Plan Review Details - Permit 02041062
Plan Review Stops For Permit 02041062
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-07-09 Cont ID  
Sent By hpiskura Date 2002-07-09 Time 10:14 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-07-09 00:00:00PERMIT PROVISIONS:
  
 SHOP DRAWINGS FOR THE STAIR HANDRAILS
 MUST BE PROVIDED BEFORE CONSTRUCTION,
 SHOWING MATERIAL, DIMENSIONS AND
 FASTENING METHODS.
  
 A STAIR CONSTRUCTION DETAIL INCLUDING
 STRINGERS, TREADS, RISERS, AND LANDING.
 SHOW DIMENSIONS, MATERIAL AND
 FASTENINGS.
  
 A CONSTRUCTION DETAIL FOR THE SECOND
 FLOOR BALCONY GUARD RAIL.
  
 CONSTRUCTION DETAILS FOR THE TRELLIS TO
 BE LOCATED AT THE FRONT OF THE GARAGE.
  
 SAFETY GLAZING FOR WINDOW SHOWN AS
 (22) AT THE BATH. SHEET A2.
  
 A GUARD RAIL AT WINDOW SHOWN AS (21) IN
 THE STAIR WALL.FBC 1015.1.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-01-24 Cont ID  
Sent By btrobaug Date 2003-01-24 Time 12:20 Rev Time 1.00
Received By btrobaug Date 2003-01-24 Time 11:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-25 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 11:49 Rev Time 0.00
Received By btrobaug Date 2002-06-25 Time 06:44 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-21 Cont ID  
Sent By btrobaug Date 2002-05-21 Time 09:55 Rev Time 0.00
Received By btrobaug Date 2002-05-21 Time 07:28 Sent To R
Notes
2002-05-21 00:00:00UNSAT!
 ~~~~~~
  
 PLLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO PLANS AND RESUBMIT FOR REVIEW:
  
 1} PLEASE NOTE THAT THERE IS AN
 ENGINEERS SEAL WITHOUT A TITLE BLOCK ON
 SHEETS S-1 THROUGH S-6,FS/FAC 471-025.
  
 2} INDICATE FEEDER CONDUCTOR SIZE TO
 "P"PANEL,AND CONDUIT TYPE AND SIZE.(IS
 A TAP RULE BEING USED FOR THIS FEEDER
 AND IF SO INDICATE WHICH ONE).
  
 3} NOTE THE PHASES ON THE PANEL SCHEDULE
 ARE MARKED "A" & "C" INSTEAD OF "A"&"B"
  
 4} PANEL "P" AMPS PER PHASE ARE LARGER
 THAN THE OCP.
  
 5} PANEL "B" AMPS PER PHASE APPEAR TO BE
 INCORRECT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-23 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 11:49 Rev Time 0.00
Received By dpalmer Date 2003-01-23 Time 11:49 Sent To E
Notes
2003-01-23 00:00:00TO BILL T'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-26 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 17:34 Rev Time 0.00
Received By btrobaug Date 2002-11-26 Time 17:34 Sent To P
Notes
2002-11-26 00:00:00IN BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-19 Cont ID  
Sent By pkrauss Date 2002-12-19 Time 15:29 Rev Time 0.20
Received By pkrauss Date 2002-12-19 Time 15:29 Sent To  
Notes
2002-12-19 00:00:00MECHANICAL PERMIT 02102214

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-12-09 Cont ID  
Sent By pkrauss Date 2002-12-09 Time 16:45 Rev Time 0.25
Received By pkrauss Date 2002-12-09 Time 16:45 Sent To  
Notes
2002-12-09 00:00:00DENIED:MECHANICAL PERMIT 02102214
  
 PLANS SUBMITTED DO NOT HAVE ENGINEER
 SEAL OR SIGNATURE.PLANS WERE APPROVED
 WITH ENGINEERED DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-18 Cont ID  
Sent By hmoser Date 2002-05-18 Time 12:16 Rev Time 1.00
Received By hmoser Date 2002-05-18 Time 13:39 Sent To  
Notes
2002-05-18 00:00:00PRIVISO
 #1 VARIFY TYPE OF VENTILATION USED
 [FRESH AIR]NATURAL 402 OR
 MECHANICAL 403
 #2 NEED CALCULATIONS FOR TYPE OF
 VANTILATION USED
 #3 REFER TO SECTION 601.4 BALANCED
 RETURN AIR
 #4 CONDENSATE DRAIN MUST TERMINATE
 12IN.FROM BUILDING 1503.4.4
 #5 NEED MANUFACTURER'S INSTRUCTIONS
 ON COOKTOP
 #6 NEED RETURN AIR SIZES
 #7 MEED PRESSURE TEST ON REFRIGERANT
 LINES SECTION 1108
 #8 ALL REFRIGERANT PIPING UNDER SLAB
 SHALL BE INCASED IN PIPE DUCT 1107.2.
 CALL FOR INSPECTIONPRIER TO COVERING
 PIPE SLEEVE WITH DIRT
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-11 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 17:34 Rev Time 0.75
Received By jleech Date 2002-05-11 Time 12:38 Sent To  
Notes
2002-05-11 00:00:00PROVISO;
 PLUMBING PERMIT ONLY, NO GAS. GAS TO BE
 INSTALLED BY LICENSED GAS CONTRACT.
 PLANS REQUIRED AT TIME OF PERMIT APPLI-
 CATION.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-07-10 Cont ID  
Sent By hpiskura Date 2002-07-10 Time 09:39 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By btrobaug Date 2002-06-25 Time 15:45 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-06-03 00:00:00BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY FOR THE CITY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 233-5025 FOR MORE
 INFORMATION.
  
 PROVIDE A DETAIL FOR THE STAIR
 HANDRAILS SEE FBC 1007.5
  
 SHOW A DETAIL AND/OR NOTE FOR THE
 EMERGENCY ESCAPE/RESCUE OPENINGS
 (WINDOWS) FOR THE SLEEPING ROOMS.SEE
 FBC 1005.4.
  
 THE WINDOWS SHOWN ON THE EAST ELEVATION,
 SHEET A4 DO NOT AGREE WITH THE FLOOR
 PLAN, SHEET A2.REVISE AS NECESSARY.
  
 SHEET A2 AND S2 DO NOT AGREE AS TO THE
 LAYOUT OF THE SECOND FLOOR BALCONY.
 SHOW A GUARDRAIL, FBC 1015.
  
 PROVIDE A STAIR CONSTRUCTION DETAIL,
 INCLUDING THE LANDINGS. SEE FBC 1007.
  
 SHOW THE METHOD OF ATTIC ACCESS, SEE
 FBC 2309.6.
  
 SHOW A CONNECTION DETAIL FOR THE PATIO
 ROOF FRAMING TO THE LEDGER AND THE BEAM.
  
 SHOW DIMESIONS TO LOCATE THE COLUMNS IN
 THE WALL BETWEEN THE HOUSE AND GARAGE.
  
 WHAT ARE THE THREE 3" COLUMNS IN FRONT
 OF THE GARAGE FOR?
  
 PROVIDE A DOOR AND WINDOWD SCHEDULE.
  
 SHOW SAFETY GLAZING IN THE WINDOWS AND
 DOORS FOR THE REAR PATIO.SEE FBC
 2405.2.
  
 SHOW A HEADER DETAIL FOR THE FRAME
 OPENING DEPICTED IN 4/S2.
  
 SHEET S4, PLEASE PROVIDE A MORE
 CONTEMPORARY ROOF TRUSS LAYOUT.
  
 PROVIDE TWO SETS OF LEGIBLE PRODUCT
 APPROVALS FOR THE DOORS, WINDOWS AND
 ROOR COVERING.ALTERNATIVELY, A
 SEPARATE PERMIT AND FEES WILL BE
 REQUIRED IF THE INFORMATION IS NOT
 INCLUDED WITH THIS PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 2 Status P Date 2002-05-07 Cont ID  
Sent By sgraham Date 2002-05-07 Time 08:45 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-04-26 Cont ID  
Sent By sgraham Date 2002-04-26 Time 11:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-04-26 00:00:00NEED SITE PLAN