Plan Review Details - Permit 02040581
Plan Review Stops For Permit 02040581
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-04-17 Cont ID  
Sent By btrobaug Date 2002-04-17 Time 16:05 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-18 Cont ID  
Sent By btrobaug Date 2002-04-18 Time 09:45 Rev Time 0.00
Received By btrobaug Date 2002-04-18 Time 09:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-17 Cont ID  
Sent By btrobaug Date 2002-04-11 Time 09:21 Rev Time 0.00
Received By btrobaug Date 2002-04-11 Time 08:40 Sent To B
Notes
2002-04-11 00:00:00*****************UNSAT!*****************
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE SHOW MEANS OF DISCONNECT
 FOR A/C EQUIPMENT PER 440-14.
  
 3} SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52,(DEN).
  
 4} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 6} PLEASE NOTE KITCHEN COUNTER
 RECEPT TO COMPLY WITH 210-8(A)(6).
  
 7} SMOKE DETECTORS TO COMPLY WITH 2-5.2.
 1.6 NFPA-72.PLEASE MOVE THE ONE IN THE
 WEST BEDROOM TO THE NORTH TO AVOID A
 "NUISANCE" ALARM,ESPECIALLY FROM THE
 KITCHEN AREA.
  
 PLEASE MAKE THE NECESSARY CORRECTIONS
 AND RESUBMIT FOR REVIEW.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-16 Cont ID  
Sent By pkrauss Date 2002-04-16 Time 08:18 Rev Time 0.40
Received By pkrauss Date 2002-04-16 Time 08:18 Sent To  
Notes
2002-04-16 00:00:00PROVISO:
  
 1.PER 2001 FBC 1503.4.4,CONDENSATE
 SHALL TERMINATE A MINIMUM OF 12 IN
 FROM BUILDING STRUCTURE.
  
 2.2001 FBC, MECHANICAL 601.4, TO AVOID
 PRESSURE DIFFERENTIALS ACROSSED
 CLOSED DOORS WHERE RETURNS ARE
 CENTRALLY LOCATED, PROVIDE AIR DUCT
 PATHWAYS OR AIR TRANSFER PATHWAYS
 FROM THE HIGH PRESSURE ZONE TO THE
 LOW ZONE.
  
 3.BALANCING DAMPERS OR OTHER MEANS OF
 SUPPLY AIR ADJUSTMENT SHALL BE
 PROVIDED IN THE BRANCH DUCTS OR AT
 EACH INDIVIDUAL DUCT REGISTER,
 GRILLE OR DIFFUSER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-17 Cont ID  
Sent By kstevens Date 2002-04-17 Time 14:48 Rev Time 0.00
Received By kstevens Date 2002-04-17 Time 14:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2002-04-17 Cont ID  
Sent By lsmith Date 2002-04-17 Time 15:50 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***