Plan Review Details - Permit 02040518
Plan Review Stops For Permit 02040518
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-01 Cont ID  
Sent By dpalmer Date 2002-05-01 Time 06:42 Rev Time 0.00
Received By dpalmer Date 2002-05-01 Time 06:42 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-26 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 12:30 Rev Time 0.00
Received By dpalmer Date 2002-04-26 Time 12:30 Sent To P
Notes
2002-04-26 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASENOTE CODE ARTS STILL
 FROM 96 NEC.NEEDS TO REF 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT OF AIC
 RATING SHOWN AS 22.00? PLEASE
 CORRLETE TO SHOW 22,000
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROETECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTES. PER210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELEECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-06 Cont ID  
Sent By pkrauss Date 2002-12-06 Time 13:14 Rev Time 0.25
Received By pkrauss Date 2002-12-06 Time 12:51 Sent To  
Notes
2002-12-06 00:00:00MECH REV PERMIT 02040561

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-24 Cont ID  
Sent By hmoser Date 2002-06-24 Time 19:15 Rev Time 0.50
Received By hmoser Date 2002-06-24 Time 19:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-25 Cont ID  
Sent By hmoser Date 2002-04-25 Time 17:46 Rev Time 0.33
Received By hmoser Date 2002-04-25 Time 17:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-27 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 12:30 Rev Time 0.33
Received By jleech Date 2002-04-27 Time 13:02 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-07-30 Cont ID  
Sent By rmcdouga Date 2002-07-30 Time 12:42 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-30 00:00:00************BUILDING PROVISO************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SUBMIT SOIL BEARING TESTS PRIOR TO
 POURING THE FOUNDATION.
  
 4) SUBMIT (2) STORM PANEL INSTALLATION
 SCHEDULE LISTING ALL OF THE OPENINGS
 THAT ARE BEING SHUTTERED. THE ONES THAT
 WERE SUBMITTED ONLY LISTED 7 OF 10
 OPENINGS.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 EVALUATION REPORTS FOR GLASS BLOCK. ONLY
 PART OF THE REPORT WAS SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-06-27 Cont ID  
Sent By rmcdouga Date 2002-06-27 Time 09:57 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-27 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) PROVIDE A SOIL BEARING TEST REPORT
 PER CITY OF WPB AMENDMENTS TO THE 2001
 FBC SEC. 1804.2.2.
  
 4) PROVIDE (2) COPIES OF INSTALLATION
 SCHEDULE FOR STORM PANELS. THESE ARE
 REQUIRED AT TIME OF PERMIT OR A SEPARATE
 PERMIT (WITH ADDITIONAL FEES) WILL HAVE
 TO BE PULLED FOR THE STORM PANELS.
  
 5) PROVIDE ADDITIONAL COPIES OF PRODUCT
 APPROVALS FOR THE FRONT DOOR AND GLASS
 BLOCK. TWO COPIES ARE REQUIRED.
  
 6) PROVIDE TESTING INFORMATION FOR GLASS
 BLOCK WHICH INDICATES BLOCK HAS A ONE
 HOUR FIRE RATING.
  
 7) PLEASE CHANGE THE CALL SIZE OF THE
 EGRESS WINDOW (I) IN THE WINDOW SCHEDULE
 TO 24-5 SH WHICH CORRESPONDS TO THE
 REVISED DIMENSIONS GIVEN.
  
 8) PLEASE CHANGE NOTE #6 UNDER GENERAL
 NOTES ON A2 TO REFERENCE THE 2001
 FLORIDA PLUMBING CODE.
  
 9) PROVIDE A DETAIL OF THE GABLE END ON
 THE ZERO LOT LINE. IT IS REQUIRED TO BE
 A ONE HOUR FIRE RATED ASSEMBLY BASED ON
 BOTH INTERIOR AND EXTERIOR EXPOSURE TO
 FIRE.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-05-22 Cont ID  
Sent By rmcdouga Date 2002-05-22 Time 14:20 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-05-22 00:00:00SAME COMMENTS AS 02040516.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-09 Cont ID  
Sent By sgraham Date 2002-04-09 Time 11:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***