Plan Review Details - Permit 02041467
Plan Review Stops For Permit 02041467
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-03 Cont ID  
Sent By lsmith Date 2002-07-03 Time 09:25 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2002-07-03 00:00:00PROCESSED PERMITS, CHECKED VALUES,
 STAMPED PLANS, ENTERED PROPERTY INFO
 7/3/02 LS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-31 Cont ID  
Sent By jwitmer Date 2002-05-31 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2002-05-31 Time 07:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-09-04 Cont ID  
Sent By btrobaug Date 2002-09-04 Time 14:09 Rev Time 0.25
Received By btrobaug Date 2002-09-04 Time 14:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-02 Cont ID  
Sent By dpalmer Date 2002-07-02 Time 14:03 Rev Time 0.00
Received By dpalmer Date 2002-07-02 Time 14:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-24 Cont ID  
Sent By dpalmer Date 2002-05-24 Time 05:46 Rev Time 0.00
Received By dpalmer Date 2002-05-24 Time 05:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-21 Cont ID  
Sent By mcarsill Date 2002-05-21 Time 09:59 Rev Time 0.00
Received By mcarsill Date 2002-05-21 Time 09:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-27 Cont ID  
Sent By pkrauss Date 2002-06-27 Time 11:34 Rev Time 0.35
Received By pkrauss Date 2002-06-27 Time 11:34 Sent To  
Notes
2002-06-27 00:00:00PROVISO:MECHANICAL PERMIT 02041469
 UNIT - BR
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 APPLIANCES SHALL NOT BE INSTALLED IN A
 LOCATION WHERE SUBJECT TO MECHANICAL
 DAMAGE UNLESS PROTECTED BY APPROVED
 BARRIERS.2001 FBC(M) 303.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-04 Cont ID  
Sent By pkrauss Date 2002-06-04 Time 14:06 Rev Time 0.40
Received By pkrauss Date 2002-06-04 Time 14:06 Sent To  
Notes
2002-06-04 00:00:00******************DENIED****************
  
 MECHANICAL PERMIT 02041469
  
 UNIT "B" - R
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 PRESSURE DIFFERNTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001" WC OR
 LESS. PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE
 ZONE TO THE LOW ZONE.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 REFERENCE DRYER LOCATION - SHALL HAVE
 PROTECTION FROM DAMAGE AS PER 2001 FBC,
 MECH 303.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-22 Cont ID  
Sent By jleech Date 2002-06-22 Time 06:42 Rev Time 0.25
Received By jleech Date 2002-06-22 Time 06:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-10 Cont ID  
Sent By sgraham Date 2002-05-10 Time 08:31 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved