Plan Review Stops For Permit 02041257 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-06-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-06-17 |
Time |
07:53 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-06-17 |
Time |
07:53 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-05-23 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-06-12 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-05-23 |
Time |
06:46 |
Sent To |
M |
|
Notes |
2002-05-23 00:00:00 | *************** UNSAT ************* | | | | 1)NOTE: PLEASE NOTE RISER DIAGRAM IS | | SHOWING A SEPARATE POOL PANEL DISC? | | PLEASE NOTE POOL PANEL IS SHOWN ON MAIN | | PANEL SCHEDULE ALONG WITH POOL PUMP | | COMING FROM MAIN PANEL ALSO? PLEASE | | NOTE POOL PANEL BEING SHOWN RIGHT NEXT | | TO MAIN PANEL. IF POOL PUMP IS COMING | | FROM MAIN PANEL, POOL PANEL IS FOR??? | | | | 2)NOTE: PLEASE NOTECONDUCTORS TO | | POOL PANEL NEED TO HAVE 2 HOTS,1-NEUTRAL | | AND AN EQUIPMENT GROUNDING CONDUCTOR | | WHICH IS NOT SHOWN??250-122 | | | | | | PLEASE MAKE THE CORRECTIONS. IF THERE | | ARE ANY CHANGES, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | | | | | *** PLEASE ALSO NOTE THAT THAT COVER | | SHEETS REF."LATEST EDITION OF NEC" | | PLEASE NOTE THIS NEEDS TO SHOW "99" | | THE "LATEST" EDITION WOULD MEAN 2002 NEC |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
N |
Date |
2002-06-27 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-28 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2002-06-27 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-27 |
Time |
09:14 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2002-06-27 |
Time |
08:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2002-06-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-06-27 |
Time |
08:31 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-06-18 |
Time |
07:33 |
Sent To |
Z |
|
Notes |
2002-06-18 00:00:00 | MODEL "B" | | | | 2ND REQUEST | | MANUAL J CALCS NOT SUBMITTED - ENERGY | | CALCS INDICATE A 4 TON UNIT & PLAN | | SHOWS A 3.5 TON UNIT. | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-05-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-05-23 |
Time |
12:51 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2002-05-28 |
Time |
07:54 |
Sent To |
R |
|
Notes |
2002-05-28 00:00:00 | 2001 FLORIDA BUILDING CODE- MODEL B | | | | ENERGY CALCS INDICATE A 4 TON UNIT, | | PLANS INDICATE A 3.5 TON UNIT. | | | | SHOW COMPLIANCE WITH 2001 FBC(M) 402.2.1 | | OR TABLE 403.3. | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | PRESSURE DIFFERNTIALS ACROSS CLOSED | | DOORS WHERE RETURNS ARE CENTRALLY | | LOCATED SHALL BE LIMITED TO .001" WC OR | | LESS. PROVIDE AIR DUCT PATHWAYS OR AIR | | TRANSFER PATHWAYS FROM THE HIGH PRESSURE | | ZONE TO THE LOW ZONE. | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | PLEASE NOTE IF DRYERS ARE GAS SHOW | | COMPLIANCE WITH 2001 FBC(M) 702. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-05-16 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-16 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-16 |
Time |
14:11 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
P |
Date |
2002-06-27 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-06-27 |
Time |
08:31 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-06-27 |
Time |
08:30 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2002-06-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-06-12 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-06-12 |
Time |
14:40 |
Sent To |
E |
|
Notes |
2002-06-12 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | ARE NUMBERED AS PER THE BUILDING PLAN | | REVIEW OF 6/4/02: | | | | 2) FBC 1606.2.2.1WIND PRESSURE.THE | | VELOCITY PRESSURE STATED ON GENERAL | | NOTES SHEET G1, AS 24.7PSF, DOES NOT | | CORRELATE TO THE CALCULATED VELOCITY | | PRESSURE OF 29.85 PSF.AMEND SHEET G1. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2002-06-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-28 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-06-04 |
Time |
20:00 |
Sent To |
|
|
Notes |
2002-06-04 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | 1) FBC* 104.2.1.2THE TRUSS DESIGN | | CALCULATIONS AND SHOP DRAWINGS HAVE NOT | | BEEN SIGNED AND SEALED. | | | | 2) FBC 1606.2.2.1THE DESIGN WIND | | PRESSURES, ON THE ROOF FRAMING PLAN AND | | GENERAL NOTES SHEET G1, HAVE BEEN | | UNDERESTIMATED (REF FBC TABLE 1606.2B). | | AMEND THE PRESSURES AND UPLIFTS AND | | RESPECIFY THE TRUSS ANCHORS AS NECESSARY | | TO DEMONSTRATE COMPLIANCE. | | | | 3) THE ATRIUM DOOR PRODUCT APPROVAL | | NOTICE OF ACCEPTANCE NO. 01-0209.02 | | EXPIRED PRIOR TO THE DATE OF APPLICATION | | SUBMIT A CURRENT PRODUCT APPROVAL. | | | | 4) FIXED GLASS WINDOW PRODUCT APPROVAL | | NOTICE OF ACCEPTANCE NO. 00-0512.02. | | THE ASSOCIATED DRAWING SHEETS HAVE BEEN | | UNNECESSARILY REDUCED DURING THE | | COPYING PROCESS AND ARE NOT PROPERLY | | LEGIBLE.SUBMIT LEGIBLE COPIES. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
N |
Date |
2002-06-18 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-18 |
Time |
08:35 |
Rev Time |
0.05 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-06-18 00:00:00 | NO ZONING REVIEW FOR A MASTER PERMIT |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2002-04-26 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-18 |
Time |
07:56 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|