Plan Review Details - Permit 02041323
Plan Review Stops For Permit 02041323
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-07 Cont ID  
Sent By jwitmer Date 2002-06-07 Time 09:25 Rev Time 1.00
Received By jwitmer Date 2002-06-07 Time 09:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-13 Cont ID  
Sent By jwitmer Date 2002-05-13 Time 17:59 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-05-13 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02041323
 1000 S DIXIE
 CONT: RAPP CONSTRUCTION
 TEL: 802-9997
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, WHAT
 TYPE BUILDING? SPRINKLERED OR NON?
 WILL BACKING FOR CABINETS REQUIRE
 PRESSURE TREATING BECAUSE OF BUILDING
 TYPE?
  
 2) SHEET A-1 INDICATES FIRE RATED WALLS
 NO RATING IS GIVEN?
  
 3) OPEN OFFICE AREA DOESN'T GIVE ANY
 LIFE SAFETY PLAN, ACCESS AISLES.
  
 4)- 1005.4 EMERGENCY ESCAPE AND RESCUE
 OPENINGS,
 (2) EVERY ROOM OR SPACE GREATER THAN
 250 FT USED FOR CLASSROOM OR OTHER ED-
 UCATIONAL PURPOSES OR NORMALLY SUBJECT
 TO STUDENT OCCUPANCY, AND EVERY ROOM
 SUBJECT TO CLIENT OCCUPNCY SHALL NOT
 HAVE NOT LESS THAN ONE OUTSIDE WINDOW
 FOR EMERGENCY RESCUE, SEE EXCEPTIONSALSO
 THIS PERTAINS TO THE PHARMACY, SCIENCE,
 PRACTICE CLASSROOMS AND STUDENT LOUNGE.
  
 5) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 6) SHEET A-2:
 LOBBY/ CLASSROOM (1) FIRE RATED PARTION
 RATING NOT GIVEN?
  
 7)- WHERE (2) TWO OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.SEE CLASS-
 ROOM #1 ?
  
 8) WHAT USAGE WILL THE UNDIFINED AREA
 HAVE? IF NOT KNOWN THE WALL BETWEEN THE
 LOUNGE (A-2) SMALL ASSEMBLY SHALL BE
 2 HRS. MIXED OCC. TABLE 704.1
  
 9)- 1012.1.2 EGRESS DOORS SHAALL BE SIDE
 SWINGING TYPE. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS FOR THE FOLLOWING:
 (1) WHEN SERVING AN OCCUPANT LOAD OF 50
 OR MORE, SEE LOUNGE DOOR# 6.
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-07-30 Cont ID  
Sent By btrobaug Date 2002-07-30 Time 17:24 Rev Time 0.00
Received By btrobaug Date 2002-07-30 Time 17:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-24 Cont ID  
Sent By btrobaug Date 2002-06-24 Time 11:29 Rev Time 0.00
Received By btrobaug Date 2002-06-24 Time 11:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-06 Cont ID  
Sent By dpalmer Date 2002-05-06 Time 19:58 Rev Time 0.00
Received By dpalmer Date 2002-05-06 Time 19:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-06-07 Cont ID  
Sent By mcarsill Date 2002-06-07 Time 11:05 Rev Time 0.00
Received By mcarsill Date 2002-06-07 Time 11:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 11:15 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 11:14 Sent To  
Notes
2002-05-17 00:00:00THIS OFFICE HAS THE SAME PLAN REVIEW
 COMMENTS AS CONSTRUCTION SERVICES.
 PLEASE ANSWER ALL PLAN REVIEW COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-07 Cont ID  
Sent By pkrauss Date 2002-06-06 Time 16:25 Rev Time 0.45
Received By pkrauss Date 2002-06-06 Time 16:19 Sent To  
Notes
2002-06-06 00:00:00PROVISO:
  
 PLEASE CLARIFY "INTERMITTENT" OCCUPANCY
 ON THE OUSIDE AIR SCHEDULE."LESS THAN
 3 HOURS" DOES THIS MEAN FOR THE ENTIRE
 DAY OR WILL THERE BE ANOTHER CLASS
 SCHEDULED AT A LATER TIME IN THE DAY?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-20 Cont ID  
Sent By pkrauss Date 2002-05-20 Time 13:33 Rev Time 0.50
Received By pkrauss Date 2002-05-20 Time 13:14 Sent To  
Notes
2002-05-20 00:00:00******************DENIED****************
  
 UNDER THE PROVISIONS OF CHAPTER 471.003
 #2(H) - #1 & 1(C) IF JOB EXCEEDS $50,000
 OR AIR CONDITIONING SYSTEM EXCEEDS A 15
 TON SYSTEM CAPACITY OR IF THE PROJECT
 IS DESIGNED TO ACCOMMODATE MORE THAN
 100 PEOPLE, SHALL BE AN ENGINEERED
 SYSTEM.
  
 UNDER THE PROVISIONS OF CHAPTER 471.025,
 PLANS SHALL BE SIGNED BY THE REGISTRANT,
 DATED, AND SEALED.
  
 PLEASE INDICATE ALL FIRE DAMPERS ON PLAN
 AS PER 2001 FBC(M) 607.6
  
 INDICATE RATED WALLS ON PLAN (SEE
 BUILDING PLAN REVIEW COMMENTS).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-05 Cont ID  
Sent By kstevens Date 2002-06-05 Time 18:48 Rev Time 0.00
Received By kstevens Date 2002-06-05 Time 18:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-11 Cont ID  
Sent By kstevens Date 2002-05-11 Time 14:10 Rev Time 0.00
Received By kstevens Date 2002-05-11 Time 14:10 Sent To  
Notes
2002-05-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) RECALCULATION OF MINIMUM FACILITIES
 IS REQUIRED. NORTH SIDE IS MIXED OCCUP-
 ANCY, PART BUSINESS AND PART EDUCATIONAL
 PLEASE INDICATE WHICH AREAS ARE BUSINESS
 RELATED AND WHICH AREAS ARE EDUCATION
 RELATED AND GIVE SQUARE FOOTAGE OF EACH.
 SOUTH SIDE IS EDUCATIONAL OCCUPANCY
 WHICH IN FBC TABLE 1003.1 INDICATES 20
 NET SHALL APPLY. SEE FOOTNOTES #2 & 3
 2) SHTS A1 & A2, IN MENS AND WOMENS TOI-
 LET ROOMS THE TURNING RADIUS SHALL BE
 IN TOILET ROOMS NOT STALLS. PLEASE SHOW
 TURNING RADIUS IN TOILET RMS. 11-4.22.3
 3) SHT A5 DETAIL #8, PLEASE SHOW KNEE
 CLEARANCE 11-4.24.3, CLEAR FLOOR SPACE
 11-4.24.5, EXPOSED PIPES AND SURFACES
 11-4.24.6 ON DETAIL.
 4) WATER RISER DIAGRAM REQUIRED. AIR
 CHAMBERS ARE NOT APPROVED. WATER HAMMER
 ARRESTORS ARE REQUIRED FOR QUICK CLOSING
 VALVES. IF INSTALLED THEY SHALL BE LOCA-
 TED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT AT TOP OF DROP.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377