Plan Review Stops For Permit 02040593 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-06-27 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2002-06-27 |
Time |
12:49 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-05-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-05-15 |
Time |
12:26 |
Rev Time |
0.50 |
Received By |
jwitmer |
Date |
2002-05-15 |
Time |
12:26 |
Sent To |
|
|
Notes |
2002-05-15 00:00:00 | PLANS APPROVED WITH PRODUCT APPROVAL | | REPORT 99-0920.05 20G OUTSWING COMMER- | | CIAL STEEL DOORS (2) W/ 16G FRAME. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-04-23 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-04-23 |
Time |
14:55 |
Rev Time |
1.50 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-23 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 02040593 | | 632 HIBISCUS STREET | | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1)- FLBLD CODE 1606.1.7 INFORMATION | | ON DRAWINGS, MINIMUM INFO REQUIRED FOR | | WIND. | | | | 2)- SHEET A-1.02 INDICATES NEW DOOR | | OPENINGS ON THE BACK EXTERIOR OF THE | | BUILDING. (COMPONENTS & CLADDING) | | FL BLD CODE 1707.4 EXTERIOR WINDOW & | | DOOR ASSEMBLIES, PROVIDE PRODUCT APPROV- | | ALS FOR NEW DOOR OPENINGS, SBCCI OR DADE | | COUNTY PRODUCT TESTING REPORT.2 COPIES. | | | | 3)- FL BLD CODE 1707.4.4 ANCHORAGE | | METHOD, THIS APPLIES TO WINDOWS & DOOR | | ASSEMBLIES THAT FASTEN TO THE MAIN FORCE | | RESISTING SYSTEM. MISSING FASTENER AND | | FREQUENCY? | | | | 4)- FL BLD CODE 104.2.1.2 ADDITIONAL | | DATA REQUIRED, IS THE STOREFRONT | | SYSTEM AN EXISTING SYSTEM? OR IS THIS | | NEW WORK? IF NEW WORK THE SAME PRODUCT | | TESTING REPORT SHALL BE REQUIRED. | | IF NEW WORK, LARGE MISSLE IMPACT TESTING | | SHALL APPLY, IMPACT GLAZING OR SHUTTERS | | | | 5)- PROVIDE THE POSITVIE & NEGATIVE | | PRESSURS THAT APPLY TO THESE OPENINGS | | BEING AFFECTED. | | | | 6)- SHEET A-1.01 DETAILS 1,2 & 4 PLEASE | | PROVIDE THE UL RATING FOR THE ASSEMBLIES | | WHERE A 1 HR RATING IS ACHIEVED WITH | | DRYWALL ON 1 SIDE, WHEN NEXT TO STRUCTUR | | AL COLUMN W/ FOAM SPRAY APPLIED. | | | | 7)- FL BLD CODE 1909.3 CONCRETE SLABS | | ON GRADE, (2) CONCRETE SLABS ON GRADE | | CONTAINING 6X6 W1.4XW1.4 WELDED WIRE REI | | NFORCEMENT FABRIC LOCATED IN THE MIDDLE | | TO UPPER 1/3RD OF THE SLAB SHALL HAVE | | APPROVED MATERIALS OR SUPPORTS AT SPAC- | | ING NOT TO EXCEED 3 FT OR IN ACCORDANCE | | WITH THE MANUFACTURERS SPEC. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096X8412 | | | | THIS IS FOR THE SLAB, STEEL FRAMING, | | DEMISING |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-06-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-06-19 |
Time |
19:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-06-19 |
Time |
19:11 |
Sent To |
|
|
Notes |
2002-06-19 00:00:00 | UNDERGROUND CONDUITS ONLY. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-04-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-04-25 |
Time |
06:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-04-25 |
Time |
06:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2002-06-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-04 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-05-17 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-05-17 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-05-17 |
Time |
13:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-04-24 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-04-24 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-24 00:00:00 | 1) PROVIDE ADDRESS NUMBER ON BUILDING. | | 2) PROVIDE SHOP DRAWING FOR FIRE ALARM | | REMODEL. | | 3) PROVIDE SHOP DRAWING FOR FIRE | | SPRINKLER REMODEL. | | 4) PROVIDE FIRE RATING INFORMATION ON | | DEMISING WALLS & CEILING. | | | | LT. MIKE WENNERGREN | | 561-835-2910 | | 561-659-8096 EXT 8497 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2002-06-27 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-06-27 |
Time |
15:57 |
Rev Time |
0.35 |
Received By |
ndenmark |
Date |
2002-06-27 |
Time |
15:57 |
Sent To |
|
|
Notes |
2002-06-27 00:00:00 | FIRE DAMPER DETAIL SHEETS ADDED FOR | | EXHAUST DUCT WALL PENETRATION |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2002-06-22 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-22 |
Time |
09:06 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-06-22 |
Time |
09:01 |
Sent To |
|
|
Notes |
2002-06-22 00:00:00 | DENIED: | | NONTE INDICATES TOILET EXHAUST DUCT | | W/FIRE DAMPERS - SEE 1/4" SCALE PLAN, | | THIS DWG.NO FIRE DAMPER DETAIL SHOWN. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2002-06-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-04 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2002-06-18 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-06-18 |
Time |
19:45 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2002-06-18 |
Time |
19:45 |
Sent To |
|
|
Notes |
2002-06-18 00:00:00 | REVISED DRAWINGS; ADDED COPPER WATER | | WATER LINES UNDER THE SLAB FOR FUTURE | | BATHROOM. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2002-06-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-04 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-06-04 |
Time |
13:19 |
Sent To |
|
|
Notes |
2002-06-03 00:00:00 | SHELL ONLY SEPARATE PERMITS FOR BUILD | | OUT. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-05-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-25 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-25 |
Time |
15:26 |
Sent To |
|
|
Notes |
2002-05-25 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | | | 1) PREVIOUS REVIEW COMMENTS NOT ADDRESS- | | ED. | | 2) PLEASE INDICATE MINIMUM FACILITIES | | REQUIRED PER TABLE 403.1. 1 HDCP ACCESS- | | IBLE TOILET ROOM AND 1 DRINKING FOUNTAIN | | REQUIRED IN EACH SPACE. | | 3) PLEASE SUBMIT DETAIL FOR TOILET ROOM | | AND DRINKING FOUNTAIN. CLEAR FLOOR SPACE | | HEIGHTS, DISTANCE TO CENTER OF FIXTURES | | OFF WALLS ECT PER 11-4.14, 4.16, 4.19, | | AND 4.22 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-04-29 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-04-29 |
Time |
16:41 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2002-04-29 |
Time |
16:41 |
Sent To |
|
|
Notes |
2002-04-29 00:00:00 | DENIED; | | MINIMUM PLUMBING FACIITIES REQUIRED SEE | | 2001 FBC PLUMBING SEC.403.1. SHOW LOCA- | | TION OF BATHROOM FACILITIES FOR EMPLOYEE | | AND PUBLIC. COMPLY WITH SEC. 403.4, | | 403.5 AND 403.6. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8369 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2002-06-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-04 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|