Plan Review Details - Permit 02041319
Plan Review Stops For Permit 02041319
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-04-30 Cont ID  
Sent By mcarsill Date 2002-04-30 Time 10:54 Rev Time 0.00
Received By mcarsill Date 2002-04-30 Time 10:54 Sent To  
Notes
2002-04-30 00:00:001) SMOKE DETECTORS ARE TO BE INSTALLED
 A MINIMUM OF AT LEAST THREE FEET FROM
 AIR HANDLING DIFFUSERS.
 2) THE EXISTING FIRE ALARM SYSTEM FOR
 THE BUILDING IS TO REMAIN IN SERVICE
 UNTIL THE NEW SYSTEM IS INSTALLED,
 TESTED AND APPROVED BY THE FIRE RESCUE
 DEPARTMENT.
 3) PLEASE INDICATE WHAT VOICE EVACUATION
 MESSAGE IS PLANNED FOR THE BUILDING.
 THE SPEC BOOKS INDICATE TWO STANDARD
 MESSAGES FOR THE DIGITAL MESSAGE MODULE.
 THIS INFORMATION IS TO BE PROVIDED IN
 WRITING.
 4) ANY AND ALL FIRE WALL OR FLOOR
 PENETRATIONS ARE TO BE SEALED IN AN
 APPROVED MANNER.
 5) THE NEW FIRE ALARM SYSTEM IS TO BE
 MONITORED BY LICENSED UL LISTED CENTRAL
 STATION APPROVED BY THE FIRE RESCUE
 DEPARTMENT.
 6) SMOKE DETECTORS ARE MISSING IN THE
 VESTIBULES OF THE TRASH CHUTE ROOMS
 ON PAGE FA-3.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910