Plan Review Details - Permit 02040691
Plan Review Stops For Permit 02040691
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-05 Cont ID  
Sent By hpiskura Date 2002-06-05 Time 09:11 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-23 Cont ID  
Sent By jwitmer Date 2002-04-23 Time 13:07 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-23 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02040691
 423 4TH ST
 SISCA CONSTRUCTION
 TEL: 686-9538
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)- EXISTING RATED STAIRWAY LEADING
 THROUGH THE EXISTING VESYIBLE, AS INDICA
 TED ON THE FLOOR PLAN THIS IS THE ONLY
 AREA THAT REQUIRES A 1 HR FIRE RATING,
 FL BLD CODE 704.2.4 REQUIRES CORRIDORS
 EXIT ENCLOSURES AND FIRE RATED WALLS
 REQUIRED TO HAVE PROTECTED OPENINGS
 SHALL BE EFFECTIVELY AND PERMANENTLY
 WITH SIGN OR STENCILING, FIRE WALL &
 SMOKE BARRIER PROTECT ALL OPENINGS.
  
 2)- FL BLD CODE 104.2.1.2 ADDITIONAL
 DATA REQUIRED, THE HANDICAPPED RESTROOMS
 ARE NOT DIMENSIONED, PLEASE PROVIDE THIS
 ADDTIONAL INFORMATION. THE MINIMUM DIS-
 TANCE BETWEEN FIXTURES SHALL BE GIVEN BY
 THE PLUMBING PLANA REVIEWER.
  
 3)- FL BLD CODE 4.17.3 TOLIET STALLS/
 LADIES RESTROOM, THE DOOR IS NOT TO
 SWING INTO THE CLEAR FLOOR SPACE SEE
 FIG. 30-E.
  
 4)- FL BLD CODE CHAPTER 11. DISPROPOR-
 TIONATE COST, DEPENDING ON THE RESULTS
 OF COMMENT #2 THE EXISTING RESTROOMS
 MAY NEED TO INCREASE IN WIDTH. 4.1.6.2.2
 DEALS WITH THE 20% DISPROPORTIONATE COST
 INDICATE WHERE THE 20%,TO INCREASE THE
 ACCESSIBLE ROUTE SHALL BE USED, SEE
 ACCESSIBLE ENTRANCE, ACCESSIBLE ROUTE
 THEN RESTROOMS ETC.
 (B)(II) A SERIES OF SMALLER ALTERATIONS
 MAY BE CONSIDERED, THE TOTAL COST OF ALL
 ALTERATIONS WITHIN THE PRECEEDING THREE
 YEARPERIOD SHALL BE CONSIDERED IN DETER-
 MINING WHETHER THE COST OF MAKING THAT
 PATH OF TRAVEL ACCESSIBLE IS DISSPROPOR-
 TIONATE.
  
 5)- FL BLD CODE 1511.7 ROOF MOUNTED
 MECHANICAL UNITS ON RAISED EQUIMENT
 SUPPORTSPROVIDE A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-11 Cont ID  
Sent By btrobaug Date 2002-04-11 Time 16:33 Rev Time 0.00
Received By btrobaug Date 2002-04-11 Time 15:42 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-04-30 Cont ID  
Sent By mamini Date 2002-04-30 Time 15:19 Rev Time 0.00
Received By mamini Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-04-11 Cont ID  
Sent By mcarsill Date 2002-04-11 Time 09:00 Rev Time 0.00
Received By mcarsill Date 2002-04-11 Time 09:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-31 Cont ID  
Sent By pkrauss Date 2002-05-31 Time 13:44 Rev Time 0.40
Received By pkrauss Date 2002-05-31 Time 13:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-03 Cont ID  
Sent By pkrauss Date 2002-05-03 Time 07:08 Rev Time 0.40
Received By pkrauss Date 2002-05-03 Time 07:02 Sent To  
Notes
2002-05-03 00:00:00PROVISO:
  
 CONDENSER UNIT STANDS SHALL COMPLY WITH
 2001 FBC TABLE 1511.7.
  
 EQUIPMENT INSTALLED ON ROOFS THAT EXCEED
 16 FT IN HEIGHT SHALL HAVE AN APPROVED
 PERMANENT MEANS OF ACCESS.SUCH ACCESS
 SHALL NOT REQUIRED CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 IN.2001
 FBC(M) 306.5
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-05 Cont ID  
Sent By kstevens Date 2002-06-05 Time 09:46 Rev Time 0.00
Received By kstevens Date 2002-06-05 Time 09:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-07 Cont ID  
Sent By kstevens Date 2002-05-07 Time 10:34 Rev Time 0.00
Received By kstevens Date 2002-05-07 Time 10:34 Sent To  
Notes
2002-05-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT #1 PLEASE GIVE DIMENSIONS FOR
 EXISTING RESTROOMS.
 2) SHT #1 DOOR SWING SHALL NOT OPEN INTO
 THE CLEAR FLOOR SPACE OF HDCP LAV. FBC-
 2001 SEC 4.17.3
 3) SHT #1 SI SINK SHALL COMPLY WITH SEC
 11-424. GIVE DETAILS FOR ALL SUBSECTIONS
 4) SHTS #1 & #3 JANITOR SINK REFERED TO
 ON SANT. RISER DIAGRAM NOT SHOWN ON DEMO
 SHT OR FLOOR PLAN?? PLEASE SHOW JANITOR
 SINK OF FLOOR PLAN. (TABLE 403.1 - FBC-
 2001 PLUMBING REQUIRES 1 SERVICE SINK).
 5) SHT #3 PLUMBING NOTE #7 - AIR CHAMB-
 ERS ARE NOT APPROVED. WATER HAMMER ARRES
 TORS ARE REQUIRED ON ALL QUICK CLOSING
 VALVES ONLY. (WASH MACHINES, ICE MAKERS,
 DISHWASHERS ECT.) IF USED THEY SHALL BE
 LOCATED NEAR FIXTURE, IN AN "EFFECTIVE
 RANGE", NOT AT TOP OF DROP.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-06-05 Cont ID  
Sent By kstevens Date 2002-06-05 Time 09:46 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***