Plan Review Details - Permit 02040817
Plan Review Stops For Permit 02040817
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-05-20 Cont ID  
Sent By btrobaug Date 2002-05-20 Time 18:23 Rev Time 0.00
Received By btrobaug Date 2002-05-20 Time 18:22 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-05-07 Cont ID  
Sent By dpalmer Date 2002-05-07 Time 21:03 Rev Time 0.00
Received By dpalmer Date 2002-05-07 Time 21:03 Sent To B
Notes
2002-05-07 00:00:00******************** UNSAT ************
  
 1 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE NOTE MISSING REQ`D
 LISTING ON PANEL SCHEDULE FOR ARC FAULT
 PROTECTION PER 210-12.
  
 3)NOTE: PLEASE NOTE #12 SHOWN FOR DRYER
 AT 5KW. #10?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-25 Cont ID  
Sent By btrobaug Date 2002-04-25 Time 17:23 Rev Time 0.00
Received By btrobaug Date 2002-04-25 Time 17:21 Sent To P
Notes
2002-04-25 00:00:00~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-05-18 Cont ID  
Sent By hmoser Date 2002-05-18 Time 09:31 Rev Time 0.33
Received By hmoser Date 2002-05-18 Time 09:30 Sent To  
Notes
2002-05-18 00:00:00PRIVISO
 #1 VARIFY TYPE OF VENTILATION USED
 [FRESH AIR]NATURAL 402 OR
 MECHANICAL 403
 #2 NEED CALCULATIONS FOR TYPE OF
 VENTILATION USED
 #3 REFER TO SECTION 601.4 BALANCED
 RETURN AIR
 #4 CONDENSATE DRAIN MUST TERMINATE
 12IN.FRON BUILDING 1503.4.4
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-05-06 Cont ID  
Sent By hmoser Date 2002-05-06 Time 19:55 Rev Time 0.33
Received By hmoser Date 2002-05-06 Time 19:55 Sent To  
Notes
2002-05-07 00:00:00PLAN DENIED
 NO ARCHITECT STAMP ON PLANS
 HAROLD MOSER [561]659-8096 EXT 8390

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-23 Cont ID  
Sent By hmoser Date 2002-04-23 Time 19:24 Rev Time 0.33
Received By hmoser Date 2002-04-23 Time 19:24 Sent To  
Notes
2002-04-23 00:00:00PLAN DENIED
 NO ENERGY CALCS OR MANUAL J
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-27 Cont ID  
Sent By btrobaug Date 2002-04-25 Time 17:24 Rev Time 0.33
Received By jleech Date 2002-04-27 Time 13:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-05-29 Cont ID  
Sent By btrobaug Date 2002-05-20 Time 18:23 Rev Time 3.00
Received By lhatten Date 2002-05-26 Time 19:21 Sent To  
Notes
2002-05-29 00:00:00REVIEW & STAMPED PLANS & TRUSS ENG.
 05/26/2002
 CALC. FEES & PRINT CARDS 05/29/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-22 Cont ID  
Sent By sgraham Date 2002-04-22 Time 11:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved