|
 |
 |
 |
 |
 |
Plan Review Details - Permit 02040724
Plan Review Stops For Permit 02040724 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-05-13 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-04-25 |
Time |
13:28 |
Rev Time |
0.50 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-04-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-24 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-04-25 |
Time |
12:56 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-05-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-03 |
Time |
18:43 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-03 |
Time |
18:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-04-24 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-24 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-24 |
Time |
14:52 |
Sent To |
E |
|
Notes |
2002-04-24 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | FORMATION REQUIRED FOR PLAN REVIEW | | A) | | FBC-2001 SEC 424.2.6.1 ENGINEERING | | DESIGN, CONSTRUCTION AND WORKMANSHIP. | | ANSI/NSPI-4 92.(SEE NOTE #10) | | B) | | FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | NUMBER AND MANUF INFO FOR VAC LOCK. | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | C) | | FBC-2001 SEC 424.2.6.6.5 WHERE PROVIDED, | | THE VACUUM OR PRESSURE CLEANER FITTING | | SHALL BE LOCATED AT LEAST 6" AND NOT | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | THE SKIMMER. | | D) | | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | | | 2) ALL REFERENCES TO SFBC, (SEE PAGE 3), | | SHALL BE DELETED. PRESENT CODE IS FBC- | | 2001 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-04-15 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-04-15 |
Time |
09:52 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |