Plan Review Details - Permit 02040747
Plan Review Stops For Permit 02040747
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-05-21 Cont ID  
Sent By btrobaug Date 2002-05-21 Time 07:22 Rev Time 0.00
Received By btrobaug Date 2002-05-21 Time 07:12 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-05-07 Cont ID  
Sent By dpalmer Date 2002-05-07 Time 21:08 Rev Time 0.00
Received By dpalmer Date 2002-05-07 Time 21:08 Sent To B
Notes
2002-05-07 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTEDCIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 3)NOTE: PLEASE NOTE 5KW LOAD FOR DRYER
 ON #12 AWG.
  
 PLEASE SUBMIT THAT ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-25 Cont ID  
Sent By btrobaug Date 2002-04-25 Time 17:56 Rev Time 0.00
Received By btrobaug Date 2002-04-25 Time 17:32 Sent To P
Notes
2002-04-25 00:00:00~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-05-18 Cont ID  
Sent By hmoser Date 2002-05-18 Time 10:52 Rev Time 0.33
Received By hmoser Date 2002-05-18 Time 10:52 Sent To  
Notes
2002-05-18 00:00:00PROVISO
 #1 VARIFY TYPE OF VENTILATION USED
 [FRESH AIR] NATURAL 402 OR
 MECHANICAL 403
 #2 NEED CALCULATIONS FOR TYPE OF
 VENTILATION USED
 #3 REFER TO SECTION 601.4 BALANCED
 RETURN AIR
 #4 CONDENSATE DRAIN MUST TERINATE
 12IN. FROM BUILBING
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-05-06 Cont ID  
Sent By hmoser Date 2002-05-06 Time 20:16 Rev Time 0.33
Received By hmoser Date 2002-05-06 Time 20:16 Sent To  
Notes
2002-05-07 00:00:00PLAN DENIED
 NO STANPED PLANS
 HAROLD MOSER[561]659-8096 EXT 8390

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-23 Cont ID  
Sent By hmoser Date 2002-04-23 Time 19:34 Rev Time 0.33
Received By hmoser Date 2002-04-23 Time 19:34 Sent To  
Notes
2002-04-23 00:00:00PLAN DENIED
 NO ENERGY CALCS OR MANUAL J
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-27 Cont ID  
Sent By btrobaug Date 2002-04-25 Time 17:56 Rev Time 0.33
Received By jleech Date 2002-04-27 Time 13:16 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-05-29 Cont ID  
Sent By btrobaug Date 2002-05-21 Time 07:22 Rev Time 3.00
Received By lhatten Date 2002-05-25 Time 19:53 Sent To  
Notes
2002-05-29 00:00:00REVIEW & STAMPED PLANS & TRUSS ENG.
 05/25/2002
 CALC. FEES & PRINT CARDS 05/29/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-22 Cont ID  
Sent By sgraham Date 2002-04-22 Time 08:59 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***