Plan Review Stops For Permit 02040826 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-05-20 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-05-20 |
Time |
18:51 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-05-20 |
Time |
18:46 |
Sent To |
R |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2002-05-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-05-07 |
Time |
21:12 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-05-07 |
Time |
21:12 |
Sent To |
B |
|
Notes |
2002-05-07 00:00:00 | ****************** UNSAT *************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2 )NOTE: PLEASE LIST THE REQ`D ARC | | FAULT PROTECTEDCIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | 3)NOTE: PLEASE NOTE LOAD OF 5KW FOR | | DRYER ON #12. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-04-25 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-04-25 |
Time |
15:59 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-04-25 |
Time |
15:33 |
Sent To |
P |
|
Notes |
2002-04-25 00:00:00 | | | | | | | | | | | | | | | ~~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~ | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2} PLEASE LIST THE REQ`D ARC | | FAULT PROECTED CIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT.8392 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2002-05-18 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-05-18 |
Time |
10:20 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2002-05-18 |
Time |
10:19 |
Sent To |
|
|
Notes |
2002-05-18 00:00:00 | PROVISO | | #1 VARIFY TYPE OF VENTILATION USED | | [FRESH AIR]NATURAL 402 OR | | MECHANICAL 403 | | #2 NEED CALCULATIONS FOR TYPE OF | | VENTILATION USED | | #3 REFER TO SECTION 601.4 BALANCED | | RETURN AIR | | #4 CONDENSATE DRAIN MUST TERMANATE | | 12IN.FROM BUILDING | | PLAN REVIEW BY HAROLD MOSER | | [561]659-8096 EXT 8390 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2002-05-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-05-06 |
Time |
20:07 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2002-05-06 |
Time |
20:07 |
Sent To |
|
|
Notes |
2002-05-07 00:00:00 | PLAN DENIED | | PLANS NOT STAMPED BY ARCHITECT | | HAROLD MOSER[561]659-8096 EXT 8390 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-04-23 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-04-23 |
Time |
19:55 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2002-04-23 |
Time |
19:55 |
Sent To |
|
|
Notes |
2002-04-23 00:00:00 | PLAN DENIED | | NO ENERGY CALCS OR MANUAL J | | PLAN REVIEW BY HAROLD MOSER | | [561]659-8096 EXT 8390 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-04-27 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-04-25 |
Time |
15:59 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2002-04-27 |
Time |
13:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2002-05-29 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-05-20 |
Time |
18:51 |
Rev Time |
3.00 |
Received By |
lhatten |
Date |
2002-05-25 |
Time |
19:40 |
Sent To |
|
|
Notes |
2002-05-29 00:00:00 | REVIEW & STAMPED PLANS & TRUSS ENG. | | 05/25/2002 | | CALC. FEES & PRINT CARDS 05/29/2002 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-04-22 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-04-22 |
Time |
11:52 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|