Plan Review Details - Permit 02040979
Plan Review Stops For Permit 02040979
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-20 Cont ID  
Sent By lhatten Date 2002-06-20 Time 11:50 Rev Time 2.50
Received By lhatten Date 2002-06-16 Time 11:49 Sent To  
Notes
2002-06-20 00:00:00REVIEW & STAMPED PLANS 06/16/2002

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-29 Cont ID  
Sent By drunnels Date 2002-05-29 Time 09:39 Rev Time 0.50
Received By drunnels Date   Time   Sent To  
Notes
2002-05-29 00:00:001. GENERAL NOTES STATES SLAB 3000 PSI/
 BEAM/COLUMN 4000 PSI, DETAILS SHOW SLAB
 2500 PSI BEAM/COLUMN 3000 PSI
 2. MEAN ROOF HEIGHTS ON DESIGN PARAMETER
 S DO NOT MATCH TRUSS SHEETS
  
 PER LOU HATTEN

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-12-04 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 14:22 Rev Time 0.50
Received By btrobaug Date 2002-12-04 Time 14:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-07 Cont ID  
Sent By dpalmer Date 2002-06-07 Time 14:05 Rev Time 0.00
Received By dpalmer Date 2002-06-07 Time 14:07 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-07 Cont ID  
Sent By drunnels Date 2002-05-29 Time 09:47 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2002-05-08 00:00:00***************** UNSAT *************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
 PLEASE NOTE MISSING FROM DOWNSTAIRS
 BEDROOM.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING UPSTAIRS BED RM.
  
 4)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SIZE PER 250-66
  
 7))NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 8)NOTE: PLEASE NOTE THAT PER LOCAL
 AMENDMENTS ALL SERVICE ENTRANCE CONDUCT-
 ORS SHALL BE IN A RACEWAY SPECIFIED IN
 230-43.
 PLEASE ALSO NOTE THAT NO ALUM CONDUCTORS
 MAY BE USED SMALLER THAN #2. 310-2
 AND NO ALUM FOR GROUNDING/OR BONDING.
 310-2B 1&2
  
 9)NOTE: PLEASE NOTE MISSING A/C DISC`S
 FOR AHU`S PER 440-11
  
  
  
  
  
  
 11)NOTE: PLEASE NOTE,ELECTRICAL NOTE
 ON PLANS MENTIONS TO PLACE SD`S ON BATH
 AND KITCHEN CIRCUIT? PLEASE CLARIFY
 LIGHTING CIRCUIT??? 210-11-C1/210-11C-3
  
 12)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-13 Cont ID  
Sent By pkrauss Date 2002-06-12 Time 16:03 Rev Time 0.33
Received By hmoser Date 2002-06-13 Time 18:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-06 Cont ID  
Sent By hmoser Date 2002-05-06 Time 18:55 Rev Time 0.50
Received By hmoser Date 2002-05-06 Time 18:55 Sent To  
Notes
2002-05-06 00:00:00PLAN DENIED
 MISSING DUCT'S,AND DUCT SIZE
 NO EQUIPMENT SCHEDULE
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-08 Cont ID  
Sent By dpalmer Date 2002-06-07 Time 14:07 Rev Time 0.33
Received By jleech Date 2002-06-08 Time 10:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-27 Cont ID  
Sent By jleech Date 2002-04-27 Time 06:53 Rev Time 0.00
Received By aneil Date 2002-05-06 Time 13:15 Sent To  
Notes
2002-04-27 00:00:00DENIED;
 1.PLUMBING RISER DIAGRAM. MASTER BATH
 NO MORE THAN 4 FIXTURE UNITS PERMITED
 ON A 2" WET VENT. SIZE OF PIPE TO BE
 3" AFTER TUB. TABLE 909.3.
 NOTES;
 NOTE #3 MINIMUM SLOPE OF PIPE TO COMPLY
 WITH TABLE 704.1. PIPE LESS THAN
 3" SHALL SLOPE AT 1/4".
 NOTE#5 NO FLOOR DRAINS SHOWN ON DRAWING.
 NOTE NOT NEEDED.
 NOTE#6 CONDENSATE IS NOT PERMITED TO
 DUMP INTO SANITARY SEWER SYSTEM
 CITY UTILITY'S REQUIREMENT.
 NOTE#7 WATER HAMMER ARRESTORS ARE
 REQUIRED. SEE SEC. 604.9 FOR
 LOCATIONS REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2002-06-18 Cont ID  
Sent By sgraham Date 2002-06-18 Time 16:08 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-04-24 Cont ID  
Sent By sgraham Date 2002-04-24 Time 09:56 Rev Time 0.00
Received By aneil Date 2002-05-06 Time 13:14 Sent To  
Notes
***NONE***