Plan Review Details - Permit 02040581
Plan Review Stops For Permit 02040581 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-04-17 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-04-17 |
Time |
16:05 |
Rev Time |
0.75 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-04-18 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-04-18 |
Time |
09:45 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-04-18 |
Time |
09:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-04-17 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-04-11 |
Time |
09:21 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-04-11 |
Time |
08:40 |
Sent To |
B |
|
Notes |
2002-04-11 00:00:00 | *****************UNSAT!***************** | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2} PLEASE SHOW MEANS OF DISCONNECT | | FOR A/C EQUIPMENT PER 440-14. | | | | 3} SHOW ALL OUTLET SPACING | | TO MEET 2`,6`,12` RULE PER 210-52,(DEN). | | | | 4} PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG. | | | | 5} PLEASE LIST THE REQ`D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | 6} PLEASE NOTE KITCHEN COUNTER | | RECEPT TO COMPLY WITH 210-8(A)(6). | | | | 7} SMOKE DETECTORS TO COMPLY WITH 2-5.2. | | 1.6 NFPA-72.PLEASE MOVE THE ONE IN THE | | WEST BEDROOM TO THE NORTH TO AVOID A | | "NUISANCE" ALARM,ESPECIALLY FROM THE | | KITCHEN AREA. | | | | PLEASE MAKE THE NECESSARY CORRECTIONS | | AND RESUBMIT FOR REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT.8392 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-04-16 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-04-16 |
Time |
08:18 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2002-04-16 |
Time |
08:18 |
Sent To |
|
|
Notes |
2002-04-16 00:00:00 | PROVISO: | | | | 1.PER 2001 FBC 1503.4.4,CONDENSATE | | SHALL TERMINATE A MINIMUM OF 12 IN | | FROM BUILDING STRUCTURE. | | | | 2.2001 FBC, MECHANICAL 601.4, TO AVOID | | PRESSURE DIFFERENTIALS ACROSSED | | CLOSED DOORS WHERE RETURNS ARE | | CENTRALLY LOCATED, PROVIDE AIR DUCT | | PATHWAYS OR AIR TRANSFER PATHWAYS | | FROM THE HIGH PRESSURE ZONE TO THE | | LOW ZONE. | | | | 3.BALANCING DAMPERS OR OTHER MEANS OF | | SUPPLY AIR ADJUSTMENT SHALL BE | | PROVIDED IN THE BRANCH DUCTS OR AT | | EACH INDIVIDUAL DUCT REGISTER, | | GRILLE OR DIFFUSER. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-04-17 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-17 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-17 |
Time |
14:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2002-04-17 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2002-04-17 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |