Plan Review Details - Permit 02040514
Plan Review Stops For Permit 02040514
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-20 Cont ID  
Sent By btrobaug Date 2002-05-20 Time 17:24 Rev Time 0.00
Received By btrobaug Date 2002-05-20 Time 17:23 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-26 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 06:51 Rev Time 0.00
Received By dpalmer Date 2002-04-26 Time 06:51 Sent To P
Notes
2002-04-26 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE PLANS ARE STILL
 SHOWING THE 96 NEC. PLEASECORRELATE
 W/ 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT FOR AIC
 RATING SHOWN AS 22.00?? SHOULD SHOW
 22,000.
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTES. PER 210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-03 Cont ID  
Sent By hmoser Date 2002-12-03 Time 19:26 Rev Time 0.50
Received By hmoser Date 2002-12-03 Time 19:26 Sent To  
Notes
2002-12-03 00:00:00NEED ENERGY CALCS.& MANUAL (J)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-25 Cont ID  
Sent By hmoser Date 2002-04-25 Time 18:24 Rev Time 0.50
Received By hmoser Date 2002-04-25 Time 18:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-27 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 06:51 Rev Time 0.33
Received By jleech Date 2002-04-27 Time 12:36 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-05-16 Cont ID  
Sent By lhatten Date 2002-05-16 Time 17:05 Rev Time 2.50
Received By lhatten Date 2002-05-14 Time 17:04 Sent To  
Notes
2002-05-16 00:00:00REVIEW & PRINT CARDS 05/14/2002
 CALC. FEES & PRINT CARDS05/16/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-09 Cont ID  
Sent By sgraham Date 2002-04-09 Time 11:50 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***