Plan Review Details - Permit 02040523
Plan Review Stops For Permit 02040523
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-01 Cont ID  
Sent By dpalmer Date 2002-05-01 Time 07:33 Rev Time 0.00
Received By dpalmer Date 2002-05-01 Time 06:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-26 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 06:29 Rev Time 0.00
Received By dpalmer Date 2002-04-26 Time 06:28 Sent To P
Notes
2002-04-26 00:00:00**************** NOTE *************
  
 1)NOTE: PLEASE NOTE THAT THE CODE ARTS
 ARE STILL FROM THE 96 NEC, PLEASE
 CORRELATE W/ 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT FOR AIC
 RATING, SHOWN AS 22.00, SHOULD SHOW AS
 22,000.
  
 3))NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
  
 4 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTES. PER 210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-12-05 Cont ID  
Sent By pkrauss Date 2002-12-05 Time 16:35 Rev Time 0.25
Received By pkrauss Date 2002-12-05 Time 16:35 Sent To  
Notes
2002-12-05 00:00:00MECHANICAL PERMIT 02040569

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-10-17 Cont ID  
Sent By hmoser Date 2002-10-17 Time 19:15 Rev Time 0.33
Received By hmoser Date 2002-10-17 Time 19:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-30 Cont ID  
Sent By hmoser Date 2002-05-30 Time 17:58 Rev Time 0.33
Received By hmoser Date 2002-05-30 Time 17:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-25 Cont ID  
Sent By hmoser Date 2002-04-25 Time 18:42 Rev Time 0.50
Received By hmoser Date 2002-04-25 Time 18:42 Sent To  
Notes
2002-04-25 00:00:00PLAN DENIED
 CFM.ON PLAN DOES NOT MATCH CFM. ON
 MANUAL J
 NEED TO KNOW DUCT SIZE FOR RISER
 12 IN.OR 16 IN.
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-27 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 06:29 Rev Time 0.33
Received By jleech Date 2002-04-27 Time 12:36 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-05-16 Cont ID  
Sent By lhatten Date 2002-05-16 Time 07:41 Rev Time 2.50
Received By lhatten Date 2002-05-16 Time 07:41 Sent To  
Notes
2002-05-23 00:00:00REVIEW & STAMPED PLANS 05/16/2002
 OKED

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-09 Cont ID  
Sent By sgraham Date 2002-04-09 Time 11:50 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***