Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-03 Cont ID  
Sent By btrobaug Date 2002-07-03 Time 13:48 Rev Time 0.00
Received By btrobaug Date 2002-07-03 Time 13:13 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-01 Cont ID  
Sent By btrobaug Date 2002-05-01 Time 06:20 Rev Time 0.00
Received By btrobaug Date 2002-05-01 Time 06:14 Sent To P
Notes
2002-05-01 00:00:00~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATIONAND MAKE ANY NECESSARY
 CHANGES TO THE PLANS AND RESUBMIT FOR
 REVIEW:
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 2} PLEASE NOTE MISSING DISCONNECT
 FOR A/C CONDENSOR,MUST CONFORM TO
 440-14NEC.
  
 3}PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.(TITLE
 BLOCK).
  
 4}PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
  
 5} RECEPTACLE SPACING TO COMPLY WITH ART
 ICLE 210-52(A).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2002-07-03 Cont ID  
Sent By ndenmark Date 2002-07-03 Time 14:03 Rev Time 0.33
Received By ndenmark Date 2002-07-03 Time 14:03 Sent To  
Notes
2002-07-03 00:00:00NOTE ON RESUB FROMA W PROVO SAYS
 MECHANICAL CONTRACTOR TO SUBMIT
 MECHANICAL PLANS WITH PERMIT APPLICATION

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-07-03 Cont ID  
Sent By btrobaug Date 2002-07-03 Time 13:48 Rev Time 0.33
Received By ndenmark Date 2002-04-23 Time 18:32 Sent To  
Notes
2002-07-03 00:00:00RESUB PLANS INDICATE MECHANICAL
 CONTRACTOR TO PROVIDE PLANS AT TIME OF
 MECHANICAL PERMIT APPLICATION.
2002-04-23 00:00:00PLAN DENIED
 PLANS ARE NOT STAMPED BY ENGINEER.
 REFER TO SECTION 402 OR 403 2001 FLORIDA
 BUILDING CODE.REFER TO SECTION 601.4
 2001 FBC.
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-02 Cont ID  
Sent By jleech Date 2002-07-02 Time 19:49 Rev Time 0.25
Received By jleech Date 2002-07-02 Time 19:49 Sent To  
Notes
2002-07-02 00:00:00RESTAMP PLUMBING PLANS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-06 Cont ID  
Sent By btrobaug Date 2002-05-01 Time 06:59 Rev Time 0.33
Received By jleech Date 2002-05-06 Time 17:57 Sent To  
Notes
2002-05-06 00:00:00DENIED;
 1.RISER DIAGRAM REQUIRED SHOWING ALL
 PIPE SIZES AND VENTS.
 2.CLOTHES WASHER CONNECTION REQUIRED
 PER FBC PLUMBING TABLE 403.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-07-08 Cont ID  
Sent By hpiskura Date 2002-07-08 Time 10:21 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-05 Cont ID  
Sent By hpiskura Date 2002-06-05 Time 07:34 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
2002-06-05 00:00:00BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 METRO DADE NOA 98-1110.06 IS EXPIRED.
  
 THE TRUSSES ARE DESIGNED TO THE 1997
 STANDARD BUILDING CODE, THEY ARE
 REQUIRED TO COMPLY WITH THE 2001 FBC.
 PLEASE REVISE AS NECESSARY.
  
 THE ENGINEER OF RECORD IS REQUIRED TO
 REVIEW THE DELEGATED DESIGN AREAS SUCH
 AS THE TRUSSES AND THE PRE-CAST WALL
 SYSTEM.PROVIDE DOCUMENTATION THAT THIS
 HAS BEEN DONE.
  
 THE ROYALL WALL PLANS DO NOT INDICATE
 THE SPECIFIC PROJECT OR CALCULATIONS.
 SEE RULE 61G15-31 OF THE FAC.
  
 THE ROYALL WALL PLANS DO NOT REFLECT
 THE DESIGN CRITERIA OF ACI 318-99 IN
 ACCORDANCE WITH FBC 1918.1 OR THE WIND
 DESIGN INFORMATION AS PROVIDED FOR IN
 FBC 1606.
  
 THE ENGINEER OF RECORD HAS NOT
 SPECIFIED ANY DESIGN CRITERIA FOR THE
 DELEGATED ENGINEERING DESIGN AS
 PROVIDED FOR IN 61G15-30.IN FACT, THE
 PLANS SHEETS ARE NOT EVEN NUMBERED.SEE
 ALSO, 61G15-30.003 RE: DOCUMENT
 CLASSIFICATION
  
 PROVIDE FOR TERMITE PROTECTION IN
 ACCORDANCE WITH FBC 1816.1.7.
  
 SHOW THE INTERNAL PRESSURE COEFFICIENT
 AND COMPONENT & CLADDING PRESSURES FOR
 THE ROOF COVERING.SEE FBC 1606.1.7.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-05 Cont ID  
Sent By hpiskura Date 2002-07-08 Time 07:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***