Plan Review Details - Permit 02041152
Plan Review Stops For Permit 02041152
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-01 Cont ID  
Sent By bstaples Date 2002-07-01 Time 14:18 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-24 Cont ID  
Sent By hpiskura Date 2002-05-24 Time 09:52 Rev Time 0.00
Received By hpiskura Date   Time   Sent To P
Notes
2002-05-15 00:00:00PASSED BY HAROLD PISKURA ON 5-18-02.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-11 Cont ID  
Sent By dpalmer Date 2002-06-11 Time 15:12 Rev Time 0.00
Received By dpalmer Date 2002-06-11 Time 15:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-30 Cont ID  
Sent By dpalmer Date 2002-04-30 Time 06:16 Rev Time 0.00
Received By dpalmer Date 2002-04-30 Time 06:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-02 Cont ID  
Sent By mcarsill Date 2002-07-02 Time 10:41 Rev Time 0.00
Received By mcarsill Date 2002-07-02 Time 10:41 Sent To  
Notes
2002-07-02 00:00:001) LOCKING DEVICES ON EXIT DOORS TO
 COMPLY WITH ACCESS CONTROLLED OR
 DELAYED EGRESS PER THE LIFE SAFETY
 CODE, 2000 EDITION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-15 Cont ID  
Sent By mcarsill Date 2002-05-15 Time 13:02 Rev Time 0.00
Received By mcarsill Date 2002-05-15 Time 13:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-11 Cont ID  
Sent By pkrauss Date 2002-06-11 Time 10:35 Rev Time 0.40
Received By pkrauss Date 2002-06-11 Time 10:35 Sent To  
Notes
2002-06-11 00:00:00MECHANICAL PERMIT 02041161

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-07 Cont ID  
Sent By pkrauss Date 2002-05-07 Time 08:29 Rev Time 0.40
Received By pkrauss Date 2002-05-07 Time 08:05 Sent To  
Notes
2002-05-07 00:00:00MECHANICAL PERMIT 02041161
  
 PROVISO:PLAN SHEET P2.1
  
 CONDENSATE SHALL DISCHARGE 12" AWAY FROM
 THE BUILDING STRUCTURE AS PER 2001 FBC
 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-07-16 Cont ID  
Sent By pschmitz Date 2002-07-16 Time 11:21 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-07-16 00:00:00PLUMBING PLAN REVIEW REVISION, APPR PES
 `

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-06-28 Cont ID  
Sent By kstevens Date 2002-06-28 Time 10:48 Rev Time 0.00
Received By kstevens Date 2002-06-28 Time 10:48 Sent To  
Notes
2002-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT P2.1 WATER RISER DIAGRAM. SHOW
 WATER HAMMER ARRESTORS LOCATED NEAR FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT AT TOP
 OF DROPS AS SHOWN. (PER PROVISO)
 2) SHT P2.1 PLEASE INDICATE A HI/LOW
 DRINKING FOUNTAIN OR CUP DISPENSER FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING AS REQUIED IN SECTION 4.1.3(10)
 CHAPTER 11. (PER PROVISO)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-24 Cont ID  
Sent By hpiskura Date 2002-05-24 Time 09:52 Rev Time 0.00
Received By kstevens Date 2002-05-24 Time 08:58 Sent To  
Notes
2002-05-24 00:00:00PASSED/PROVISO
  
 1) CUP DISPENSOR REQUIRED FOR DRINKING
 FOUNTAIN FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING. 4.1.3(10)
 2) WATER HAMMER ARRESTORS SHALL BE LO-
 CATED NEAR FIXTURES NOT AT TOP OF DROP.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-11 Cont ID  
Sent By kstevens Date 2002-05-11 Time 12:11 Rev Time 0.00
Received By kstevens Date 2002-05-11 Time 12:11 Sent To  
Notes
2002-05-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BLDG CHAPTER 11
  
 1) SHTS A-1 & P-2.1 DOOR SHALL NOT OPEN
 INTO CLEAR FLOOR SPACE OF AND ACCESSIBLE
 FIXTURE.
 2) FBC PLMG TABLE REQUIRES A DRINKING
 FOUNTAIN & AND A SERVICE SINK. PLEASE
 PROVIDE REQUIRED FIXTURES.
 3) SHT P0.1 PLUMBING NOTES #23, CONDEN-
 SATE LINES AS SHOWN ON SHT P2.1 FBC SEC
 1503.4.4 REQUIRES THAT DISCHARGE FROM
 CONDENSATE BE MINIMUM OF 12" FROM BLDG.
 4) SHT PO.1 PLUMBING NOTES #13 AIR CHAM-
 BERS NOT APPROVED, DELETE REFERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377