Plan Review Details - Permit 02040775
Plan Review Stops For Permit 02040775
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-21 Cont ID  
Sent By btrobaug Date 2002-05-21 Time 07:06 Rev Time 0.00
Received By btrobaug Date 2002-05-21 Time 06:48 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-08 Cont ID  
Sent By dpalmer Date 2002-05-08 Time 06:10 Rev Time 0.00
Received By dpalmer Date 2002-05-08 Time 06:02 Sent To B
Notes
2002-05-08 00:00:00************* UNSAT**************
  
 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION ON PANEL SCHEDULE. PER
 210-12
  
 2)NOTE: PLEASE NOTE 5KW DRYER LOAD ON
 #12 AWG. #10?
  
 PLEASE SUBMIT THE ABOV EINFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-18 Cont ID  
Sent By hmoser Date 2002-05-18 Time 09:59 Rev Time 0.33
Received By hmoser Date 2002-05-18 Time 09:59 Sent To  
Notes
2002-05-18 00:00:00PROVISO
 #1 VARIFY TYPE OF VENTILATIONUAED
 [FRESH AIR] NATURAL 402 OR
 MECHANICAL 403
 #2 NEED CALCULATIONS FOR TYPE OF
 VENTILATION USED
 #3 REFER TO SECTION 601.4 BALANCED
 RETURN AIR
 #4 CONDENSATE DRAIN MUST TERMINATE
 12IN.FROM BUILDING 1503.4.4
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-07 Cont ID  
Sent By hmoser Date 2002-05-07 Time 17:49 Rev Time 0.33
Received By hmoser Date 2002-05-07 Time 17:48 Sent To  
Notes
2002-05-07 00:00:00PLAN DENIED
 NO STAMPED PLANS
 HAROLD MOSER[561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-27 Cont ID  
Sent By jleech Date 2002-04-27 Time 10:18 Rev Time 0.33
Received By jleech Date 2002-04-27 Time 10:17 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-05-29 Cont ID  
Sent By btrobaug Date 2002-05-21 Time 07:09 Rev Time 3.00
Received By lhatten Date 2002-05-25 Time 18:22 Sent To  
Notes
2002-05-29 00:00:00REVIEW & STAMPED PLANS & TRUSS ENG.
 05/25/2002
 CALC. FEES & PRINT CARDS 05/25/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-22 Cont ID  
Sent By sgraham Date 2002-04-22 Time 11:51 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***