHEET CITES
 THE 1997 SBCCI CODE WHICH HAS BEEN
 SUPERCEDED BY THE FBC 2001.PLEASE
 REVISE AS NECESSARY AND ENSURE
 COMPLIANCE WITH THE FBC.
  
 SHUTTERS FOR THE SECOND STORY ARE NOT A
 PRACTICAL APPLICATION.PLEASE PROVIDE
 AN ALTERNATE HURRICANE MISSILE IMPACT
 RESISTANT METHOD.SEE THE ATTACHED
 CITY IMPLEMENTATION STANDARD.
  
 SHEET 11 SECTION F, WRONGLY DEPICTS THE
 FRT PLYWOOD ROOF SHEATHING TO BE
 INSTALLED FOUR FEET FROM THE CENTER
 LINE OF THE PARTY WALL.FBC 704.4.2
 (2) PROVIDES FOR THE PROTECTION TO
 OCCUR FROM EACH "SIDE" OF THE WALL.
 PLEASE REVISE AS NECESSARY.
  
 SHEET 11 SECTION B SHOWS A FOOTING DEPTH
 OF 8" THAT SHOULD BE 12" IN ACCORDANCE
 WITH FBC 1804.1.3.
  
 SHEET 11 SECTION C IS NOT CLEAR AS TO
 HOW THE OVERHANG OUTLOOKER WILL BE
 CONNECTED AND THE FEASIBILITY OF THE
 VENTING IN THE SOFFIT.
  
 SBCCI REPORT #9755 FOR THE AMARR GARAGE
 DOOR IS NOT A CURRENT LISTING WITH SBCCI
 PLEASE PROVIDE A CURRENT OR ALTERNATE
 LISTING.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-11 Cont ID  
Sent By hpiskura Date 2002-06-10 Time 09:56 Rev Time 0.00
Received By dpalmer Date 2002-06-11 Time 07:40 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-22 Cont ID  
Sent By dpalmer Date 2002-05-22 Time 06:02 Rev Time 0.00
Received By dpalmer Date 2002-05-22 Time 19:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-28 Cont ID  
Sent By mcarsill Date 2002-05-28 Time 13:59 Rev Time 0.00
Received By mcarsill Date 2002-05-28 Time 13:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-27 Cont ID  
Sent By hmoser Date 2002-05-27 Time 07:07 Rev Time 0.50
Received By hmoser Date 2002-05-27 Time 07:16 Sent To  
Notes
2002-05-27 00:00:00PASSED/PROVISO
  
 1) NEED REVISED PLAN BEFORE FINAL INSP-
 ECTION
 2) VERIFY TYPE OF VENTILATION USED FOR
 FRESH AIR. NATURAL 402 OR MECHANICAL 403
 3) NEED CALCULATIONS FOR TYPE OF VENTIL-
 ATION USED.
 4) REFER TO SECTION 403 MECHANICAL VENT-
 ILATION. NO WINDOW EXCEPTION.
 5) CONDENSATE DRAIN MUST TERMINATE 12"
 FROM BLDG. 1503.4.4
  
 PLAN REVIEW BY HAROLD MOSER
 (561) 659-8096 EXT 8390
 PASSED/PRIVISO
 1) NEED REVISER PLAN BEFORE FINAL
 INSPECTION
 2) VERIFY TYPE OF VENTILATION USED FOR
 FRESH AIR.NATURAL 402 OR MECHANICAL
 403
 3) NEED CALCULATIONS FOR TYPE OF
 VENTILATION USED
 4) REFER TO SECTION 601.4 BALANCED
 RETURN AIR
 5) REFER TO SECTION 403 MECHANICAL
 VENTILATION.NO WINDOW EXCEPTION
 6) CONDENSATE DRAIN MUST TERMINATE 12"
 FROM BUILDING
 PLAN REVIEW BY HAROLD MOSER

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-18 Cont ID  
Sent By kstevens Date 2002-05-18 Time 11:58 Rev Time 0.00
Received By kstevens Date 2002-05-18 Time 11:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-06 Cont ID  
Sent By sgraham Date 2002-05-06 Time 11:55 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***