Plan Review Details - Permit 02040593
Plan Review Stops For Permit 02040593
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-06-27 Cont ID  
Sent By lmartine Date 2002-06-27 Time 12:49 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-15 Cont ID  
Sent By jwitmer Date 2002-05-15 Time 12:26 Rev Time 0.50
Received By jwitmer Date 2002-05-15 Time 12:26 Sent To  
Notes
2002-05-15 00:00:00PLANS APPROVED WITH PRODUCT APPROVAL
 REPORT 99-0920.05 20G OUTSWING COMMER-
 CIAL STEEL DOORS (2) W/ 16G FRAME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-23 Cont ID  
Sent By jwitmer Date 2002-04-23 Time 14:55 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-23 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02040593
 632 HIBISCUS STREET
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)- FLBLD CODE 1606.1.7 INFORMATION
 ON DRAWINGS, MINIMUM INFO REQUIRED FOR
 WIND.
  
 2)- SHEET A-1.02 INDICATES NEW DOOR
 OPENINGS ON THE BACK EXTERIOR OF THE
 BUILDING. (COMPONENTS & CLADDING)
 FL BLD CODE 1707.4 EXTERIOR WINDOW &
 DOOR ASSEMBLIES, PROVIDE PRODUCT APPROV-
 ALS FOR NEW DOOR OPENINGS, SBCCI OR DADE
 COUNTY PRODUCT TESTING REPORT.2 COPIES.
  
 3)- FL BLD CODE 1707.4.4 ANCHORAGE
 METHOD, THIS APPLIES TO WINDOWS & DOOR
 ASSEMBLIES THAT FASTEN TO THE MAIN FORCE
 RESISTING SYSTEM. MISSING FASTENER AND
 FREQUENCY?
  
 4)- FL BLD CODE 104.2.1.2 ADDITIONAL
 DATA REQUIRED, IS THE STOREFRONT
 SYSTEM AN EXISTING SYSTEM? OR IS THIS
 NEW WORK? IF NEW WORK THE SAME PRODUCT
 TESTING REPORT SHALL BE REQUIRED.
 IF NEW WORK, LARGE MISSLE IMPACT TESTING
 SHALL APPLY, IMPACT GLAZING OR SHUTTERS
  
 5)- PROVIDE THE POSITVIE & NEGATIVE
 PRESSURS THAT APPLY TO THESE OPENINGS
 BEING AFFECTED.
  
 6)- SHEET A-1.01 DETAILS 1,2 & 4 PLEASE
 PROVIDE THE UL RATING FOR THE ASSEMBLIES
 WHERE A 1 HR RATING IS ACHIEVED WITH
 DRYWALL ON 1 SIDE, WHEN NEXT TO STRUCTUR
 AL COLUMN W/ FOAM SPRAY APPLIED.
  
 7)- FL BLD CODE 1909.3 CONCRETE SLABS
 ON GRADE, (2) CONCRETE SLABS ON GRADE
 CONTAINING 6X6 W1.4XW1.4 WELDED WIRE REI
 NFORCEMENT FABRIC LOCATED IN THE MIDDLE
 TO UPPER 1/3RD OF THE SLAB SHALL HAVE
 APPROVED MATERIALS OR SUPPORTS AT SPAC-
 ING NOT TO EXCEED 3 FT OR IN ACCORDANCE
 WITH THE MANUFACTURERS SPEC.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412
  
 THIS IS FOR THE SLAB, STEEL FRAMING,
 DEMISING

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-19 Cont ID  
Sent By dpalmer Date 2002-06-19 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2002-06-19 Time 19:11 Sent To  
Notes
2002-06-19 00:00:00UNDERGROUND CONDUITS ONLY.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-25 Cont ID  
Sent By dpalmer Date 2002-04-25 Time 06:08 Rev Time 0.00
Received By dpalmer Date 2002-04-25 Time 06:08 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-06-04 Cont ID  
Sent By kstevens Date 2002-06-04 Time 13:21 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 13:44 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 13:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-24 Cont ID  
Sent By mcarsill Date 2002-04-24 Time 13:50 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2002-04-24 00:00:001) PROVIDE ADDRESS NUMBER ON BUILDING.
 2) PROVIDE SHOP DRAWING FOR FIRE ALARM
 REMODEL.
 3) PROVIDE SHOP DRAWING FOR FIRE
 SPRINKLER REMODEL.
 4) PROVIDE FIRE RATING INFORMATION ON
 DEMISING WALLS & CEILING.
  
 LT. MIKE WENNERGREN
 561-835-2910
 561-659-8096 EXT 8497

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-06-27 Cont ID  
Sent By ndenmark Date 2002-06-27 Time 15:57 Rev Time 0.35
Received By ndenmark Date 2002-06-27 Time 15:57 Sent To  
Notes
2002-06-27 00:00:00FIRE DAMPER DETAIL SHEETS ADDED FOR
 EXHAUST DUCT WALL PENETRATION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 09:06 Rev Time 0.35
Received By pkrauss Date 2002-06-22 Time 09:01 Sent To  
Notes
2002-06-22 00:00:00DENIED:
 NONTE INDICATES TOILET EXHAUST DUCT
 W/FIRE DAMPERS - SEE 1/4" SCALE PLAN,
 THIS DWG.NO FIRE DAMPER DETAIL SHOWN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-06-04 Cont ID  
Sent By kstevens Date 2002-06-04 Time 13:21 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-06-18 Cont ID  
Sent By jleech Date 2002-06-18 Time 19:45 Rev Time 0.33
Received By jleech Date 2002-06-18 Time 19:45 Sent To  
Notes
2002-06-18 00:00:00REVISED DRAWINGS; ADDED COPPER WATER
 WATER LINES UNDER THE SLAB FOR FUTURE
 BATHROOM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-04 Cont ID  
Sent By kstevens Date 2002-06-04 Time 13:20 Rev Time 0.00
Received By kstevens Date 2002-06-04 Time 13:19 Sent To  
Notes
2002-06-03 00:00:00SHELL ONLY SEPARATE PERMITS FOR BUILD
 OUT.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-25 Cont ID  
Sent By kstevens Date 2002-05-25 Time 15:26 Rev Time 0.00
Received By kstevens Date 2002-05-25 Time 15:26 Sent To  
Notes
2002-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PREVIOUS REVIEW COMMENTS NOT ADDRESS-
 ED.
 2) PLEASE INDICATE MINIMUM FACILITIES
 REQUIRED PER TABLE 403.1. 1 HDCP ACCESS-
 IBLE TOILET ROOM AND 1 DRINKING FOUNTAIN
 REQUIRED IN EACH SPACE.
 3) PLEASE SUBMIT DETAIL FOR TOILET ROOM
 AND DRINKING FOUNTAIN. CLEAR FLOOR SPACE
 HEIGHTS, DISTANCE TO CENTER OF FIXTURES
 OFF WALLS ECT PER 11-4.14, 4.16, 4.19,
 AND 4.22
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-29 Cont ID  
Sent By jleech Date 2002-04-29 Time 16:41 Rev Time 0.50
Received By jleech Date 2002-04-29 Time 16:41 Sent To  
Notes
2002-04-29 00:00:00DENIED;
 MINIMUM PLUMBING FACIITIES REQUIRED SEE
 2001 FBC PLUMBING SEC.403.1. SHOW LOCA-
 TION OF BATHROOM FACILITIES FOR EMPLOYEE
 AND PUBLIC. COMPLY WITH SEC. 403.4,
 403.5 AND 403.6.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status N Date 2002-06-04 Cont ID  
Sent By kstevens Date 2002-06-04 Time 13:21 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***