Plan Review Details - Permit 02040746
Plan Review Stops For Permit 02040746
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-10 Cont ID  
Sent By lsmith Date 2002-06-10 Time 11:13 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-08 Cont ID  
Sent By btrobaug Date 2002-04-25 Time 10:53 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2002-05-08 00:00:00****************FAILED***************
  
 1. MUST REFERENCE FBC 2001 FOR SAFETY
 BARRIER WITH CORRECT CHAPTER & SECTION#
 2. MUST SHOW DETAIL OF EQUIPMENT SLAB &
 ANCHORING OF EXUIPMENT ON PLANS
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-25 Cont ID  
Sent By kstevens Date 2002-04-24 Time 13:48 Rev Time 0.00
Received By btrobaug Date 2002-04-25 Time 10:41 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-10 Cont ID  
Sent By kstevens Date 2002-06-10 Time 11:53 Rev Time 0.00
Received By kstevens Date 2002-06-10 Time 11:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-29 Cont ID  
Sent By jleech Date 2002-05-29 Time 19:07 Rev Time 0.75
Received By jleech Date 2002-05-29 Time 19:07 Sent To  
Notes
2002-05-29 00:00:00DENIED;
 SEE PLAN REVIEW NOTES DONE BY KEN
 STEVENS ON 4/24/02. NOTES B,E,F,G,H,I,J
 AND K.
 PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-24 Cont ID  
Sent By kstevens Date 2002-04-24 Time 13:38 Rev Time 0.00
Received By kstevens Date 2002-04-24 Time 13:38 Sent To E
Notes
2002-04-24 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 A) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. SEE NOTE TOP OF
 FIRST PAGE.
 B) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92. SEE NOTE #14 GEN. NOTES
 C)
 FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 D)
 FBC-2001 SEC 424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 E)
 FBC-2001 SEC 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 F)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 G)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 H)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 I)
 FBC-2001 SEC 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 J)
 FBC-2001 SEC 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 K)
 FBC-2001 SEC 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-15 Cont ID  
Sent By sgraham Date 2002-04-15 Time 16:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***