Plan Review Details - Permit 02041267
Plan Review Stops For Permit 02041267
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-17 Cont ID  
Sent By dpalmer Date 2002-06-17 Time 13:08 Rev Time 0.00
Received By dpalmer Date 2002-06-17 Time 13:08 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-23 Cont ID  
Sent By rbrown Date 2002-06-12 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2002-05-23 Time 11:30 Sent To M
Notes
2002-05-23 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT ONLY ONE SET
 HAS A E-SHEET FOR MODEL "D". OTHER SET
 HAS TWO E MODEL SHEETS.
  
 2)NOTE: PLEASE NOTE POOL PANEL NOTES
 MOSTLY THE SAME A MODEL "B" COMMENTS.
 PLEASE NOTE ON THIS MODEL PUMP IS SHOWN
 AS 2P-30 AND PANEL IS SHOWN AS 2P-25
 ON MAIN PANEL SCHEDULE. PLEASE NOTE
 THIS NEEDS TO CORRELATE WITH RISER
 DIAGRAM. PLEASE ALSO NOTE THAT #6 AWG
 SHOWN WILL NOT FIT UNDER 2P30A OR 2P-25
  
 PLEASE SEE THE ABOVE NOTES AND SUBMIT
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-06-27 Cont ID  
Sent By pkrauss Date 2002-06-27 Time 09:16 Rev Time 0.30
Received By pkrauss Date 2002-06-27 Time 09:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-06-18 Cont ID  
Sent By rbrown Date 2002-06-27 Time 08:34 Rev Time 0.35
Received By pkrauss Date 2002-06-18 Time 08:12 Sent To Z
Notes
2002-06-18 00:00:00MODEL "D"
  
 PLEASE PROVIDE MANUAL J CALCS
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-28 Cont ID  
Sent By dpalmer Date 2002-06-17 Time 13:08 Rev Time 0.50
Received By pkrauss Date 2002-05-28 Time 09:24 Sent To  
Notes
2002-05-28 00:00:002001 FLORIDA BUILDING CODE - MODEL D
  
 SHOW COMPLIANCE WITH 2001 FBC(M) 402.2.1
 OR TABLE 403.3.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 PRESSURE DIFFERNTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001" WC OR
 LESS. PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE
 ZONE TO THE LOW ZONE.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 PLEASE NOTE IF DRYERS ARE GAS, SHOW
 COMPLIANCE WITH 2001 FBC(M) 702.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-16 Cont ID  
Sent By kstevens Date 2002-05-16 Time 14:13 Rev Time 0.00
Received By kstevens Date 2002-05-16 Time 14:13 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-06-27 Cont ID  
Sent By rbrown Date 2002-06-27 Time 08:24 Rev Time 0.00
Received By rbrown Date 2002-06-27 Time 08:24 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-06-12 Cont ID  
Sent By rbrown Date 2002-06-12 Time 15:17 Rev Time 0.00
Received By rbrown Date 2002-06-12 Time 15:17 Sent To E
Notes
2002-06-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/4/02:
  
 2) FBC 1606.2.2.1WIND PRESSURE.THE
 VELOCITY PRESSURE STATED ON GENERAL
 NOTES SHEET G1, AS 24.7PSF, DOES NOT
 CORRELATE TO THE CALCULATED VELOCITY
 PRESSURE OF 29.85PSF.AMEND SHEET G1.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-04 Cont ID  
Sent By rbrown Date 2002-06-04 Time 20:36 Rev Time 0.00
Received By rbrown Date 2002-06-04 Time 20:36 Sent To  
Notes
2002-06-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.1.2THE SUBMITTED COPY OF
 ROOF FRAMING PLAN A-05 HAS BEEN
 REPRODUCED SUCH THAT THE UPLIFT MARKERS
 AT THE LEFT EDGE HAVE BEEN TRUNCATED
 AND ARE THEREFOR ILLEGIBLE.SUBMIT A
 COMPLETE COPY.
  
 2) FBC 1606.2.2.1THE DESIGN WIND
 PRESSURES, ON THE ROOF FRAMING PLAN AND
 GENERAL NOTES SHEET G1, HAVE BEEN
 UNDERESTIMATED (REF FBC TABLE 1606.2B).
 AMEND THE PRESSURES AND UPLIFTS AND
 RESPECIFY THE TRUSS ANCHORS AS NECESSARY
 TO DEMONSTRATE COMPLIANCE.
  
 3) THE ATRIUM DOOR PRODUCT APPROVAL
 NOTICE OF ACCEPTANCE NO. 01-0209.02
 EXPIRED PRIOR TO THE DATE OF APPLICATION
 SUBMIT A CURRENT PRODUCT APPROVAL.
  
 4) FIXED GLASS WINDOW PRODUCT APPROVAL
 NOTICE OF ACCEPTANCE NO. 00-0512.02.
 THE ASSOCIATED DRAWING SHEETS HAVE BEEN
 UNNECESSARILY REDUCED DURING THE
 COPYING PROCESS AND ARE NOT PROPERLY
 LEGIBLE.SUBMIT LEGIBLE COPIES.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop Z ZONING
Rev No 2 Status N Date 2002-06-18 Cont ID  
Sent By pkrauss Date 2002-06-18 Time 08:38 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2002-06-18 00:00:00NO ZONING REVIEW FOR A MASTER PERMIT

Review Stop Z ZONING
Rev No 1 Status F Date 2002-04-26 Cont ID  
Sent By pkrauss Date 2002-06-18 Time 08:24 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-04-26 00:00:00NEED APP PLAT


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved