Plan Review Stops For Permit 02041062 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-07-09 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-07-09 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-07-09 00:00:00 | PERMIT PROVISIONS: | | | | SHOP DRAWINGS FOR THE STAIR HANDRAILS | | MUST BE PROVIDED BEFORE CONSTRUCTION, | | SHOWING MATERIAL, DIMENSIONS AND | | FASTENING METHODS. | | | | A STAIR CONSTRUCTION DETAIL INCLUDING | | STRINGERS, TREADS, RISERS, AND LANDING. | | SHOW DIMENSIONS, MATERIAL AND | | FASTENINGS. | | | | A CONSTRUCTION DETAIL FOR THE SECOND | | FLOOR BALCONY GUARD RAIL. | | | | CONSTRUCTION DETAILS FOR THE TRELLIS TO | | BE LOCATED AT THE FRONT OF THE GARAGE. | | | | SAFETY GLAZING FOR WINDOW SHOWN AS | | (22) AT THE BATH. SHEET A2. | | | | A GUARD RAIL AT WINDOW SHOWN AS (21) IN | | THE STAIR WALL.FBC 1015.1. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2003-01-24 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-01-24 |
Time |
12:20 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2003-01-24 |
Time |
11:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-06-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-23 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-06-25 |
Time |
06:44 |
Sent To |
R |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-05-21 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-05-21 |
Time |
09:55 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-05-21 |
Time |
07:28 |
Sent To |
R |
|
Notes |
2002-05-21 00:00:00 | UNSAT! | | ~~~~~~ | | | | PLLEASE PROVIDE THE FOLLOWING | | INFORMATION,MAKE ANY NECESSARY CHANGES | | TO PLANS AND RESUBMIT FOR REVIEW: | | | | 1} PLEASE NOTE THAT THERE IS AN | | ENGINEERS SEAL WITHOUT A TITLE BLOCK ON | | SHEETS S-1 THROUGH S-6,FS/FAC 471-025. | | | | 2} INDICATE FEEDER CONDUCTOR SIZE TO | | "P"PANEL,AND CONDUIT TYPE AND SIZE.(IS | | A TAP RULE BEING USED FOR THIS FEEDER | | AND IF SO INDICATE WHICH ONE). | | | | 3} NOTE THE PHASES ON THE PANEL SCHEDULE | | ARE MARKED "A" & "C" INSTEAD OF "A"&"B" | | | | 4} PANEL "P" AMPS PER PHASE ARE LARGER | | THAN THE OCP. | | | | 5} PANEL "B" AMPS PER PHASE APPEAR TO BE | | INCORRECT. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT. 8392 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-01-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-23 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-01-23 |
Time |
11:49 |
Sent To |
E |
|
Notes |
2003-01-23 00:00:00 | TO BILL T'S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2002-11-26 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-26 |
Time |
17:34 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-11-26 |
Time |
17:34 |
Sent To |
P |
|
Notes |
2002-11-26 00:00:00 | IN BOX./WRT. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2002-12-19 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-12-19 |
Time |
15:29 |
Rev Time |
0.20 |
Received By |
pkrauss |
Date |
2002-12-19 |
Time |
15:29 |
Sent To |
|
|
Notes |
2002-12-19 00:00:00 | MECHANICAL PERMIT 02102214 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2002-12-09 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-12-09 |
Time |
16:45 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2002-12-09 |
Time |
16:45 |
Sent To |
|
|
Notes |
2002-12-09 00:00:00 | DENIED:MECHANICAL PERMIT 02102214 | | | | PLANS SUBMITTED DO NOT HAVE ENGINEER | | SEAL OR SIGNATURE.PLANS WERE APPROVED | | WITH ENGINEERED DRAWINGS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-05-18 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-05-18 |
Time |
12:16 |
Rev Time |
1.00 |
Received By |
hmoser |
Date |
2002-05-18 |
Time |
13:39 |
Sent To |
|
|
Notes |
2002-05-18 00:00:00 | PRIVISO | | #1 VARIFY TYPE OF VENTILATION USED | | [FRESH AIR]NATURAL 402 OR | | MECHANICAL 403 | | #2 NEED CALCULATIONS FOR TYPE OF | | VANTILATION USED | | #3 REFER TO SECTION 601.4 BALANCED | | RETURN AIR | | #4 CONDENSATE DRAIN MUST TERMINATE | | 12IN.FROM BUILDING 1503.4.4 | | #5 NEED MANUFACTURER'S INSTRUCTIONS | | ON COOKTOP | | #6 NEED RETURN AIR SIZES | | #7 MEED PRESSURE TEST ON REFRIGERANT | | LINES SECTION 1108 | | #8 ALL REFRIGERANT PIPING UNDER SLAB | | SHALL BE INCASED IN PIPE DUCT 1107.2. | | CALL FOR INSPECTIONPRIER TO COVERING | | PIPE SLEEVE WITH DIRT | | PLAN REVIEW BY HAROLD MOSER | | [561]659-8096 EXT 8390 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-05-11 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-26 |
Time |
17:34 |
Rev Time |
0.75 |
Received By |
jleech |
Date |
2002-05-11 |
Time |
12:38 |
Sent To |
|
|
Notes |
2002-05-11 00:00:00 | PROVISO; | | PLUMBING PERMIT ONLY, NO GAS. GAS TO BE | | INSTALLED BY LICENSED GAS CONTRACT. | | PLANS REQUIRED AT TIME OF PERMIT APPLI- | | CATION. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8369 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2002-07-10 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-07-10 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2002-06-03 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-06-25 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-06-03 00:00:00 | BEFORE A PERMIT TO CONSTRUCT MAY BE | | ISSUED, IMPACT FEES MUST BE PAID TO THE | | COUNTY FOR THE CITY, THE PERMIT PLANS | | STAMPED BY THAT OFFICE AND A COPY OF | | THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION.CALL 233-5025 FOR MORE | | INFORMATION. | | | | PROVIDE A DETAIL FOR THE STAIR | | HANDRAILS SEE FBC 1007.5 | | | | SHOW A DETAIL AND/OR NOTE FOR THE | | EMERGENCY ESCAPE/RESCUE OPENINGS | | (WINDOWS) FOR THE SLEEPING ROOMS.SEE | | FBC 1005.4. | | | | THE WINDOWS SHOWN ON THE EAST ELEVATION, | | SHEET A4 DO NOT AGREE WITH THE FLOOR | | PLAN, SHEET A2.REVISE AS NECESSARY. | | | | SHEET A2 AND S2 DO NOT AGREE AS TO THE | | LAYOUT OF THE SECOND FLOOR BALCONY. | | SHOW A GUARDRAIL, FBC 1015. | | | | PROVIDE A STAIR CONSTRUCTION DETAIL, | | INCLUDING THE LANDINGS. SEE FBC 1007. | | | | SHOW THE METHOD OF ATTIC ACCESS, SEE | | FBC 2309.6. | | | | SHOW A CONNECTION DETAIL FOR THE PATIO | | ROOF FRAMING TO THE LEDGER AND THE BEAM. | | | | SHOW DIMESIONS TO LOCATE THE COLUMNS IN | | THE WALL BETWEEN THE HOUSE AND GARAGE. | | | | WHAT ARE THE THREE 3" COLUMNS IN FRONT | | OF THE GARAGE FOR? | | | | PROVIDE A DOOR AND WINDOWD SCHEDULE. | | | | SHOW SAFETY GLAZING IN THE WINDOWS AND | | DOORS FOR THE REAR PATIO.SEE FBC | | 2405.2. | | | | SHOW A HEADER DETAIL FOR THE FRAME | | OPENING DEPICTED IN 4/S2. | | | | SHEET S4, PLEASE PROVIDE A MORE | | CONTEMPORARY ROOF TRUSS LAYOUT. | | | | PROVIDE TWO SETS OF LEGIBLE PRODUCT | | APPROVALS FOR THE DOORS, WINDOWS AND | | ROOR COVERING.ALTERNATIVELY, A | | SEPARATE PERMIT AND FEES WILL BE | | REQUIRED IF THE INFORMATION IS NOT | | INCLUDED WITH THIS PERMIT APPLICATION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2002-05-07 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-05-07 |
Time |
08:45 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2002-04-26 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-04-26 |
Time |
11:49 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-26 00:00:00 | NEED SITE PLAN |
|
|