Plan Review Details - Permit 02040459
Plan Review Stops For Permit 02040459
Review Stop B BUILDING (STRUCTURAL)
Rev No 75 Status P Date 2005-12-12 Cont ID  
Sent By shill Date 2005-12-12 Time 12:46 Rev Time 0.00
Received By shill Date 2005-12-12 Time 12:46 Sent To  
Notes
2005-12-12 00:00:00FINAL SURVEY

Review Stop B BUILDING (STRUCTURAL)
Rev No 74 Status P Date 2005-12-05 Cont ID  
Sent By shill Date 2005-12-05 Time 16:01 Rev Time 0.50
Received By shill Date 2005-12-05 Time 16:01 Sent To  
Notes
2005-12-05 00:00:00LIGHT POLE CALCS PREPARED BY DAVID B
 ROGERS, PE DATED 8/16/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 73 Status F Date 2005-10-03 Cont ID  
Sent By shill Date 2005-10-03 Time 11:02 Rev Time 0.50
Received By shill Date 2005-10-03 Time 11:02 Sent To PC
Notes
2005-10-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE TITLE BLOCK IS TO BE IN
 COMPLIANCE WITH FAC61G15-23.002 (THE
 CERTIFICATE OF AUTHORIZATION NUMBER IS
 NOT ON THE CALCS).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 72 Status N Date 2005-09-14 Cont ID  
Sent By shill Date 2005-09-14 Time 09:22 Rev Time 0.45
Received By jleahy Date 2005-09-19 Time 13:59 Sent To  
Notes
2005-09-14 00:00:00ELECTRIC REVISION DATED 8/15/05
 PROVISO - SUBMIT BUILDING REVISION IF
 ARCHITECTURAL/STRUCTURAL SHEETS ARE
 AFFECTED BY ELECTRICAL CHANGES.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 71 Status P Date 2005-08-24 Cont ID  
Sent By shill Date 2005-08-24 Time 19:07 Rev Time 0.00
Received By shill Date 2005-08-24 Time 19:07 Sent To  
Notes
2005-08-24 00:00:00LIGHT POLE CALCS PREPARED BY YOUSSEF
 HACHEM, PE

Review Stop B BUILDING (STRUCTURAL)
Rev No 70 Status F Date 2005-08-04 Cont ID  
Sent By shill Date 2005-08-04 Time 11:25 Rev Time 0.50
Received By shill Date 2005-08-04 Time 11:25 Sent To PC
Notes
2005-08-04 00:00:00****CORRECTIONS****
 LIGHT POLE SUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)ALL SUBMITTALS TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 2.)SHOW COMPLIANCE WITH FBC1606.
 CALCULATIONS SUBMITTED PREVIOUSLY ARE
 FOR A DIFFERENT COMPANY AND PRODUCT.TO
 AVOID CONFUSION, PLEASE CLARIFY WHICH
 LIGHT POLES WERE SUBMITTED PREVIOUSLY
 (AND WHERE THEY ARE BEING INSTALLED) AND
 PROVIDE SAME INFORMATION IN REGARDS TO
 THIS LIGHT POLE SUBMITTAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 69 Status F Date 2005-08-04 Cont ID  
Sent By shill Date 2005-07-19 Time 19:19 Rev Time 0.50
Received By shill Date 2005-07-19 Time 19:18 Sent To PC
Notes
2005-08-04 00:00:00****CORRECTIONS****
 LIGHT POLE CALCS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)HAVE ALL SUBMITTALS REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
2005-07-19 00:00:00LIGHT POLE CALCS PREPARED BY YOUSSEF
 HACHEM, PE

Review Stop B BUILDING (STRUCTURAL)
Rev No 68 Status P Date 2005-05-27 Cont ID  
Sent By shill Date 2005-05-27 Time 15:05 Rev Time 3.00
Received By shill Date 2005-05-27 Time 15:05 Sent To PC
Notes
2005-05-27 00:00:00REVISION 65, VARIOUS SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 67 Status P Date 2005-05-27 Cont ID  
Sent By shill Date 2005-05-27 Time 15:03 Rev Time 2.00
Received By shill Date 2005-05-27 Time 13:14 Sent To  
Notes
2005-05-27 00:00:00REVISION 64
 NEEDS ZONING (PARKING AND ELEVATION
 CHANGES)
  
 TO LM OFFICE

Review Stop B BUILDING (STRUCTURAL)
Rev No 66 Status P Date 2005-05-27 Cont ID  
Sent By shill Date 2005-05-27 Time 13:13 Rev Time 3.00
Received By shill Date 2005-05-27 Time 07:39 Sent To  
Notes
2005-05-27 00:00:00REVISION 59, VARIOUS SHEETS
  
 NOTE - COULD NOT FIND CHANGES ON LS1.01
 AND A7.03.

Review Stop B BUILDING (STRUCTURAL)
Rev No 65 Status P Date 2005-05-26 Cont ID  
Sent By shill Date 2005-05-26 Time 10:22 Rev Time 3.00
Received By shill Date 2005-05-25 Time 18:49 Sent To PC
Notes
2005-05-26 00:00:00ARCHITECTURAL REVISIONS 46, 50, 58 -
 VARIOUS DATES
  
 PROVISO - SUBMIT REVISIONS FOR OTHER
 TRADES IF APPLICABLE
  
 REMOVED SHEET 11.12
  
 REDLINED 3.10 - COMPLY W/FBC1015, SUBMIT
 SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 64 Status P Date 2005-05-16 Cont ID  
Sent By shill Date 2005-05-16 Time 15:18 Rev Time 0.50
Received By shill Date 2005-05-16 Time 15:18 Sent To  
Notes
2005-05-16 00:00:00REVISION #63, SHEET A7.02 DATED 4/14/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 63 Status P Date 2005-04-29 Cont ID  
Sent By shill Date 2005-04-29 Time 09:12 Rev Time 0.50
Received By shill Date 2005-04-29 Time 09:12 Sent To PC
Notes
2005-04-29 00:00:00PRECAST MOULDINGS, ATTACHMENTS
 PREPARED BY PATRICIA M BOTAS, PE
 3/11/05
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 62 Status F Date 2005-03-15 Cont ID  
Sent By shill Date 2005-03-15 Time 15:23 Rev Time 6.00
Received By shill Date 2005-03-15 Time 15:23 Sent To  
Notes
2005-03-15 00:00:00****CORRECTIONS****
 REVISION #59
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)FBC1006.1.3.1 PENETRATIONS INTO AND
 OPENINGS THROUGH A STAIRWAY ENCLOSURE
 ASSEMBLY ARE PROHIBITED.REGARDING THE
 LOUVERS IN THE STAIRS, SHOW COMPLIANCE
 WITH ONE OF THE EXCEPTIONS.THIS
 COMMENT MAY ALSO AFFECT THE REVISIONS
 46, 50 AND 58.
  
 2.) K-A6.05, LABELED "SCUPPER" ALTHOUGH
 IT APPEARS TO BE AN OVERFLOW DRAIN;
 FBC1503.4.2 OVERFLOW DRAIN SHALL BE
 INSTALLED 2" ABOVE THE LOW POINT OF THE
 ROOF.
  
 3.)SHEET A11.12, PLEASE NOTE WHERE
 THESE RAILS/GUARDRAILS ARE TO BE
 INSTALLED.NOTE THAT THE NEWEL DETAIL
 HAS BEEN REVISED TO STATE A STEEL TOP
 RAIL BUT SOME OF THE OTHER STAIR DETAILS
 SPECIFY WOOD.
  
  
  
 SOME OF THE REVISIONS 46 - 59 AFFECT
 OTHER TRADES.SUBMIT REVISIONS ON THE
 AFFECTED SHEETS FOR OTHER TRADES IF YOU
 HAVE NOT ALREADY DONE SO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 61 Status F Date 2005-03-11 Cont ID  
Sent By shill Date 2005-03-11 Time 14:10 Rev Time 16.00
Received By shill Date 2005-03-11 Time 14:10 Sent To  
Notes
2005-03-11 00:00:00****CORRECTIONS****
 REVISIONS 46, 50, 58
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 THE REVISIONS 46 THROUGH 59 SUBMITTED
 WERE NOT CLOUDED WITH THE EXCEPTION OF
 THE MOST CURRENT REVISION. I WAS UNABLE
 TO LOCATE SOME OF THE CHANGES ON THE
 PLAN, NOTED BELOW.
  
 1.)SHEET A8.06, 22.2, IDENTIFY AND
 CLARIFY 4X4 1 HR ACCESS PANEL.
  
 2.)SHEET A8.06, 22.3, CMU WALL
 RELOCATED, IDENTIFY.
  
 3.)SHEET A8.31, 43.3 AND 43.6, UNCLEAR
 FROM TRANSMITTAL AS TO WHAT CHANGED.
  
 4.)SHEET A11.03, IS THIS DETAIL 13?
 SPECIFY FIRE RATING REQUIREMENT AND SHOW
 COMPLIANCE.
  
 5.)DRAWING A8.23, 35.2.IT IS UNCLEAR
 WHY THE 1 HR WALL WAS ADDED AS IT IS NOT
 CONTINUOUS AROUND THE ENTIRE STORAGE
 ROOM AREA.ALSO THE SEPARATION
 REQUIREMENT FOR STORAGE LOW HAZARD IS 2
 HR FBC704.1 IF IT IS REQUIRED.SEE
 FBC704.1.2.2(4).
  
 REVISION #50 DATED 7/21/2004
  
 6.)A3.10, THE RAILING DETAIL SHOWS A 2
 1/2" DISTANCE BETWEEN THE BOTTOM RAIL
 AND THE SLAB.THE GUARDRAIL IS TO
 COMPLY WITH FBC1015.3, TO REJECT A 2"
 OBJECT (7-A3.10 SHOWS 2 1/2"), AND IT IS
 NOT CLEAR IF THE 6 1/2" DISTANCE FROM
 BOTTOM OF BOTTOM RAIL TO TOP OF NEXT
 RAIL IS COMPLIANT WITH THE REQUIREMENT
 TO REJECT A 4" OBJECT.
  
 7.)A A11.12, DETAILS 6 AND 7, PROVIDE
 DESIGN CRITERIA.THE DESIGN FOR THE
 HANDRAIL IS TO COMPLY WITH FBC1608.2.1,
 THE GUARDRAIL IS TO COMPLY WITH
 FBC1608.2.2.
  
 8.)IT IS NOT CLEAR HOW THE NEW DETAILS
 TIE INTO THE OLD DETAIL (8), OR WHERE
 THEY ARE TO BE INSTALLED. THE GUARDRAIL
 SHOWS A HANDRAIL.IF THIS IS NOT A
 GUARDRAIL WHICH IS ALSO A STAIR RAIL, IS
 THE HANDRAIL REQUIRED?THE DISTANCE
 BETWEEN THE HANDRAIL (AT 2'10") AND THE
 SUPPORTS FOR THE TOP RAIL APPEARS TOO
 NARROW (REQUIREMENT BETWEEN A HANDRAIL
 AND WALL IS 1 1/2").IT IS DIFFICULT TO
 DETERMINE CODE COMPLIANCE AS I AM UNSURE
 AS TO THE APPLICATION OF THE DETAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 60 Status P Date 2005-03-11 Cont ID  
Sent By shill Date 2005-03-11 Time 09:27 Rev Time 1.50
Received By shill Date 2005-03-11 Time 09:27 Sent To PC
Notes
2005-03-11 00:00:00STRUCTURAL REVISION #53 DATED 8/31/04
  
 SHEETS S6, S7, S24, S29, S31, S32, S33,
 S34, S35, S36, S36A, S37, S37A, S52,
 S53, S54

Review Stop B BUILDING (STRUCTURAL)
Rev No 59 Status P Date 2004-10-13 Cont ID  
Sent By shill Date 2004-10-12 Time 16:20 Rev Time 2.00
Received By shill Date 2004-10-12 Time 16:20 Sent To PC
Notes
2004-10-12 00:00:00POST TENSION SHOPS, PREPARED BY
 SUNCOAST, RICARDO LAZARAZU PE
  
 PT 00, 10, 11, 20, 21, 30, 31, 40, 41
 50, 51, 60, 61, 70, 71, 80, 81
  
 TENDON & SUPPORT PLANS
 LANAI LEVEL
 11TH LEVEL
 12TH LEVEL
 ROOF LEVEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 58 Status F Date 2004-09-21 Cont ID  
Sent By csiegber Date 2004-10-06 Time 10:12 Rev Time 0.50
Received By shill Date 2004-09-21 Time 11:10 Sent To  
Notes
2004-09-21 00:00:00****CORRECTIONS****
 POST TENSION SHOPS, PREPARED BY LIZARU,
 PE DATED 8/6/04
  
 1.)A TITLE BLOCK IS REQUIRED FOR THE
 ENGINEER CONTAINING ALL INFORMATION
 REQUIRED BY FAC61G15-23.002.
  
 2.)SHEETS WERE NOT COLLATED.PROVIDE
 THREE SETS, COLLATED AND BOUND FOR
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 57 Status P Date 2004-08-27 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:24 Rev Time 1.00
Received By shill Date 2004-08-27 Time 14:14 Sent To  
Notes
2004-08-27 00:00:00REVISION #52 DATED 8/16, A1.04, A1.06,
 A11.04 ADDRESSING PROVISOS

Review Stop B BUILDING (STRUCTURAL)
Rev No 56 Status P Date 2004-08-27 Cont ID  
Sent By shill Date 2004-08-27 Time 13:35 Rev Time 0.50
Received By shill Date 2004-08-27 Time 13:35 Sent To  
Notes
2004-08-27 00:00:00SHORING/POUR LETTERS
 POUR #66, MAIN LEVEL
 POUR #67, MAIN ROOF LEVEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 55 Status P Date 2004-08-19 Cont ID  
Sent By csiegber Date 2004-08-25 Time 13:30 Rev Time 1.00
Received By shill Date 2004-08-19 Time 11:10 Sent To  
Notes
2004-08-19 00:00:00AS BUILT SURVEYS, PREPARED BY CAUFIELD
 & WHEELER
  
 COLUMN ELEVATIONS
 GRID LINE CONTROL, 9TH FLOOR
 GRID LINE CONTROL, 12TH FLOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 54 Status P Date 2004-08-12 Cont ID  
Sent By csiegber Date 2004-08-18 Time 15:02 Rev Time 0.50
Received By shill Date 2004-08-12 Time 08:53 Sent To  
Notes
2004-08-12 00:00:00POUR LETTERS, #65 SOUTH SIDE PUMP 1
 MAIN ROOF LEVEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 53 Status P Date 2004-08-09 Cont ID  
Sent By csiegber Date 2004-08-11 Time 15:36 Rev Time 0.50
Received By shill Date 2004-08-09 Time 14:16 Sent To  
Notes
2004-08-09 00:00:00POUR LETTERS, #63, 16TH FLOOR EAST
 POST TENSIONED TENDONS
  
 POUR #62, 16TH FLOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 52 Status P Date 2004-07-30 Cont ID  
Sent By csiegber Date 2004-08-04 Time 14:20 Rev Time 0.25
Received By alange Date 2004-07-30 Time 13:53 Sent To  
Notes
2004-07-30 00:00:00POUR #61 LETTERS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 51 Status P Date 2004-07-30 Cont ID  
Sent By mjacobs Date 2004-07-30 Time 13:08 Rev Time 1.50
Received By mjacobs Date 2004-07-30 Time 13:07 Sent To  
Notes
2004-07-30 00:00:007-30-04 REBAR SUBMITTALS
  
 PARK 7TH LOFT 5TH: BEAMS & WALLS
 PARK 7TH/LOFT 5TH: BOTTOM
 POUR #1 COLS (AREA 5) G5@ ROOF
 POUR #3 (AREA 7) COLS PC & 2 @ 6
 SHEERWALL #5 MEZZANINE TO 6TH FL.
 2ND FL. POUR #5,6,7,9,& 11. BEAMS
 STAIR 5,7 & 8
 MEZZ. P#4 SLAB BOTTOM & BEAMS
 S.W.#1 & S.W.#2
 POUR #1 PART MEZZ. STAIRS #12-5
 FDN.PAD 76-PC-SP. BOTTOM
 84-PC-SP.TOP MAT,ADD & SW-3 DWLS
 TOWER 7TH FL. LANAI TOP

Review Stop B BUILDING (STRUCTURAL)
Rev No 50 Status P Date 2004-08-02 Cont ID  
Sent By shill Date 2004-07-30 Time 10:34 Rev Time 6.00
Received By shill Date 2004-07-30 Time 09:38 Sent To  
Notes
2004-07-30 00:00:00****PROVISO****
 REVISION ADDRESSING COMMENTS 6/1/02
 THROUGH REVISION #44
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SHEET A1.04 STILL SHOWS SLOPES OF
 1:35 AND 1:38 FOR THE ACCESSIBLE PARKING
 SPACE.THIS IS NOT COMPLIANT WITH
 FBC11-4.6.3; "PARKING SPACES AND ACCESS
 AISLES SHALL BE LEVEL WITH SURFACE
 SLOPES NOT EXCEEDING 1:50 (2%) IN ALL
 DIRECTIONS."SEE REVIEW SET; ABOVE
 REFERENCED SLOPES HAVE BEEN HIGHLIGHTED.
 REVISE SHEET A1.04
  
 2.)DOORS IN THE STAIRWAY ENCLOSURES
 TO COMPLY WITH FBC705.1.3.4.
  
 3.)REVISE SHEET 1.06 (NO WHITEOUT)
  
 4.)PROVIDE A FIREBLOCKING
 DETAIL FOR THE DROPPED CEILINGS SHOWN
 ON A5.12 FBC705.3.1.1.
  
 5.)PROVIDE CALCULATIONS FOR STAIR #5
 (FBC412.11(5)).

Review Stop B BUILDING (STRUCTURAL)
Rev No 49 Status P Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-07-28 Time 12:31 Rev Time 0.33
Received By alange Date 2004-07-28 Time 09:45 Sent To  
Notes
2004-07-28 00:00:00SUBMITTALS OK FOR POUR#60, AND SHORING
 FOR POUR 60PER SH

Review Stop B BUILDING (STRUCTURAL)
Rev No 48 Status P Date 2004-07-28 Cont ID  
Sent By alange Date 2004-07-27 Time 15:56 Rev Time 0.33
Received By alange Date 2004-07-27 Time 15:56 Sent To  
Notes
2004-07-27 00:00:00BALCONY HANDRAIL SUBMITTALS OK PER SH

Review Stop B BUILDING (STRUCTURAL)
Rev No 47 Status F Date 2004-07-22 Cont ID  
Sent By mjacobs Date 2004-07-22 Time 13:37 Rev Time 2.00
Received By mjacobs Date 2004-07-22 Time 13:37 Sent To  
Notes
2004-07-22 00:00:00BUILDING PLAN REVIEW
 PERMIT:02040459
 ADD:851 SOUTH OLIVE AVE
 CONT:SUFFOLK CONSTRUCTION CO. INC.
 TEL: (561)655-6400
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 SUBMITTALS REVIEW
 ACTION: DENIED
  
 1) PLEASE SUBMMIT THREE IDENTICAL COPIES
 OF EACH PLAN.
 2) EACH PLAN NEEDS TO TO BE REVIEW BY
 ENGINEER OF RECORD.
 3) ENGINEER STAMP NEEDS TO CLEAR AND
 LEGIBLE. ALSO EACH SET OF PLANS NEED
 TO BE SIGNED.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 46 Status P Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-21 Time 14:58 Rev Time 4.00
Received By mjacobs Date 2004-07-22 Time 09:41 Sent To  
Notes
2004-07-22 00:00:00SUBMITTALS - REBAR SHOPS,
  
  
 REBAR SHOPS DRAWINGS -
 PARKING 8TH TOP
 PARK 6TH/LOFT 4TH BEAMS/WALLS #63
 PARK 6TH/LOFT 4TH BEAMS/WALLS #63A
 PARK 6TH/LOFT 4TH BOTTOM #61
 TOWER 7TH FL. LANAI BEAMS & WALLS #74
 PARK 6TH/LOFT 4TH. TOP #62
 GROUND SLAB, THICKED & VERTICALS
 49-PC-SP. BOTTOM MAT & ADDIT
 POUR #39 COLUMS TO 2ND LEVEL MEZZANINE
 AND GUARAGE LEVEL 2
 PARK 5TH FL. BOTTOM BEAME & WALLS #59
 TOWER 11TH. FL. TOP #78
 TOWER 7TH FL. LAMAI BEAMS & WALLS #74A
 TOWER 8-10TH (TYP) TOP #76
 SW #4 6TH FL. PARKING TO ROOF #56
 SW #3 6TH FL. PARKING TO ROOF #55
 TOWER 7TH FL. LANAI BEAMS & WALLS #74
 POUR#5 (AAREA 11) COLS G6 @ ROOF #53
 PARK 7TH LOFT 5TH FL. BEAMS & WALLS #66A
 SW #5 6TH FL. PARKING TO ROOF #57
 PARK 8TH FL. BOTTOM, BEAMS & WALLS #67
 PARK 9TH/TOWER 6TH FL. TOP #74A
 SHARWALLS #1&2 TO 12TH FL. #54
 TOWER 12/16TH FL. TOP. #80
 TOWEWR 12/16TH FL. BOTTOM & BEAMS #79
 POUR #3. FDN, DWLS & G.BEAMS #7
 TOWER 7TH FL. LANAI BEAMS & WALLS #88A
 PAARKING SECOND LEVEL & LOFT SECOND
 LEVEL FRAMING PLAN.
 POURS #6-8 COLS TO M,GS & L2 #17-17B
 TOWER MAIN FOOF,BOTTOM & BEAMS. #81(75)
 POUR #3 COLS (AREA 7) G6 @ ROOF.#51(58)
 TOWER 11TH FL. BOTTOM & BEAMS #77(89)
 PARK 9TH/TOWER 6TH FL. BOTTOM #69(65)
 TOWER MAIN ROOF. BOTM,BEAMS,WALLS
 TOWER MAIN ROOF TOP, TCOL & WALLS
 PARKING 8TH TOP
 POUR #1 PART MEZZANINE SLAB @+12-5
 RETAINING WALLS POURS 6-8 #20
 POUR #4-9 FOUNDATION #11(21)
 49-PC-SP. TOP MAT & ADDIT. #22(26)
 PARK 7TH/LOFT 5TH. TOP#65
 84-PC-SP. BOTTOM MAT & ADDITIONAL #12
 STAIRS 1,2,4,10#32 (38)
 PARK 9TH/TOWER 6TH. BEAMS & WALLS
 PARK 9TH/TOWER 6TH. TOP #70
 POUR #5 COLS TO 2ND & MEZZ #16
 76PC-SP. TOP MAT, ADD & SW-5 DWLS #4(12)
 R-1A-7 PILE CAP 76 PCSP BOTTOM BARS
 R-1A-8 PILE CAP 76PCSP TOP BARS
 R-1A-9 PILE CAP 76PCSP STANDEES AND
 CARRY BARS
 R-1A-10 PILE CAP 76PCSP COL SW #5 DOWELS
 ALUMINUM RAIL @ RAMP AR-SW-1
 POUR #59 15TH FL. SOUTH SIDE
 POUR #2 COLS (AREA 6) G5 @ ROOF
 2ND FL. POUR #5,6,7,9,11. BOTTOM
 POUR #4: COL & SW-5 TO MEZZ

Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status F Date 2004-07-16 Cont ID  
Sent By shill Date 2004-07-16 Time 16:42 Rev Time 1.00
Received By mjacobs Date 2004-07-16 Time 11:07 Sent To  
Notes
2004-07-16 00:00:001) SUBMITTALS:TENDON SUPPORT PLAN @
 MEZZANINE/3RD FL AND 4TH FL. PLANS
 NEED TO BE SIGNED AND SEALED.ALSO PLEASE
 BE AWARE THAT NAME HAS TO PRINTED UNDER
 SINGITURE. THE ENGINEER CA# NEED TO BE
 ON PLANS ALSO. THE TITLE BLOCK NEEDS THE
 PE# AND LICENSE #. FOR FURTHER INFO.
 PLEASE SEE FAC.61G-23.002

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status P Date 2004-07-16 Cont ID  
Sent By mjacobs Date 2004-07-16 Time 08:50 Rev Time 0.50
Received By mjacobs Date 2004-07-16 Time 08:50 Sent To  
Notes
2004-07-16 00:00:00SHORING/RESHORE/CONTR CERT LETTERS
 POST TENSIONED TENDONS - OK PER SMH
 POUR #55, 12TH FLOOR, NORTH SIDE
 POUR #56, 14TH FLOOR, SOUTH SIDE
 POUR #57, 14TH FLOOR, EAST SIDE
 POUR #58, 14TH FLOOR, NORTH SIDE

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status F Date 2004-07-13 Cont ID  
Sent By mjacobs Date 2004-07-14 Time 14:39 Rev Time 0.50
Received By shill Date 2004-07-13 Time 15:21 Sent To  
Notes
2004-07-13 00:00:00****CORRECTIONS****
 REBAR SHOPS SUBMITTAL
 POUR #2 (AREA 6,10,15) COLS M&G2 TO G5
 SW #1, SW #2 TO 6TH FLOOR
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLEASE NOTE THAT THE 2ND AND 3RD
 SHEETS OF THIS SUBMITTAL HAVE BEEN
 REJECTED BY THE ENGINEER OF RECORD.
 PLEASE REVISE AND HAVE APPROVED.
  
 2.)ONE SHEET CONTAINS A TITLE BLOCK
 SO IS REQUIRED TO BE SEALED FAC61G15-
 23.002.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status P Date 2004-07-13 Cont ID  
Sent By shill Date 2004-07-13 Time 14:22 Rev Time 2.00
Received By shill Date 2004-07-13 Time 14:22 Sent To  
Notes
2004-07-13 00:00:00REBAR SHOPS
 POUR #1 COLS (AREA 5) G5 @ ROOF
 PARK 4TH/LOFT 3RD ALL POUR BOT
 PARK 4TH/LOFT 3RD ALL POUR TOP
 2ND FL POUR #5,6,7,9,11 BOTTOM
 PARK 4TH FL, LOFTS 3RD FL BEAMS
 POUR #4 COLS (AREA 9) G6 @ ROOF
 2ND FL POUR #5,6,7,9,11 TOP
 PARKING 3RD BOT, BEAMS & WALLS
 POUR #5 (AREA 11) COLS L,M &2@6
 POUR #1 (AREA 5, 8, 12) COLS G2 @ G5
 SW #3 TO 6TH FLOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status P Date 2004-06-29 Cont ID  
Sent By csiegber Date 2004-07-07 Time 11:28 Rev Time 0.50
Received By shill Date 2004-06-29 Time 10:35 Sent To  
Notes
2004-06-29 00:00:00INSPECTION LETTERS POUR #53, 12TH LEVEL
 POUR #54, 12TH LEVEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status F Date 2004-06-21 Cont ID  
Sent By csiegber Date 2004-06-25 Time 16:30 Rev Time 1.00
Received By shill Date 2004-06-21 Time 10:34 Sent To  
Notes
2004-06-21 00:00:00****CORRECTIONS****
 TYP GATE AT LANAI DECK
 STAIR RAIL SHOPS & CALCS
 PREPARED BY THOMAS M. KELAHER, PE
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE STRUCTURAL NOTES REFER TO THE
 WRONG BUILDING CODE (SOUTH FLORIDA
 BUILDING CODE SECTION 2305).PLEASE
 REVISE.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status P Date 2004-06-21 Cont ID  
Sent By shill Date 2004-06-21 Time 10:19 Rev Time 1.00
Received By shill Date 2004-06-21 Time 10:19 Sent To  
Notes
2004-06-21 00:00:00SHOPS/CALCS PREPARED BY THOMAS M.
 KELAHER, PEDATED 5/07/04
  
 ELEVATOR MACHINE ROOM GALV STEEL STAIRS
 HANDRAIL & GUARDRAIL, SHOPS & CALCS
 ALUMINUM TRELLISES, SHOPS & CALCS
 POOL FENCE SHOPS
 ROOF LADDER W/WALKOVER

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status P Date 2004-06-21 Cont ID  
Sent By shill Date 2004-06-21 Time 09:22 Rev Time 0.50
Received By shill Date 2004-06-21 Time 09:22 Sent To  
Notes
2004-06-21 00:00:00SHORING/RESHORE LETTERS
 ARBER & ASSOCIATES
 CHM
 SUFFOLK
  
 POUR #50, 11TH FLOOR
 POUR #46, 9TH FLOOR
 POUR #52, 11TH FLOOR
 POUR #51, 11TH FLOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2004-06-18 Cont ID  
Sent By shill Date 2004-06-18 Time 16:25 Rev Time 0.50
Received By shill Date 2004-06-18 Time 16:25 Sent To  
Notes
2004-06-18 00:00:003/8 STEEL PLATE LANDINGS FOR THE
 STEEL SPIRAL STAIRS @ THE MEZZANINE,
 3RD FL & 5TH FLCALCS PREPARED BY
 THOMAS M KELAHER, PE
 DATED 3/29/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status F Date 2004-06-10 Cont ID  
Sent By csiegber Date 2004-06-17 Time 14:20 Rev Time 0.50
Received By shill Date 2004-06-10 Time 13:39 Sent To  
Notes
2004-06-10 00:00:00****CORRECTIONS****
 SHORING/RESHORE, POST TENSIONED TENDONS
 INSPECTION LETTERS, POUR #50, 11TH LEVEL
  
 POUR 49 LEVEL 10
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ORIGINAL SIGNATURE REQUIRED
 (FRANCISCO BERMUDEZ,PE).THE PRINTED
 LICENSE NUMBER OF THE PERSON SEALING THE
 DOCUMENT AND THE CA NUMBER IS TO BE
 ON EACH SHEET, FAC61G15-23.002.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status F Date 2004-06-08 Cont ID  
Sent By csiegber Date 2004-06-09 Time 16:26 Rev Time 0.50
Received By shill Date 2004-06-08 Time 10:31 Sent To  
Notes
2004-06-08 00:00:00****CORRECTIONS****
 RAILING SHOPS PREPARED BY T. KELAHER PE
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)RE: SHEET A4, ARE THE RAILINGS
 DECORATIVE ONLY, NOT SERVING AS A
 GUARDRAIL?INDICATE ON THE PLAN,
 OTHERWISE MUST BE COMPLIANT WITH
 FBC1608 AND FBC1015.
  
 2.)SHEET A0, STRUCTURAL NOTE #1 REFERS
 TO THE WRONG BUILDING CODE.REVISE TO
 REFLECT CORRECT DESIGN CRITERIA. PROVIDE
 CALCULATIONS TO SHOW COMPLIANCE WITH
 FBC1608.2.2.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2004-06-08 Cont ID  
Sent By shill Date 2004-06-08 Time 09:20 Rev Time 1.00
Received By shill Date 2004-06-08 Time 09:20 Sent To  
Notes
2004-06-08 00:00:00RAILING SHOPS PREPARED BY THOMAS
 KELAHER PE
  
 WINDOW GRILL

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status F Date 2004-06-08 Cont ID  
Sent By shill Date 2004-06-08 Time 08:22 Rev Time 0.50
Received By shill Date 2004-06-08 Time 07:57 Sent To  
Notes
2004-06-08 00:00:00****CORRECTIONS****
 POUR 45 LEVEL 9, SHORE/RESHORE INSP
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 ORIGINAL SIGNATURE, PRINTED LICENSE
 OF FIRM, PRINTED LICENSE NUMBER OF
 ENGINEER SIGNING THE DOCUMENT REQUIRED
 FAC61G15-23.002.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status P Date 2004-06-02 Cont ID  
Sent By csiegber Date 2004-06-04 Time 13:58 Rev Time 0.50
Received By shill Date 2004-06-02 Time 07:25 Sent To  
Notes
2004-06-02 00:00:00INSPECTION LETTERS, POUR 48 LEVEL 10
 SHORING/RESHORE/POST TENSIONED TENDONS
 MARK MOSBAT, PE, WILLIAM H. BLUE, PE
 SUFFOLK LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2004-06-01 Cont ID  
Sent By shill Date 2004-06-01 Time 13:47 Rev Time 2.00
Received By shill Date 2004-06-01 Time 13:47 Sent To  
Notes
2004-06-01 00:00:00STRUCTURAL REVISION, S-0 THROUGH S-53
 DATED 5/4/4

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status F Date 2004-06-01 Cont ID  
Sent By csiegber Date 2004-06-01 Time 09:13 Rev Time 5.00
Received By shill Date 2004-06-01 Time 08:17 Sent To  
Notes
2004-06-01 00:00:00****CORRECTIONS****
 ARCHITECTURAL REVISION, VARIOUS
 SHEETS, DATED 4/12/04
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SHEET A1.04 SHOWS TWO SLOPES
 GREATER THAN 1:50, NOT COMPLIANT WITH
 FBC11-4.6.3. (SEE REVIEW SET)
  
 2.)SHEET A2.02 IS NOT SIGNED AND
 SEALED ON REVIEW SET.
  
 3.)SHEET A1.06, AT 17'5" ELEVATION,
 STAIR 3, WHAT IS THE PURPOSE OF THE
 DOOR IN THE MIDDLE OF THE STAIR LANDING?
  
 4.)THE REVISIONS AFFECT MEPS.SUBMIT
 THE REVISIONS AS NECESSARY.
  
 5.)SHEETS 5.08 AND 5.09, WHERE IS
 THE DETAIL FOR THE METAL STUD WALLS?
 THE RECENT STRUCTURAL REVISION
 SUBMITTED SHOWS THESE WALLS AS A TYPE
 W3, CONCRETE WALL.TRANSMITTAL LETTER
 INDICATES THE WALLS AS "SHOWN WITHOUT
 CONCRETE - TO BE METAL STUD
 CONSTRUCTION."PLEASE CLARIFY.
  
 6.) A3.09 REFERS TO FOAM COLUMN AND
 PANEL.ARCHITECTURAL TRIM ON BUILDINGS
 LOCATED IN THE FIRE DISTRICT SHALL BE
 CONSTRUCTED OF APPROVED NONCOMBUSTIBLE
 MATERIALS OR FIRE RETARDANT TREATED
 WOOD, F102.2.7 CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC, FBC1404.
  
 7.)PROVIDE CALCULATIONS FOR STAIR
 #5, THE NEW EGRESS STAIR, TO SHOW
 COMPLIANCE WITH FBC412.11(5).
  
 8.)DOORS IN THE STAIRWAY ENCLOSURES
 ARE TO COMPLY WITH FBC705.1.3.4.
  
 9.)PROVIDE A DETAIL FOR TYPE I
 REFERRED TO ON SHEET 5.12 (2 HR SHAFT).
  
 10.) SHEET 6.04, PROVIDE A CONSTRUCTION
 DETAIL, INCLUDING METHOD OF ATTACHMENT
 TO THE BUILDING, FASTENING CONNECTION
 DETAILS.
  
 11.) TRASH CHUTES SHALL COMPLY WITH
 NFPA82 3-2.4.3.1, THE SIZE OF THE
 SERVICE OPENING ROOM OR COMPARTMENT
 SHALL NOT BE LESS THAN THAT REQUIRED TO
 MAINTAIN A MINIMUM OF 6" CLEARANCE
 BETWEEN THE OPEN LOADING DOOR AND THE
 CLOSED SERVICE OPENING ROOM DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2004-05-25 Cont ID  
Sent By csiegber Date 2004-05-28 Time 10:43 Rev Time 0.50
Received By shill Date 2004-05-25 Time 17:07 Sent To  
Notes
2004-05-25 00:00:00POUR 47 10TH LEVEL
 SHORING/RESHORE INSPECTION, W.BLUE PE
 POST TENSION TENDONS, MARK MOSBAT PE
 SUFFOLK LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status F Date 2004-05-25 Cont ID  
Sent By shill Date 2004-05-25 Time 14:05 Rev Time 8.00
Received By shill Date 2004-05-25 Time 14:05 Sent To  
Notes
2004-05-25 00:00:00****CORRECTIONS****
 REVISIONS THROUGH #44, A SHEETS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SHEET A1.06 - AT THE 17'5" EL.,
 STAIR 3, A DOOR IS SHOWN IN THE MIDDLE
 OF THE STAIR LANDING.PLEASE CLARIFY
 AS TO THE PURPOSE OF THIS DOOR.
  
 2.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2004-05-21 Cont ID  
Sent By csiegber Date 2004-05-21 Time 11:26 Rev Time 0.50
Received By shill Date 2004-05-21 Time 09:16 Sent To  
Notes
2004-05-21 00:00:00POUR #45, 9TH LEVEL
 POST TENSION TENDON INSP LETTER, CHM
 SUFFOLK CONSTRUCTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status F Date 2004-05-21 Cont ID  
Sent By shill Date 2004-05-21 Time 09:05 Rev Time 0.50
Received By shill Date 2004-05-21 Time 09:05 Sent To  
Notes
2004-05-21 00:00:00****CORRECTIONS****
 SHORING/RESHORE INSPECTION LETTER,
 ARBER & ASSOC., POUR #45, PUMP 2
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ORIGINAL SIGNATURE REQUIRED, NOT
 PHOTOCOPY.INCLUDE PRINTED CA NUMBER
 FOR ARBER & ASSOC AS WELL AS PRINTED
 PE NUMBER FOR FRANCISCO BERMUDEZ, PE
 FAC61G15-23.002.
  
 2.)FOR FUTURE SUBMITTALS, PLEASE
 INCLUDE THE CA NUMBER FOR CHM PER
 FAC61G15-23.002.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-05-19 Time 13:47 Rev Time 0.50
Received By shill Date 2004-05-17 Time 12:32 Sent To  
Notes
2004-05-17 00:00:00INTERIOR STEEL RAILING @ MEZZANINE
 SHOPS & CALCS
 PREPARED BY THOMAS M. KELAHER, PE
 3/10/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2004-05-14 Cont ID  
Sent By shill Date 2004-05-13 Time 14:52 Rev Time 0.50
Received By shill Date 2004-05-13 Time 14:52 Sent To  
Notes
2004-05-13 00:00:00INSPECTION LETTERS, POUR #42, 8TH LEVEL
 POST TENSION TENDONS, CHM
 SHORING/RESHORE, SUFFOLK & ARBER & ASSOC
  
 INSPECTION LETTERS, POUR #41, 8TH LEVEL
 POST TENSION TENDONS, CHM
 SHORING/RESHORE, SUFFOLK & ARBER & ASSOC
  
 INSPECTION LETTERS, POUR #43, 8TH LEVEL
 SHORING/RESHORE, SUFFOLK & ARBER & ASSOC
  
 INSPECTION LETTERS, POUR #44, 9TH LEVEL
 POST TENSION TENDONS, CHM
 SHORING/RESHORE, SUFFOLK & ARBER & ASSOC

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status F Date 2004-05-13 Cont ID  
Sent By shill Date 2004-05-13 Time 13:17 Rev Time 0.50
Received By shill Date 2004-05-13 Time 13:17 Sent To  
Notes
2004-05-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THIS PLAN HAS BEEN REVIEWED UNDER
 PERMIT #04050133.A COPY OF THE
 COMMENTS ARE ATTACHED FOR YOUR
 CONVENIENCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2004-05-11 Cont ID  
Sent By csiegber Date 2004-05-13 Time 09:00 Rev Time 0.50
Received By shill Date 2004-05-11 Time 10:41 Sent To  
Notes
2004-05-11 00:00:00FIRESTOPPING SUBMITTALS
 PROVISO - IN ACCORDANCE W/APPROVED PLAN
 AND FBC

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2004-05-11 Cont ID  
Sent By shill Date 2004-05-11 Time 10:13 Rev Time 0.50
Received By shill Date 2004-05-11 Time 10:13 Sent To  
Notes
2004-05-11 00:00:00POUR #43, 8TH LEVEL, SLAB/POST TENSIONED
 TENDON INSPECT LETTER BY MARK MOSBAT, PE
  
 **PROVISO**SUBMIT FUTURE DOCUMENTS WITH
 CA # (CHM CONSULTING ENGINEERS)

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status F Date 2004-05-11 Cont ID  
Sent By shill Date 2004-05-11 Time 10:10 Rev Time 0.50
Received By shill Date 2004-05-11 Time 10:10 Sent To  
Notes
2004-05-11 00:00:00****CORRECTIONS****
 POUR/SHORING LETTERS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
  
 1.)RAISED IMPRINTED SEAL, ORIGINAL
 SIGNATURE, CA AND PE PRINTED NUMBERS
 REQUIRED ON ALL COPIES, FAC61G15-23.002.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status F Date 2004-05-05 Cont ID  
Sent By csiegber Date 2004-05-11 Time 09:57 Rev Time 0.50
Received By shill Date 2004-05-05 Time 18:34 Sent To  
Notes
2004-05-05 00:00:00****CORRECTIONS****
 3/8 STEEL PLATE LANDINGS FOR STEEL
 SPIRAL STAIRS @ 3RD & 5TH FLOORS
 PREPARED BY THOMAS KELAHER, PE
  
 1.)SOME SHEETS AREN'T CALCULATIONS,
 THEY ARE DETAILS.SIGN AND SEAL EACH
 SHEET AND INCLUDE THE LICENSE NUMBER
 ON EACH SHEET, FAC61G15-23.002.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2004-05-05 Cont ID  
Sent By shill Date 2004-05-05 Time 17:53 Rev Time 1.00
Received By shill Date 2004-05-05 Time 17:53 Sent To  
Notes
2004-05-05 00:00:00STAIR SHOPS AND CALCS, PREPARED BY
 THOMAS KELAHER, PE
  
 STEEL TUBE HANDRAIL & GUARDRAIL ASSEMBLY
 FOR STEEL SPIRAL STAIRS
  
 FOLDED STEEL PLATE TREAD FOR THE STEEL
 SPIRAL STAIRS
  
 SPIRAL STAIR SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-05-05 Time 14:55 Rev Time 0.50
Received By shill Date 2004-04-28 Time 15:31 Sent To  
Notes
2004-04-28 00:00:00POUR LETTERS, TOWER POUR 40, LANAI LEVEL
 SHORING/RESHORE INSPECTION BY ARBER &
 ASSOC
 POST TENSION TENDON INSPECTION BY
 CHM
 4/15/4, 4/23/4

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 15:11 Rev Time 1.00
Received By shill Date 2004-04-27 Time 09:44 Sent To  
Notes
2004-04-28 00:00:00METAL PAN STAIR SHOPS & CALCS
 PREPARED BY THOMAS KELAHER, PE 3/25/04
  
 PROVISO - PROVIDE CONNECTION DETAIL FOR
 POST TO BUILDING (SHEET ST-D3)

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-04-20 Time 10:03 Rev Time 0.50
Received By shill Date 2004-04-05 Time 09:19 Sent To  
Notes
2004-04-05 00:00:00SHORING LETTER, CHM POUR #36 LANAI LEVEL
 SHORING LETTER, CAPFORM, POUR #36
 LETTER FROM SUFFOLK #36 (7TH FL TOWER,
 SOUTH SIDE)
 4/1/4

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2004-03-26 Cont ID  
Sent By csiegber Date 2004-04-02 Time 15:51 Rev Time 0.50
Received By shill Date 2004-03-26 Time 07:39 Sent To  
Notes
2004-03-26 00:00:00POUR #34 - 6TH LEVEL LOFT
 INSPECTION LETTERS FROM CHM AND CAPFORM
 DATED 3/25 AND 3/23, NOTARIZED LETTER
 FROM SUFFOLK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2004-03-05 Cont ID  
Sent By csiegber Date 2004-03-25 Time 15:19 Rev Time 0.50
Received By shill Date 2004-03-05 Time 09:03 Sent To  
Notes
2004-03-05 00:00:00SHORING/RESHORE LETTERS 3/4/4
 CAPFORM (WILLIAM BLUE, PE)
 TOWER POUR 30 PUMP MAST 1, SOUTH SIDE
 6TH FLOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-05 Time 08:04 Rev Time 0.50
Received By shill Date 2004-03-04 Time 13:45 Sent To  
Notes
2004-03-04 00:00:00POUR LETTERS PREPARED BY CHM, ARBOR &
 ASSOCIATES, SUFFOLK DATED 2/26
  
 POUR #31, PUMP #3, 8TH LEVEL PARKING

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-04 Time 13:31 Rev Time 0.50
Received By shill Date 2004-03-01 Time 17:44 Sent To  
Notes
2004-03-01 00:00:00SHORING/RESHORING INSPECTION LETTERS
 PREPARED BY CAPFORM INC 2/17/04
 POST TENSIONED TENDON LETTER CHM 2/17/4
 TOWER POUR 28 PUMP MAST 3
  
 SHORING/RESHORING INSPECTION LETTERS
 PREPARED BY CAPFORM INC 2/17/04
 POST TENSIONED TENDON LETTER CHM 2/17/4
 GARAGE POUR 24 AND PUMP MAST 1

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2004-02-23 Cont ID  
Sent By csiegber Date 2004-02-25 Time 16:41 Rev Time 4.00
Received By shill Date 2004-02-23 Time 07:35 Sent To  
Notes
2004-02-23 00:00:00***CORRECTIONS***
  
 REVISIONS 12 THROUGH 17B, VARIOUS DATES
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)WHAT IS THE USE OF THE NEW ROOM
 BEING CREATED ABOVE THE TRASH CHUTE
 ROOM, AND HOW WILL THAT ROOM BE
 ACCESSED? (A7.06)
  
 2.)CHUTE PROTECTION REQUIRED, SECTIONS
 10 AND 3, A7.06.
  
 3.)WHAT TRANSPIRED BETWEEN REVISIONS
 13 AND 17B?
  
 4.)ACCESSIBLE PARKING SPACES SHALL BE
 LEVEL WITH SURFACE SLOPES NOT EXCEEDING
 1:50 (PLAN SHOWS 1/4"/FT), FBC11-4.6.3.
  
 5.)WHERE CHANGES IN ELEVATION OF 12"
 OR LESS OCCUR IN EXITS, RAMPS COMPLYING
 WITH FBC1013 SHALL BE PROVIDED, SHEET
 A7.11 (2-A7.11) SHOWS A 6" CHANGE IN
 ELEVATION.
  
 6.)PROVIDE INFORMATION REGARDING THE
 ATTACHMENT FOR THE STONE BASE AND WALL
 PANELS SHOWN ON A8.03.
  
 7.)SHEET 11.08 STILL HAS REFERENCES TO
 FOAM MOLDINGS (THERE IS A NOTE
 INDICATING THAT ALL MOLDINGS WILL BE
 STONE).
  
 8.)THE ARCHITECTURE FIRM LICENSE
 NUMBER AND PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS REQUIRED TO BE
 ON EACH SHEET, FAC61G1-16.004.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2004-02-19 Cont ID  
Sent By shill Date 2004-02-19 Time 08:02 Rev Time 1.00
Received By shill Date 2004-02-19 Time 08:02 Sent To  
Notes
2004-02-19 00:00:00****CORRECTIONS****
  
 STRUCTURAL STEEL STAIR, GUARDRAILS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE GUARDRAIL (REFERRED TO AS A
 HANDRAIL ON THE CALCULATIONS) IS TO
 COMPLY WITH FBC1608.2.2.1 THROUGH
 1608.2.2.3.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2004-02-18 Cont ID  
Sent By shill Date 2004-02-18 Time 09:30 Rev Time 0.50
Received By shill Date 2004-02-18 Time 09:30 Sent To  
Notes
2004-02-18 00:00:00SHORING/RESHORE INSPECTION, FRANCISCO
 BERMUDEZ, PE (2/4/4) AND MARK MOSBAT, PE
 (2/4/4), POUR #24, 5TH LEVEL LOFT

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2003-10-01 Cont ID  
Sent By csiegber Date 2004-02-05 Time 10:25 Rev Time 0.00
Received By hpiskura Date 2003-10-01 Time 13:44 Sent To  
Notes
2003-10-01 00:00:00REVISIONS DATED 7/9/03
  
 BRITO-COHAN LETTER DATED 7/11/03 SIGNED
 AND SEALED BY LAWRENCE S. COHAN RE:
 SUBSTITUTION OF FOAM CORE MOLDINGS FOR
 EXTERIOR TRIM.
  
 THE USE OF THIS PRODUCT WAS PREVIOUSLY
 DENIED PRIOR TO ISSUANCE OF THE PERMIT
 WITH CITATIONS OF THE PERTINENT CODE
 SECTIONS FROM THE FBC WHY IT IS
 PROHIBITTED.
  
 FBC 1404.1.1 LIMITS ARCHITECTURAL TRIM
 OF TYPE VI CONSTRUCTION TO BUILDINGS OF
 THREE STORIES OR 40' IN HEIGHT WHEN THE
 BUILDING IS OF TYPE I, II, IV OR V
 CONSTRUCTION.CITY PLAZA IS TYPE I
 CONSTRUCTION AND HIGHER THAN 40'.
  
 FBC F102.2.7 AS AMENDED BY THE CITY
 ALLOWS ARCHITECTURAL TRIM ON BUILDINGS
 IN THE FIRE DISTRICT TO BE ONLY OF
 NON-COMBUSTIBLE MATERIALS OR FIRE
 RETARDANT TREATED WOOD.CLEARLY, THE
 FOAM COATED WITH 0.040" OF POLYURETHANE
 AS DESCRIBED IN THE UNIVERSAL FOAM, INC.
 LETTER IS NEITHER.
  
 THE ARCHITECT'S LETTER ASSERTS THAT A
 FLAME SPREAD OF 25 OR LESS AS DESCRIBED
 IN FBC 803.2 IS EQUIVALENT TO THE CODE
 REQUIREMENTS.
  
 FBC (OR THE FORMER SBC) 803.2 PERTAINS
 TO INTERIOR FINISHES.THIS IS EXTERIOR
 ARCHITECTURAL TRIM.NOTE WORTHY IS 803.
 4 FOAM PLASTICS, THAT PROHIBITS FOAM
 WITH AN EXCEPTION FOR MOLDINGS AND
 SIMILAR, LIMITED TO A MAXIMUM THICKNESS
 OF 1/2" AND A MAXIMUM WIDTH OF 4".
 FURTHER, IT IS CONDITIONED UPON FOAM
 HAVING A DENSITY OF 20 LB/CU FT, NOT
 THE 1.25 LB/CU FT AND TICKNESSES OF 6"
 AND INDETERMINATE WIDTH CALLED FOR IN
 THE UNIVERSAL FOAM, INC. LETTER.
  
 ATTACHED TO THE ARCHITECT'S LETTER FOR
 DATA TO SUBSTANTIATE HIS EQUIVALENCY
 ASSERTION WERE COPIES OF REPORTS FROM
 RADCO LABORATORIES TO THE CARPENTER
 INSULATION COMPANY.
  
 THE PRODUCTS AND ASSEMBLIES IN THE
 REPORTS SUCH AS DRYVIT, PAREX AND STO,
 ARE PERMITTED TO BE USED WHEN INSTALLED
 IN ACCORDANCE WITH THEIR LISTING,
 CURRENT RECOGNIZED EVALULATION REPORT,
 AND MANUFACTURER'S PUBLISHED
 INSTRUCTIONS.
  
 ONE LETTER IS FOR A UL LISTING FOR ROOF
 INSULATION WHICH IS COVERED BY OTHER
 CODE SECTIONS AND NOT A COMPARABLE TO
 THE PROPOSED USE.FURTHER, AS ALL OF
 THE OTHER TEST LETTERS, THE FOAM
 PRODUCT MEETS THE DEFINITION OF A
 COMBUSTIBLE MATERIAL AS DEFINED IN FBC
 202.
  
 IT SHOULD BE NOTED THAT THE
 INTRODUCTION TO THE TEST REPORTS
 CONTAINS THE DISCLAIMER THAT THE TEST
 IS NOT ACCURATE FOR CERTAIN PLASTICS.
  
 THE ARCHITECT'S LETTER SPEAKS TO THE
 ALLOWED USE OF FIRE RETARDANT TREATED
 WOOD.THE DEFINITION OF FRTW SETS OUT
 CRITERIA FOR SPECIFIC TESTING AND TIMES
 TO BE USED WITH ASTM E-84.THE LETTERS
 DO NOT REFLECT THOSE. IN FACT THE SGS
 U.S. LETTER FOR FUTURA COATINGS, IN THE
 OBSERVATION SECTION DESCRIBES "FLAMING
 PIECES FALLING TO THE FLOOR OF THE
 CHAMBER AFTER 2 MINUTES".
  
 THE CHARACTERISTICS OF FOAM AND FRT
 WOOD UNDER FIRE CONDITIONS ARE NOT THE
 SAME NOR IS THIS DEMONSTRATED IN THE
 DATA PROVIDED THUS FAR.
  
 MATERIAL MEETING THE DEFINITION OF
 NON-COMBUSTIBLE IS REQUIRED.
  
 A DEMONSTRATION OF COMPLIANCE WITH FBC
 2603.8 FOAM INSULATION, SPECIAL
 APPROVAL IS A MORE LIKELY "EQUAL AND
 ALTERNATE" THEN THE ARGUMENT PROVIDED.
 IT INCLUDES TESTING IN THE "END USE
 CONFIGURATION".

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-30 Time 14:57 Rev Time 0.00
Received By hpiskura Date 2003-09-29 Time 12:48 Sent To  
Notes
2003-09-29 00:00:00CAPFORM SHORING LETTERS DATED 9/4/03,
 9/17/03 AND 9/18/03 SIGNED AND SEALED
 BY WILLIAM H. BLUE, PE.
  
 FBC 105.12 REQUIRES SHORING FOR
 THRESHOLD BUILDINGS TO BE DESIGNED AND
 "INSPECTED" BY A FL. LICENSED
 ENGINEER.
  
 THE FIRST SENTENCE OF THE LETTERS READ
 "ENNIO MARIN, MY DESIGNATED ON SITE
 REPRESENTATIVE,"
  
 PLEASE ESTABLISH CLEARLY THAT THE
 INSPECTIONS WERE PERFORMED BY A FLORIDA
 LICENSED PROFESSIONAL ENGINEER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2003-08-28 Cont ID  
Sent By csiegber Date 2003-09-24 Time 16:14 Rev Time 0.00
Received By hpiskura Date 2003-08-28 Time 12:31 Sent To  
Notes
2003-08-28 00:00:00NOA'S AND TEST REPORTS SUBMITTED 8/28/03
  
 PLEASE PROVIDE AN INSTALLATION AND
 LOCATION SCHEDULE, MARK COMPONENTS TO
 BE USED IN THE INDIVIDUAL REPORTS WHERE
 APPLICABLE.
  
 NOA 03-0401.06 HAS AN ILLEGIBLE DRAWING.
  
 PLEASE PROVIDE A NOTE THAT THESE REPORTS
 HAVE BEEN REVIEWED BY THE ENGINEER OF
 RECORD FOR CONFORMANCE WITH HIS DESIGN
 INTENTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-08-27 Cont ID  
Sent By csiegber Date 2003-08-27 Time 14:42 Rev Time 0.00
Received By hpiskura Date 2003-07-24 Time 11:21 Sent To  
Notes
2003-07-28 00:00:00PROVISO:
  
 THE FOAM MOULDINGS SHOWN ON SHEETS A1108
 AND A1108A MUST HAVE A TEST REPORT AS
 NON-COMBUSTIBLE IN ACCORDANCE WITH FBC
 202 DEFINITIONS.INFORMATION PROVIDED
 TO DATE INCLUDING THE LETTER DATED
 7/11/03 AND CITING REPORTS TESTED TO
 ASTM E-84, DOES NOT SHOW TESTING TO ASTM
 E-136.
  
 THE USE OF COMBUSTIBLE EXTERIOR
 (ARCHITECTURAL) TRIM IS PROHIBITED BY
 FBC F102.2.7 AS AMENDED BY THE CITY AND
 LIMITED BY FBC 1404.1.1.
  
 PLEASE PROVIDE THE INFORMATION BEFORE
 INSTALLATION OF THE PRODUCTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-05-12 Cont ID  
Sent By sgraham Date 2003-06-06 Time 16:44 Rev Time 0.00
Received By hpiskura Date 2003-05-06 Time 13:57 Sent To  
Notes
2003-05-12 00:00:001 THE ARDAMAN UNDERPINNING SCHEME IS
 REQUIRED TO BE SIGNED AND SEALED WHEN
 SUBMITTED FOR PUBLIC RECORD.
  
 2ENERGY CODE FORMS IN ACCORDANCE WITH
 FBC 13-101.1.1 HAVE NOT BEEN PROVIDED
 (FORM 400C)
  
 3 SPEC 05520-1 HANDRAILS HAS DESIGN
 LOADS NOT IN ACCORDANCE WITH FBC 1608.2.
  
 4IF TEST AND/OR NOTICE OF ACCEPTANCE
 REPORTS FOR THE ROOF COVERINGS, DOORS
 AND WINDOWS ARE NOT INCLUDED WITH THIS
 PERMIT APPLICATION, SEPARATE PERMITS,
 FEES AND INFORMATION WILL BE REQUIRED.
  
 5THE ARCH/STRUCT SPECIFICATIONS ARE
 NOT SIGNED AND SEALED BY THE ENGINEER
 OF RECORD.
  
 6SPEC 07240-1 EPS FOAM TRIM IS
 PROHIBITTED BY FBC F102.2.7 AMENDED AND
 FBC 1404.
  
 7SHEET A 1.03, THE TOTAL NUMBER OF
 RESIDENTIAL UNITS IS NOT CLEAR.
  
 8FBC 1006.1.1 REQUIRES EXIT STAIRS TO
 BE ENCLOSED WITH FIRE RATED
 CONSTRUCTION AND THE OPTION OF FBC
 412.11 #5 IS APPLICABLE AS WELL.
 STAIRS SHOWN AS #5, #6, #8 AND #10 DO
 NOT COMPLY, PLEASE REVISE AS NECESSARY.
  
 9SHEET LS 1.03, UNITS 1, 2, 3, 5, 6,
 9, 10, 13, 16, 27, 30, 33, 34, AND 38
 HAVE TRAVEL DISTANCE GREATER THAN 75'
 TO THE ENTRANCE TO THE EXIT ACCESS AND
 DO NOT COMPLY WITH FBC 1004.1.2.SEE
 ALSO FBC 1004.1.4.
  
 10SHEET M7.02, SEQ OF OP NOTES C #1 &
 #2 CITES .005 WC DIFFERENTIAL PRESSURE.
 MINIMUM IS 0.05 PLEASE REVISE
 NECESSARY.REFERENCES ON THIS SHEET
 AND M4.03 TO ELEVATOR PRESSURIZATION
 ARE NOT REFLECTED IN THE FAN SCHEDULE
 ONM5.03.PLEASE CLARIFY.
  
 11SHEET M 4.03 CALLS FOR A STATIC
 PRESSURE SENSOR SET TO MAINTAIN 0.75".
 THE MAX PRESSURE WATER COLUMN ALLOWED
 BY FBC 1005.6.9.9 IS 0.35".
  
 12THE PLANS DO NOT INDICATE A
 DAMPERED RELIEF OR EXHAUST FAN AT THE
 TOP TO PROVIDE THE MINIMUM 2500 CFM
 DISCHARGE.
  
 13THE UNSIGNED, UNDATED LETTER
 "RESPONSE TO BUILDING DEPARTMENT
 COMMENTS" ON THE BRITO COHAN LETTER
 HEAD HAS BEEN REVIEWED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-03-07 Cont ID  
Sent By sgraham Date 2003-03-05 Time 09:48 Rev Time 0.00
Received By hpiskura Date 2003-03-01 Time 10:21 Sent To  
Notes
2003-03-07 00:00:00PAID PLAN REVIEW, NOT A PERMIT
 APPLICATION.
  
 AT TIME OF PERMIT APPLICATION, THE
 ENERGY CODE CALCULATIONS ARE REQUIRED
 TO BE SIGNED, DATED AND SEALED BY THE
 PREPARER. FBC 13-103.1
  
 COMPLETE SPECIFICATIONS HAVE NOT BEEN
 PROVIDED, THEY WILL BE NECESSARY FOR
 THE PERMIT APPLICATION.SEE FBC 104.2.1
  
 CONCURRENT WITH THE PERMIT APPLICATION
 COMPLIANCE WITH FBC 1803.1.3 AND 1803.2
 MUST BE DEMONSTRATED.
  
 ITEM #6 UNDER BUILDING CODE INFO ON
 SHEET LS 1.00 DECLARES FIRE RATING
 REDUCTIONS APPLIED.SEE FBC TABLE 600
 FOOTNOTE (L) FORTHE LIMITATIONS.
 EXTERIOR WALLS, SHAFT ENCLOSURES AND
 OCCUPANCY SEPARATIONS ARE NOT INCLUDED.
  
 SHEET LS NOTE 9 SPEAKS TO GLASS IN DOORS
 HAVING A SPRINKLER ON EACH SIDE.
 OPENING PROTECTIVES MUST COMPLY WITH
 FBC 705.
  
 NOTE 8 ON LS 1.00 IMPLIES AND IMPROPER
 APPLICATION OF FBC TABLE 600.
 HORIZONTAL MEASUREMENTS ARE FROM THE
 WALL PLANE AND VERTICAL MEASUREMENTS
 ARE PER FLOOR, FROM FINISH FLOOR TO
 CEILING ABOVE.
  
 NOTE 18 SPEAKS TO FOAM MOLDINGS.
 ARCHITECTURAL TRIM IS REQUIRED TO BE
 NON-COMBUSTIBLE OR FRT WOOD.SEE FBC
 F102.2.7 AS AMENDED BY THE CITY AND FBC
 1404.
  
 SEVERAL OF THE MEZZANINE UNITS SHOW A
 TRAVEL DISTANCE >75'. FBC 1005.7.1
 REQUIRES TWO MEANS OF EGRESS COMPLYING
 WITH FBC 1004.1.4.
  
 THE STAIRS SHOWN AS #5, #7 AND #10 DO
 NOT COMPLY WITH FBC 1006.1.1 AND FBC
 412.11 #5.
  
 SHEET A11.05. IF THE HC PARKING SPACES
 SERVICE THE GROUP "B" LIVE WORK LOFT
 THEY MUST BE 12' WIDE IN ACCORDANCE
 WITH FBC 11-4.6 INCLUDING THE 98"
 VERTICAL CLEARANCE.
  
 SHEET A6.05 SHOWS POLYSTYRENE TO VE
 USEDFOR EXTERIOR TRIM.THIS IS
 PROHIBITED BY FBC F102.2.7 (AMENDED)
 FBC 1404
  
 SHEET A11.01, SHOW A SPECIFIC FRAMING
 AND FASTENING DETAIL FOR THE SUSPENDED
 GYP BOARD CEILINGS. FBC 104.2.
  
 THE WALL SHOWN AS W19 ON SHEET S-32 IS
 ABERING WALL AND IS REQUIRED TO BE FIRE
 RATED.SEE FBC TABLE 600.
  
 THE WIND TUNNEL TEST REPORT EXCLUDES
 THE ROOF TILE FROM ITS FINDINGS.
 PROVIDE THE NECESSARY INFORMATION IN
 ACCORDANCE WITH FBC 104.2.1.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-07 Cont ID  
Sent By hpiskura Date 2002-05-07 Time 14:00 Rev Time 0.00
Received By hpiskura Date 2002-04-30 Time 14:38 Sent To  
Notes
2002-05-07 00:00:00THE PLAN PACKAGE IS INCOMPLETE AND A
 CLOSE AND CRITICAL PLAN REVIEW WAS NOT
 POSSIBLE.
  
 SPECIFICATIONS, SOIL TEST REPORTS AND
 WIND TUNNEL TESTING INFORMATION MUST BE
 INCLUDED AT THE TIME OF PERMIT
 APPLICATION.
  
 A RECENT PROPERTY SURVEY AND A
 DIMENSIONED SITE PLAN WILL BE REQUIRED
 AT TIME OF PERMIT APPLICATION.
  
 SEE FBC 104.3.1 SO THAT IT MAY ACT AS A
 GUIDELINE AS TO THE INFORMATION TO BE
 INCLUDED WITH THE PLANS TOGETHER WITH
 THE CRITERIA SPECIFIED IN FBC 1606.1.7.
  
 THE PROPOSED BUILDING WILL BE TYPE I FS
 CONSTRUCTION, GROUP R2 OCCUPANCY AND
 SIXTEEN STORIES SINCE THE "ROOF
 STRUCTURES" EXCEED 1/3 OF THE ROOR AREA
 AS PROVIDE FOR IN FBC 1511.1.1.2.
  
 A THRESHOLD BUILDING INSPECTION PLAN AND
 INSPECTOR WILL BE REQUIRED AS STATED
 INFBC 105.13.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE, AND A COPY OF
 THE PAID RECEIPT ATTCHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 STAIR #1 DOES NOT PROVIDE A PROTECTED
 EXIT TO THE EXTERIOR OF THE BUILDING
 NOR DOES IT COMPLY WITH FBC 1010.1.
  
 SHEET LS1 DEPICTS THE WEST END OF THE
 TWO CORRIDORS DISCHARGING INTO THE
 GARAGE.THE PLANS ALSO INDICATE STEPS
 THERE WHICH DO NOT COMPLY WITH FBC
 1003.2.7, A RAMP IS REQUIRED.
  
 SEE FBC 1003.2.7 FOR THE STEP
 SPECIFICATIONS AT THE LOBBY DISCHARGE
 ON THE EAST SIDE.
  
 THE LS PLANS DO NOT INDICATE THE
 OCCUPANT LOADS SERVED OR THE EXIT
 WIDTHS.SEE FBC 104.2.
  
 SHEET LS 2 AND OTHERS, DO NOT INDICATE
 ANY EXITS ON THE WEST SIDE OF THE
 GARAGE.
 FBC 411.2.4 SPECIFICALLY PROHIBITS
 TRAVEL ON THE PARKING RAMPS FOR EGRESS.
  
 STAIR SECTION 3 ON SHEET A7.04 SHOWS A
 RISE OF MORE THAN TWELVE FEET FOR A
 SINGLE FLIGHT OF STAIRS.SEE FBC
 1007.4.1.
  
 THE PLANS SHOW THE WALL ON THE WEST SIDE
 AS A ZERO LOT LINE, FBC TABLE 600
 REQUIRES A FOUR HOUR FIRE RATING FOR
 EXTERIOR BEARING WALLS.THE INTERIOR
 BEARING WALLS ARE REQUIRED TO BE THREE
 HOUR RATED.INCLUDE A FIRE DESIGN
 NUMBER FOR THE MASONRY WALLS.
  
 A COMPLETE REVIEW FOR TABLE 600 IS NOT
 POSSIBLE WITHOUT A SURVEY / SITE PLAN.
  
 THE USE OF EIFS TRIM IS NOT ALLOWED BY
 FBC APPENDIX F 102.2.7 AS AMENDED BY
 THE CITY AND FBC 1404.1
  
 THE PLANS DO NOT SHOW A METHOD OR
 SCHEDULE FOR THE PROTECTION OF FLOOR
 AND WALL PENETRATIONS IN ACCORDANCE
 WITH FBC 705.4.
  
 THE PLANS DO NOT CLEARLY DEPICT THE
 PARAPETS OR GUARDRAIL SYSTEM TO BE USE
 ON THE ROOF AREAS.SEE FBC 1015.
  
 SEE FBC 2810 FOR MARKING AND OTHER
 REQUIERMENTS FOR INTAKE VENTS ON
 LOCATED ON THE ROOF.
  
 SHOW SITE ACCESSIBILITY AS REQUIRE BY
 FBC 11-4.1.2 (1).
  
 FBC 11-4.1.2 (5) (B) REQUIRES TWELVE
 FEET WIDE PARKING SPACES FOR THE
 HANDICAP.
  
 CITY AMENDMENTS TO FBC 2111.1.9 REQUIRE
 A 1.5 INCH RECESS IN THE FLOOR SLABS FOR
 EXTERIOR MASONRY WALLS.
  
 HOW WILL THE SMOKE VENTING OPENINGS
 ALTERNATIVE CONTAINED IN FBC 412.5 (1)
 BE ACCOMPLISHED IN THE WEST WALL
 ELEVATIONS?
  
 THE FIRE PROTECTION PLANS ARE
 INCOMPLETE, SEE SECTION 8-1.1.1 OF NFPA
 13-99 FOR INFORMATION TO BE PROVIDED ON
 THE PLANS.

Review Stop E ELECTRICAL
Rev No 27 Status F Date 2006-03-29 Cont ID  
Sent By jleahy Date 2006-03-29 Time 10:46 Rev Time 4.00
Received By jleahy Date 2006-03-29 Time 10:46 Sent To  
Notes
2006-03-29 00:00:00PG. E3.01GENERATOR DETAILS BLANK?
  
 PG. E3.02MAIN ELECTRICAL ROOM NOT TO
 PLANS
  
 6TH FLOOR TRANSFORMERS NOT
  
 CORRECT.
  
 PG. E2.24KITCHEN AND FITNESS ROOM
 REVISED. NOT TO PLAN
  
 PG. E2.52NO GFI PROTECTION FOR LIGHTS.
 AT THE FOUNTAIN.
  
 PG. E5.3PLAN CALLS FOR METAL ROOF?
  
 PG. E5.12LABEL SYSTEM NOT USED FOR
 PANELS
  
 PG. E5.10PVC TO BE USED ON PLAN MC
 INSTALLED.
  
 #2/0 USED ON RUNS OVER 200'
  
 LONG.
  
 PG. E4.01METAL LABELS NOT USED.
  
 PG. E6.01FUSES NOT IN THE FIXTURES.
  
 PG. E2.03NO SHUNT TRIP INSTALLED OR
 GENERATOR CONTROLER.
  
 PG. E2.51NOTE 4 WIRE SIZES?
  
 PAGE WITH ALL THE NOTES THAT NEED TO BE
 ADDRESSED WAS NOT SUBMITTED WITH PLANS.
  
 MASTER LABEL FOR THE LIGHTNING
 PROTECTION SYSTEM NOT INSTALLED.
  
 WEATHERPROOF HORN/STROBE ATTACHED TO A
 NON-WEATHERPROOF BOX STICKING OUT 2".
  
  
  

Review Stop E ELECTRICAL
Rev No 26 Status P Date 2006-03-03 Cont ID  
Sent By jleahy Date 2006-03-03 Time 09:08 Rev Time 0.00
Received By jleahy Date 2006-03-03 Time 09:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 25 Status P Date 2006-01-13 Cont ID  
Sent By jleahy Date 2006-01-13 Time 07:00 Rev Time 0.30
Received By jleahy Date 2006-01-13 Time 07:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 24 Status P Date 2005-09-19 Cont ID  
Sent By jleahy Date 2005-09-19 Time 14:00 Rev Time 0.45
Received By jleahy Date 2005-09-19 Time 14:00 Sent To B
Notes
2005-09-19 00:00:00REVISION FOR LIGHT FIXTURES ON ROOFJL

Review Stop E ELECTRICAL
Rev No 23 Status F Date 2005-09-19 Cont ID  
Sent By jleahy Date 2005-09-19 Time 07:16 Rev Time 5.00
Received By jleahy Date 2005-09-19 Time 09:28 Sent To  
Notes
2005-09-19 00:00:00REVISION 66
  
 PAGE 2.02SUBMIT DETAIL ON LOW VOLTAGE
 TRANSFORMER FOR LOW VOLTAGE
 ROPE LIGHTINGSIZE OF TRANS
 OVERCURRENT PROTECTION.
 SHOW LOCATION OF TRANS, DISC.
  
 PAGE 3.026TH FLOOR ELECTRICAL ROOM
 SHOWS NEW TRANSFORMER WHAT
 DOES IT FEED?
 IF THE CHANGE IS ONLY ONE
 TRANSFORMER PLEASE DON'T
 CLOUD WHOLE ROOM TAKES A LONG
 TIME TO FIGURE OUT WHAT THE
 CHANGE IS!!!!!!!!!!
  
 PAGE 4.016TH FLR CHANGE NOT SHOWN ON
 RISER.
  
 NOTE K-8 ??? WHAT SIZE CKT.
 BREAKER IS A 150 HP ???????
  

Review Stop E ELECTRICAL
Rev No 22 Status F Date 2005-07-26 Cont ID  
Sent By dpalmer Date 2005-07-26 Time 20:17 Rev Time 0.25
Received By dpalmer Date 2005-07-26 Time 20:17 Sent To B
Notes
2005-07-26 00:00:00********** UNSAT ************
  
 LIGHTING SUBMITTALS FOR ROOF POLE LTS.
  
  
 1)NOTE: PLEASE SUBMIT WIND LOADING
 CALCULATIONS FOR LT POLES PER FBC 140
 MPH.
 PLEASE SEE AL REVISIONS, DETAILS FOR LTS
 ETC MUST BE DONE BY THE DESIGNER'S OF
 RECORD.
 PLANS MUST ALSO BE SIGNED, DATED AND
 SELAED BY THE ENGINEERS/ ARCHITECT;S OF
 RECORD.
 FS 481.221,471.025
  
 LT SUBMITTIAL ROUTED TO BLDG REVIEW FOR
 WIND LOAD COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 21 Status P Date 2005-07-12 Cont ID  
Sent By jleahy Date 2005-07-12 Time 09:47 Rev Time 0.30
Received By jleahy Date 2005-07-12 Time 09:47 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 20 Status P Date 2005-07-12 Cont ID  
Sent By jleahy Date 2005-07-12 Time 09:47 Rev Time 0.30
Received By jleahy Date 2005-07-12 Time 09:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 19 Status P Date 2005-07-12 Cont ID  
Sent By jleahy Date 2005-07-12 Time 09:45 Rev Time 0.30
Received By jleahy Date 2005-07-12 Time 09:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 18 Status P Date 2005-07-12 Cont ID  
Sent By jleahy Date 2005-07-12 Time 09:45 Rev Time 0.01
Received By jleahy Date 2005-06-01 Time 07:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 17 Status P Date 2005-05-17 Cont ID  
Sent By dpalmer Date 2005-05-17 Time 07:23 Rev Time 0.25
Received By dpalmer Date 2005-05-17 Time 07:23 Sent To  
Notes
2005-05-17 00:00:00LTR PERTAINING TO EQUIPMENT GROUNDING
 BETWEEN 200 AND 250 FT AS #4 OK PER
 ENGINEER.
 OK PER CODE.

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2005-05-03 Cont ID  
Sent By dpalmer Date 2005-05-03 Time 20:25 Rev Time 0.75
Received By dpalmer Date 2005-05-03 Time 19:51 Sent To  
Notes
2005-05-03 00:00:00REV'S IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 15 Status P Date 2005-05-03 Cont ID  
Sent By dpalmer Date 2005-04-13 Time 19:48 Rev Time 0.00
Received By dpalmer Date 2005-04-13 Time 20:23 Sent To  
Notes
2005-04-13 00:00:00REDLINED OCP FOR BATHS SOME SHOWN AS
 15A. 210.52D,210.11C3
 REDLINED, SOME BRANCH CIRCUITS SHOWN:
 SHOWS 20A ON #14 AWG.240.4,310.16
2005-04-01 00:00:00REV'S IN FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 14 Status N Date 2005-04-13 Cont ID  
Sent By dpalmer Date 2005-04-13 Time 19:47 Rev Time 0.00
Received By dpalmer Date 2005-04-01 Time 11:06 Sent To  
Notes
2005-04-13 00:00:00SHEETS REVISED INTO ONE SET IN THREE
 ROLLS.
2005-04-01 00:00:00REV'S IN FOR REVIEW.
 LEEROY HILL TO COME IN ON 4/4 TO GO OER
 PLANS.

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2005-02-11 Cont ID  
Sent By dpalmer Date 2005-02-11 Time 09:53 Rev Time 1.25
Received By dpalmer Date 2005-02-11 Time 09:53 Sent To  
Notes
2005-02-11 00:00:00**** ITEMS REDLINED ****
  
 1)NOTE: PLEASE SEE NOTE #2 FROM REVIEW
 DATED 8/12/04 HAS NOTE BEEN
 RESUBMITTED.
 PLEASE SEE OTHER NOTES FROM THAT REVIEW
 HAVE BEEN ADDED TO PLANS SUBMITTED.
  
 2)NOTE: PLEASE 2.11 UNITS 36/37
 PENINSULAR. BOTH SAME DEVICE, YET ONE
 SHOWS APPL CIRUIT, THE OTHER SHOWN ON
 LIGHTING CIRCUIT.
  
 3)NOTE: PLEASE SEEE 2.04 WHAT APPEARS
 TO BE A MISSING RECEPT FOR
 PENINSULAR/WALL SPACE PER 210.52C1,C3,
 BUT NOT CLEAR. THIS IS TO BE CHECKED IN
 FIELD BY INSPECTOR..
  
 4)NOTE: PLEASE SEE E2.12, MISSING
 CIRCUIT # FOR STAIR ARE RECEPT.
  
 5)NOTE: PLEASE SEE E2.19, LTS NEAR TUB
 AREA, PER 410.4D.
  
  
 THE ABOVE ITEMS HAVE BEEN REDLINED AND
 HIGHLIGHTED ON PLANS FOR FIELD
 VERIFICATION BY ELECTRICAL INSPECTOR.
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2004-08-12 Cont ID  
Sent By dpalmer Date 2004-08-12 Time 13:41 Rev Time 4.00
Received By dpalmer Date 2004-08-12 Time 10:43 Sent To  
Notes
2004-08-12 00:00:00************ UNSAT *******************
  
 1)NOTE: PLEASE ONLY SUBMIT SHEETS WHICH
 ARE BEING REVISED/NEEDING REVIEW.
 PLEASE SEE THERE ARE MANY SHEETS THAT
 HAVE ALREADY BEEN SUBMITTED FOR REVIEW
 AND HAVE BEEN STAMPED ON PREVIOUS REVIEW
 'S.
  
 2)NOTE: PLEASE SEE EGRESS LTS/CONTROLS
 HAVE NOW BEEN REMOVED FROM UNIT ON FIRST
 FLR WHICH EXIT TO STREET. NEC 210.70
 LS 101 5-8.
 PLEASE SEE THAT SPEACIAL PERMISSION
 SHALL BE REQUIRED FOR REMOVAL OF THE
 REQUIRED EGRESS LTS/CONTROL PER CODES
 ABOVE.
 PLEASE ADDRESS THE ABOVE.
 PLEASE CLARIFY WHAT WILL EGRESS LT BE?
 ETC
  
 3)NOTE: PLEASE SEE SOME UNITS ARE MISS-
 -ING RECEPTS REQUIRED PER 210.52C3,C5
 PLEASE SEE 2.32 UNIT "M" KIT PENINSULAR.
 PLEASE SEE 2.33,2.34 UNIT "O1" FOR SAME.
  
 4)NOTE: PLEASE KNOW, LIGHTNING PROTECT-
 -ION NOW SUBMITTED TO MEET NFPA-780 IS
 OK.
 IF INSTALLED AND CERITIFIED BYA
 SUB-CONTRACTOR, A SEPARATE WILL BE
 REQUIRED.
  
 PLEASE BE SURE TO SEE POSSIBLE COMMENTS
 FROM OTHER REVIEWERS WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 ***** PLEASE REMOVE ALL OLD/VOIDED SHEET
 -S AND ONLY INSERT NEW SHEETS FOR REVIEW
 AND STAMPING. PLEASE REMOVE ALL SHEETS
 WHICH DO HAVE NEW REVISIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 11 Status N Date 2004-05-08 Cont ID  
Sent By dpalmer Date 2004-05-08 Time 15:48 Rev Time 0.33
Received By dpalmer Date 2004-05-08 Time 15:48 Sent To  
Notes
2004-05-08 00:00:00PLANS SUBMITTED APPEAR TO BE FOR BLDG
 REVIEW ONLY.
 NO ELECTRICAL PLANS LOCATED FOR REVIEW?

Review Stop E ELECTRICAL
Rev No 10 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-04-27 Time 13:55 Rev Time 0.50
Received By dpalmer Date 2004-02-19 Time 10:31 Sent To  
Notes
2004-02-19 00:00:00*************** NOTE***********
  
 LIGHTNING PROTECTION SYSTEM IS NOT PART
 OF THE ORIGINAL ELECTRICAL PERMIT.
 PLANS WERE NOTED : LIGHTNING PROTECTION
 TO BE UNDER SEPARATE PERMIT.
 PLEASE ALSO NOTE: ESE SYSTEMS ARE NOT
 PERMITTED BY CODE AT THIS TIME AND WILL
 NOT BE PERMITTED TO BE INSTALLED.
  
 PLEASE NOTE: ANY LIGHTNING PROTECTION
 SYSTEM(S) TO BE INSTALLED MUST MEET
 NFPA-780.
  
  
 IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2003-09-22 Cont ID  
Sent By dpalmer Date 2003-09-22 Time 21:31 Rev Time 1.01
Received By dpalmer Date 2003-09-22 Time 21:21 Sent To  
Notes
2003-09-22 00:00:00***** REV'S ***
 E 0.00,2.03,2.06,2.07,2.09,2.10,2.15,
 2.21,2.27,2.42.
  
 REDLINED MISSING SD IN BEDROOM #2 IN
 UNIT "D".2.27
 SD ALSO REDLINED TO BE MIN 3' FT.
  
 FHAR SHOWN AS 100.20S/ SHOULD BE 100.
 205.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2003-09-19 Cont ID  
Sent By dpalmer Date 2003-09-19 Time 12:41 Rev Time 1.00
Received By dpalmer Date 2003-09-19 Time 12:41 Sent To  
Notes
2003-09-19 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE E-SHEETS 4.02
 AND 1.00 FOR FEEDERS. 8SETS OF 500MCM
 ON ONE AND 8 SETS OF 600MCM ON OTHER?
  
 2)NOTE: PLEASE ALSO SEE RISER DIAGRAM,
 APPEARS TO HAVE 4000A SW BOARD "2MCR"
 FEEDING A 3000A ALUM, BUS DUCT?
 SHOWN AS K-7.
 PLEASE CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2003-08-27 Cont ID  
Sent By dpalmer Date 2003-08-27 Time 15:27 Rev Time 0.25
Received By dpalmer Date 2003-08-27 Time 15:27 Sent To  
Notes
2003-08-27 00:00:00REVISIONS TO FOLLOW FOR UNDERGROUND
 SERVICE CONDUITS AND CONDUCTORS.
 REDTAG ISSUED TO JOBSITE.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2003-08-21 Cont ID  
Sent By dpalmer Date 2003-08-21 Time 15:36 Rev Time 2.00
Received By dpalmer Date 2003-08-21 Time 15:36 Sent To  
Notes
2003-08-21 00:00:00************ UNSAT/HOLD *************
  
 ENGINEER HAS BEEN NOTIFIED THAT PLANS
 HAVE TO REVISED FOR SERVICE CONDUITS
 AND FEEDERS BEFORE PERMIT CAN BE ISSUED.
  
 PLEASE SEE D PALMER. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 561-805-6717

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-07-29 Cont ID  
Sent By dpalmer Date 2003-07-29 Time 06:02 Rev Time 3.50
Received By dpalmer Date 2003-07-29 Time 06:01 Sent To  
Notes
2003-07-29 00:00:00**LIGHTNING PROTECTION IS DONE BY
 A SUB CONTRACTOR SEPARATE PERMIT WILL
 BE REQ'D.
 PASSED PENDING FIRE REVIEW OF ELECTRICAL
 PLANS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-05-20 Cont ID  
Sent By dpalmer Date 2003-05-20 Time 13:12 Rev Time 3.00
Received By dpalmer Date 2003-05-20 Time 06:16 Sent To  
Notes
2003-05-20 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SEE SHEETS 5.12 AND 5.13
 OF ALL SETS. PLANS NOT SIGNED, DATED AND
 SEALED BY ENGINEER OF RECORD. PER
 FS 471.
  
 2)NOTE: PLEASE SEE 5.14, PLANS WERE
 REVISED W/ NOTE THAT INDICATES GFI
 PROTECTION FOR MSB, BUT NOT FOR 1MCR,
 2MCRS, 3MCRS(TYP). 230-95,240-13
  
 3)NOTE: PLEASE SEE PANELS THAT ARE
 REVERSED ON 2.12,2.13, AND 2.33.
  
 PLANS ARE COMING BACK FOR COMMENTS FROM
 OTHER REVIEWS. PLEASE ADDRESS THE ABOVE
 AT THIS TIME AND IF 2002 NEC WHICH IS
 REFERENECED ON MANY SHEETS CAN BE CHANG-
 -ED AT THIS TIME. IF NOT, THEN MUST BE
 REDLINED. I HAVE REDLINED ONE SET.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLANS HAVE HAD ALMOST ALL COMMENTS
 ADDRESSED AND ARE IN GOOD SHAPE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-05-08 Cont ID  
Sent By dpalmer Date 2003-05-08 Time 09:41 Rev Time 2.50
Received By dpalmer Date 2003-05-08 Time 09:41 Sent To  
Notes
2003-05-08 00:00:00********** PLEASE NOTE *********
  
 AS OF MEETING ON 5/1/03. WENT OVER PLANS
 AND FOUND ITEMS THAT NEEDED TO BE
 ADDRESSED. WAITING FOR NEW ELECTRICAL
 SHEETS TO BE BROUGHT IN AND REPLACE
 SHEETS IN SETS SUBMITTED FOR REVIEW ON
 5/1/03.
 AS REQUESTED BY STEPHAN BERJAN, NO
 ELECTRICAL REVIEW TO BE DONE UNTIL NEW
 SHEETS HAVE BEEN SUBMITTED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-03-11 Cont ID  
Sent By dpalmer Date 2003-03-11 Time 05:33 Rev Time 8.00
Received By dpalmer Date 2003-03-11 Time 05:33 Sent To  
Notes
2003-03-11 00:00:00****************** UNSAT ************
  
 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULES
 PER 210-12
  
 2)NOTE: PLEASE SEE MISSING FINAL LOAD
 ON APT 28 PANEL.
  
 3)NOTE: PLEASE PROVIDE GROUNDING DETAIL
 ON RISER DIAGRAM. PLEASE INCLUDE BLDG/
 FOOTER STEEL, COLD WATER. 250-50
  
 4)NOTE: PLEASE NOTE, MANY PAGES REFER
 TO PAGE E4.06 AND THIS PAGE WAS NOT
 SUBMITTED.?
 IT APPEARS PLANS SHOW A FPL VAULT ON
 EVERY OTHER FLOOR??
 PLEASE CLARIFY?
 ALL MAINS FOR BLDG ARE TO BE GROUPED
 PER 230-72.ALSO 230-70/230-2
 SHUNT TRIPS ARE NOT RATED FOR MEANS OF
 DISCONNECT. PLEASE SEE 230-76/230-79.
 IT IS SHOWN IN FIRE CONTROL ROOM, SHUNT
 TRIPS FOR METER CENTERS.
 PLEASE SEE THIS IS NOT PERMITTED. PLEASE
 SEE ABOVE NOTES PER NEC AND ALSO PER
 LOCAL FIRE MARSHALLS OFFICE. ALL MAINS
 ARE TO BE GROUPED IN CLOSE PROXIMITY.
  
 5)NOTE: PLEASE SEE RISER, SHOWS DP REH
 FEEDING PANEL DP REL. PLEASE SEE 5.14
 PANEL SCHEDULE FOR DP_REL IS MISSING
 COMPLETED INFORMATION FOR DP REL?
 PLANS SEEM TO BE MISSING DP REL PANEL
 SCHEDULE?
  
 6)NOTE: PLEASE CLARIFY GFI PROTECTION
 FOR 3000A MAIN? 230-95/240-13
 PLEASE ALSO NOTE ON PLANS FOR REQ`MENTS
 OF 230-203
  
 7)NOTE: PLEASE PROVIDE NOTE FOR VERTICAL
 CONDUCTOR SUPPORT PER 300-19
  
 8)NOTE: PLEASE PROVIDE INFORMATION/SPECS
 FOR FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE SEE 695-4/695-4-B1/ 695-5
 PLEASE ALSO PROVIDE CODE LETTER INFOR-
 -MATION SET ON NAMEPLATE. PLEASE SEE
 TABLES UNDER 430
  
 9)NOTE: PLEASE CORRELATE KW RATING OF
 GENERATOR. RISER SHOWS 900KW/750KVA
 AND 3.01 SHOWS 750KW?
  
 10)NOTE: PLEASE CORRELATE CONDUIT FOR
 FIRE PUMP. RISER SHOWS ONE-2 1/2"
 CONDUIT AND 1.0 SHOWS 4"?.
  
 11)NOTE:PLEASE PROVIDE NOTED INFORMATION
 FOR FIXTURES THAT ARE REQ`D FOR
 EMERGENCY ILLUMINATION TO MEET 700-16.
 PLEASE SEE FIRE PUMP ROOM AND OTHER
 LOCATIONS.
  
 12)NOTE: PLEASE SHOW OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 ED. PER 210-8-A6
  
 13)NOTE: AS PER 240-24E PANELS ARE NOT
 TO BE LOCATED IN BATHROOMS. (2.01)
  
 14)NOTE: PLEASE PROVIDE/CLARIFY WHERE
 CAN LIGHTING FOR OUTSIDE OF BLDG BE
 FOUND? PLEASE CLARIFY HOW 210-70 IS MET?
  
 15)NOTE: PLEASE COMPLETE APT/UNIT LAYOUT
 -S. SOME PAGES REFER OTHER PAGES AND
 THERE IS NOTHING ON THOSE PAGES TO
 CORRELATE NOTE?? THIS WAS NOTED ON
 FIRST REVIEW ALSO. PLEASE SEE PAGE #`S
  
 16)NOTE: PLEASE CLARIFY WHAT APPEARS TO
 BE AN ISLAND IN UNIT 12L? AND ANY OTHERS
 PLEASE SEE 210-52-C-2
  
 17)NOTE: PLEASE SEE MANY OTHER UNITS
 SHOWING TWO PANELS??
  
 18)NOTE: PLEASE SEE AREA WHERE LOFTS/
 MEZZ LEVEL RAILS ARE. RECEPT SPACING IS
 STILL REQ`D TO MEET 210-52
 RAILS ARE CONSIDERED WALL SPACE.
  
 19)NOTE: SIGNAGE REQ`D FOR ALL ELEC-
 -TTRICAL ROOMS.
  
 20)NOTE: PLEASE SEE 210-52-C1 FOR
 SPACING OF COUNTERSPACE RECEPTS.
  
 21)NOTE: PLEASE SEE PLANS, SOME UNITS
 MISSING SD`S ON 2ND LEVELS.
  
 22)NOTE: PLEASE SEE PLANS, SOME UNITS
 ARE MISSING RECEPTS FOR WALL SPACING
 2'/6'/12'. 210-52
  
 23)NOTE: PLEASE SEE G-1 ON 2.31,
 PLEASE CLARIFY 4-5 HORN/SROBES IN
 BEDROOM??
  
 24)NOTE: PLEASE SEE PANEL UNIT N ON
 2.32 SHOWN FACING INTO BATHRROM RECEPT??
 110-26 ETC.
  
 25)NOTE: PLEASE SHOW SERVICE RECEPTS
 ON ROOF 210-63
  
 26)NOTE: NOT ENOUGH INFORMATION FOR
 POOL AREA. PLEASE SUBMIT FOR MIN REQ`
 -MENTS.
  
 PLEASE NOTE, THIS IS THE SECOND TIME
 PLANS HAVE BEEN REVIEWD FOR THIS PROJECT
 PLEASE SEE FS/FAC 553-80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS.
  
 PLEASE ALSO NOTE, MANY COMMENTS ABOVE
 PERTAIN TO MORE THAN ONE SHEET AND/OR
 PAGE. PLEASE GO OVER ENTIRE SET BEFORE
 RESUBMITTING.
  
 PLEASE ADDRESS AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL. IF A MEETING
 IS DESIRED TO GO OVER COMMENTS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-06 Cont ID  
Sent By dpalmer Date 2002-05-06 Time 06:32 Rev Time 0.00
Received By dpalmer Date 2002-05-01 Time 20:25 Sent To  
Notes
2002-05-06 00:00:00*************** UNSAT *****************
  
 PLEASE NOTE THAT PLANS ARE NOT COMPLETE
 FOR SUFFICIENT REVIEW.
 PLEASE ALSO NOTE THAT SOME OF THE
 NOTES ARE SET AS TYPICAL FOR MANY UNITS.
  
  
 1)NOTE: PLEASE NOTE,E1.02 NOTE SAYS TO
 SEE E0.00 FOR ELEC RM DETAIL? PLEASE
 NOTE ELEC RM IS NOTE SHOWN ON THAT PAGE.
  
  
 2)NOTE: PLEASE NOTE THAT SOME NOTE ON
 E1.01,1.02 ETC MENTION TO SEE E1.05 FOR
 TYP UNITS AND THOSE UNITS ARE NOT SHOWN
 ON OTHER SHEET.? PLEASE NOTE THAT THIS
 IS TYP FOR OTHER SHEETS AS WELL.
  
 3)NOTE: PLEASE NOTE E1.05 ,SOME UNITS
 SHOWING TWO PANELS? (TH-1,TH-2 ETC )
 PLEASE CLARIFY. MISPRINT?
  
 4)NOTE: PLEASE NOTE THAT SOME UNIT IN
 THE BEGINING PART OF THE SETS ARE NOT
 SHOWING CATV. PLEASE NOTE IF CATV IS
 GOING TO BE THOSE UNITS, PLEASE REVISE
 AND SHOW.
  
 5)NOTE: PLEASE NOTE TYPICAL OF ALL UNITS
 PLEASE SHOW/CLARIFY GFI/GFI PROTECTION
 FOR ALL JACUZZI/SPA UNITS. 680-42
  
 6)NOTE: PLEASE NOTE MISSING HALLWAY REC
 210-52H. PLEASE NOTE MISSING INSOME UNIT
 -S.
  
 7)NOTE: PLEASE NOTE TYPICAL FOR MANY
 UNITS, 2` 6 ` RULE FOR RECEPT SPACING
 PER 210-52. PLEASE NOTE SOME UNITS ARE
 MISSING MORETHAN OTHERS.
  
 8)NOTE: PLEASE NOTE E1.20 PANEL SHOWN
 IN THE MIDDLE OF THE ROOM WITH OTHER
 EQUIPMENT?? PLEASE CLARIFY.
  
 9)NOTE: PLEASE NOTE THAT ALL SMOKE
 DETECTORS ARE TO BE A MIN OF 3' FROM
 BATHS RMS AND KITCHENS. NFPA-72 2-5.2.1.
 6.
  
 10)NOTE:PLEASE NOTE RECEPT SPACING FOR
 ALLKITCHENS COUNTERSPACES 210-52C-1
 PLEASE NOTE FOR 12", 24" ETC.
  
 11)NOTE: PLEASE NOTE PENINSULAR RECEPT
 SPACINGPER 210-52C-3. PLEASE NOTE THAT
 ANY INTERUPTION OF CONTINUOUS SPACE
 REQ`SADDTIONAL RECEPTS. (SINKS)
 * PLEASE NOTE MANY UNITS ARE MISSING
 RECEPTS PER 210-52C 1,2,3,4,5***
  
 12)NOTE: PLEASE NOTE E1.28 UNIT B2 SAYS
 SEE SIMULAR UNIT ON E1.29? PLEASE NOTE
 NOTHING SHOWN FOR THIS?
  
 13)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING PER 210-70. PLEASE NOTE MANY
 UNITS COMING INTO FOYER HAVE A FIXTURE/
 AND SOME DO NOT. PLEASE NOTE ANY OTHER
 LOCATIONS ON PLANS. SOME MISSING IN
 HALLWAYS AND /OR HABITABLE ROOMS.
  
 14)NOTE: PLEASE NOTE SOME PAGES/NOTES
 REFERENCE OTHER PAGES AND THAT INFORMAT-
 -ION IS NOT SHOWN. PLEASE GO OVER PLANS.
 E1.29ETC/
  
 15)NOTE: PLEASE NOTE OTHERS SHEETS/UNITS
 SHOWING TWO PANEL AND APPEAR TO BE
 A DOUBLE PRINT?
  
 16)NOTE:PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
 ROOF TOP.
  
 17)NOTE: PLEASE NOTE MISSING ELECTRICAL
 FOR ROOF TOP POOL/ POOL AREA /CABANAS??
  
 18)NOTE: PLEASE NOTE THAT SOME UNITS
 DO SHOW A/C UNIT CIRCUIT #`S ON PLANS
 BUT DO NOT CORRELATE WITH PANEL SCHEDULE
 (S). OTHER UNITS DO NOT SHOW ANY CIRCUIT
 #`S AT ALL. PLEASE SHOW .
 PLEASE NOTE SIZING OF OCP FOR AHU`S PER
 424-3B. PLEASE NOTE THAT KW RATINGS THAT
 ARE SHOWN DO NOT SEEM BE COMMON SIZE??
  
 19)NOTE: PLEASE NOTE METER CENTER(S) IS
 SHOWING TYP AS 600A AND SOME ARE SHOWN
 AS 800A? PLEASE CORRELATE AND CLARIFY.
  
 20)NOTE: PLEASE NOTE THAT THERE ARE SOME
 PANEL SCHEDULES SHOWNON SHEETS ARE NOT
 SHOWN ON RISER DIAGRAM.?? PLEASE SHOW.
  
 21)NOTE: PLEASE NOTE NO OCP / WIRE /
 CONDUIT SIZES SHOWN FOR FIRE PUMP.
 659-3,695-4,695-5
  
 22)NOTE: MISSING FEEDERS AND CONDUIT
 SIZES FOR MSB/ESB ,,,,,,
  
 23)NOTE: PLEASE NOTE NO GFI PROTECTION
 SHOWN FOR ANY OF THE 277V/480V SERVICES
 RATED FOR MORETHAN 1000AMPS.
 240-13/230-95
  
 24)NOTE: PLEASE NOTE ESB SHOWN AS 1600A
 ON RISER AND 1200A ON PNAEL SCHEDULE.
 PLEASE CORRELATE.
  
 25)NOTE: PLEASE NOTE MCN AND MCS ARE
 SHOWN AS 4000A AND MCS SHOWN AS 5000A
 ON SCHEDULE? PLEASE CORRELATE.
  
 26)NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 215-2,215-3,230-42
  
 27)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SIZE PER 250-66
 PLEASE NOTE THAT THERE IS NO GROUNDING
 DETAIL SHOWN.
  
 28)NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULES. PER 210-12
  
 29)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
 PLEASE NOTE THAT NO LOAD CALCULATIONS
 ARE SHOWN FOR HOUSE SERVICES. PLEASE
 SHOW.
  
 30) NOTE: PLEASE NOTE THAT ELECTRICAL
 SPEC BOOKS NEED TO BE SUBMITTED FOR
 REVIEW.
  
 31)NOTE: PLEASE NOTE PER LOCAL AMENDMENT
 -S. COLOR CODING OF FEEDERS NEED TO BE
 NOTED ON PLANS. PLEASE NOTE THAT THE
 LOCAL AMENDMENTS ARE SHOWN IN THE AMEND
 BOOKS THAT WERE HANDED OUT IN THE PRE-
 PLAN REVIEW MEETING.
  
 32)NOTE: PLEASE NOTE THAT ON E4.02,
 NOTE 19 SAYS "NOT USED", BUT IS # ON
 ELECTRICAL RISER DIAGRAM.??
  
 PLEASE COMPLETE PLANS AND SUBMIT ALL OF
 THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-01-30 Cont ID  
Sent By mamini Date 2003-01-30 Time 13:31 Rev Time 1.00
Received By mamini Date 2003-01-30 Time 13:31 Sent To  
Notes
2003-01-30 00:00:00PASSED:
 1. SEE PERMIT # 03012074 FOR UNDERGROUND
 UTILITIES AND SITE WORKS PERMITTING.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-05-07 Cont ID  
Sent By mamini Date 2002-05-07 Time 13:13 Rev Time 2.00
Received By mamini Date 2002-05-07 Time 13:12 Sent To  
Notes
2002-05-07 00:00:00FAILED:
 1. PLEASE PROVIDE CIVIL/SITE PLANS FOR
 OUR REVIEW AND APPROVAL. PLEASE NOTE
 THAT A SEPARATE PERMIT APPLICATION AND
 FEES FOR CIVIL/SITE WORKS IS REQUIRED.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status P Date 2005-09-21 Cont ID  
Sent By mwennerg Date 2005-09-21 Time 10:09 Rev Time 0.00
Received By mwennerg Date 2005-09-21 Time 10:09 Sent To  
Notes
2005-09-21 00:00:00REVISION DATED 8/15/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status P Date 2005-05-27 Cont ID  
Sent By mwennerg Date 2005-05-27 Time 13:49 Rev Time 0.00
Received By mwennerg Date 2005-05-27 Time 13:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2005-05-26 Cont ID  
Sent By mwennerg Date 2005-05-26 Time 09:35 Rev Time 0.00
Received By mwennerg Date 2005-05-26 Time 09:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2005-05-05 Cont ID  
Sent By nmccray Date 2005-05-04 Time 15:56 Rev Time 0.00
Received By nmccray Date 2005-05-03 Time 15:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2005-03-31 Cont ID  
Sent By mwennerg Date 2005-03-31 Time 14:24 Rev Time 0.00
Received By mwennerg Date 2005-03-31 Time 14:24 Sent To  
Notes
2005-03-31 00:00:00NO COMMENTS FROM LAST REVIEW.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR9561) 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2005-03-02 Cont ID  
Sent By nmccray Date 2005-03-02 Time 13:47 Rev Time 0.00
Received By nmccray Date 2005-03-02 Time 13:47 Sent To  
Notes
2005-03-02 00:00:00REVISION DATED 2/8/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2004-08-18 Cont ID  
Sent By mcarsill Date 2004-08-18 Time 16:13 Rev Time 0.00
Received By mcarsill Date 2004-08-18 Time 16:12 Sent To  
Notes
2004-08-18 00:00:001) COND LINE ON PAGFE M2.05 APPEARS
 TO BE POSSIBLY LOCATED IN A STAIRWAY.
 ONLY CERTAIN ITEMS PERMITTED IN
 STAIRWAYS.
  
 2) LINES IN STAIR # 10 ON PAGE M2.10.
 PLEASE SEE ABOVE.
  
 3) FA SYSTEM TO BE UL LISTED FOR
 CENTRAL STATION SERVICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2004-05-07 Cont ID  
Sent By mcarsill Date 2004-05-07 Time 10:17 Rev Time 0.00
Received By mcarsill Date 2004-05-07 Time 10:17 Sent To  
Notes
2004-05-07 00:00:001) STAIR # 5 SHALL BE EQUIPPED WITH
 A STANDPIPE SYSTEM SINCE IT WILL BE
 USED IN LIEU OF STAIR # 8.
  
 2) GATES SHALL MEET THE REQUIREMENTS
 FOR LOCKING DEVICES ON PAGE LS-1.09
 SHALL COMPLY WITH LIFE SAFETY CODE
 REQUIREMENTS.
  
 3) DOOR SWINGS ARE INCORRECT ON PAGE
 A2.13 FOR STAIRS 1 & 3.
  
 4) MAGNETIC LOCK NOTED ON DOOR SCHEDULE
 FOR DOOR P4. LOCKS CANNOT INTERFERE
 WITH EXITING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2004-02-03 Cont ID  
Sent By mcarsill Date 2004-02-03 Time 14:17 Rev Time 0.00
Received By mcarsill Date 2004-02-03 Time 14:17 Sent To  
Notes
2004-02-03 00:00:001) ALL REQUIRED EXIT STAIRS SHALL
 BE PROVIDED WITH STANDPIPE SYSTEM
 VALVES. NON REQUIRED STAIRS ARE
 NOT REQUIRED TO HAVE STANDPIPES.
 ALL PORTIONS OF THE BUILDING SHALL
 BE ACCESSIBLE WITHIN 200 FEET.
  
 2) SPIRAL STAIRS TO COMPLY WITH
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 3) RAILINGS ARE TO COMPLY WITH
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 4) PLANS WERE NOT STAPLED TOGETHER.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2003-10-03 Cont ID  
Sent By mcarsill Date 2003-10-03 Time 14:56 Rev Time 0.00
Received By mcarsill Date 2003-10-03 Time 14:56 Sent To  
Notes
2003-10-03 00:00:001) SMOKE DETECTOR MISSING FROM BEDROOM
 # 2, UNIT D ON PAGE E2.27.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-08-15 Cont ID  
Sent By mcarsill Date 2003-08-15 Time 16:57 Rev Time 0.00
Received By mcarsill Date 2003-08-15 Time 16:57 Sent To  
Notes
2003-08-15 00:00:001) ON SHEET E2.01 NEAR STAIR # 1 EXIT
 SIGNS APPEAR TO OPPOSE ONE ANOTHER.
 SHEET E2.02 APPEARS TO HAVE THE
 SAME PROBLEM.
  
 2) THE LIFE SAFETY SYSTEM NOTES ON
 PAGE E2.03 INDICATES EQUIPMENT THAT
 WILL BE CONTAINED IN THE FIRE
 COMMAND CENTER AND AT THE CONCEIRGE
 DESK. PLEASE REVIEW FIRE COMMAND
 STATION REQUIREMENTS IN THE FLORIDA
 BUILDING CODE AND INCLUDE ALL
 REQUIRED DEVICES IN THIS ROOM. THE
 CONCEIRGE DESK IS NOT MENTIONED IN
 THIS CODE SECTION AND THEREFORE NOT
 ACCEPTABLE.
  
 3) A SPEAKER STROBE IS NOT DESIRED IN
 THE FIRE COMMAND CENTER.
  
 4) ARE ANY EMERGENCY LIGHTS PRESENT
 IN THE MEZZANINE LEVEL AREA 1, TENANT
 STORAGE BINS SEEN ON PAGE E2.06.
  
 5) NO SMOKE DETECTORS SHOWN IN UNIT
 18L AND 19L.
  
 6) TENANT STORAGE BINS LOCATED ON
 MEZZANINE LEVEL AREA II DOES NOT
 ALLOW FOR THE REQUIRED 44" HALLWAY
 CLEARANCE. PLEASE EXPLAIN, PAGE E2.07.
  
 7) SMOKE DETECTOR MISSING FROM
 ELECTRICAL ROOM MEZZANINE LEVEL AREA
 II, PAGE E2.07.
  
 8) UNIT 36 DOES NOT DISPLAY A SMOKE
 DETECTOR ON PAGE E2.15.
  
 9) ANY EMERGENCY LIGHTS OR EXIT SIGNS
 PRESENT IN TENANT STORAGE TOWER LEVEL
 6, PAGE E.2.21.
  
 10) SMOKE DETECTOR(S) APPEAR TO BE
 MISSING IN BEDROOM # 2 IN UNIT B7.
  
 11) EXIT SIGN ON PAGE E2.42 IS LEADING
 PERSONS THRU A SOLID WALL.
  
 12) IT APPEARS ON PAGE E2.42 THAT ONLY
 ONE DOOR IS IDENTIFIED BY AN EXIT SIGN.
  
 13) FIRE SPRINKLER HEADS ARE REQUIRED
 AT THE TOP OF ALL SHAFTS. PLEASE SEE
 REVISION # 10 ON PAGE LS 100 WHICH
 IS INCORRECT.
  
 14) PLANS STILL DISPLAY A 1000 GPM FIRE
 PUMP. A 1250 GPM FIRE PUMP IS THE
 MINIMUM SIZE THAT WILL BE ACCEPTED.
  
 15) ALL SHAFTWAYS LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE MARKED
 SHAFTWAY IN 6" HIGH LETTERS.
  
 16) ARCHITECTURAL TRIM ON OUTSIDE OF
 BUILDING SHALL BE NON-COMBUSTIBLE.
  
 APPROVED PROVISO. NEW SHEETS WITH
 SIGNED AND SEALED LETTERS ARE TO BE
 SUBMITTED WITH CORRECTIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910
 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-06-02 Cont ID  
Sent By nmccray Date 2003-06-02 Time 14:22 Rev Time 0.00
Received By nmccray Date 2003-06-02 Time 14:22 Sent To  
Notes
2003-06-02 00:00:001) PLEASE PROVIDE MORE INFORMATION WITH
 REGARDS TO GLASS IN LOBBY DOORS THAT ARE
 PROTECTED WITH A SPRINKLER HEAD ON EACH
 SIDE OF GLASS. WATER CURTAINS ARE NOT
 DESIGNED TO PROTECT DOORS. PLEASE
 PROVIDE RECOGNIZED TEST DATA.
  
 2) ALL EXIT STAIRS THAT TERMINATE INTO
 EXIT PASSAGEWAYS SHALL HAVE THE SAME
 FIRE PROTECTION RATING AS THE STAIRS.
  
 3) THE PLAN PROPOSED A 1000 GPM FIRE
 PUMP. AGAIN THIS INFORMATION DOES NOT
 APPEARS TO BE CORRECT. ALL REQUIRED
 STAIRS FOR THE BUILDING SHALL HAVE
 STANDPIPE CONNECTIONS. IF EIGHT STAIRS
 ARE REQUIRED, THEN IN REALITY A 1000 GPM
 FIRE PUMP IS NOT LARGE ENOUGH. PLEASE
 ADVISE.
  
 4) PLEASE EXPLAIN GATES AND CARD READERS
 AND HOW DO THEY AFFECT EXITING.
  
 5) PLEASE EXPLAIN OPEN UNPROTECTED
 STAIRS.
  
 6) PLEASE PROVIDE FIRE RATING FOR STAIR
 # 10.
  
 7) STAIR # 5 APPEARS TO BE OPEN PLEASE
 EXPLAIN RATIONALE.
  
 8) HOW DO YOU DIRECT PEOPLE VIA STAIRS
 ACROSS AREAS OF PARKING TO REACH
 ENCLOSED EXIT STAIRS.
  
 9) MORE DETAILS NEEDED ON ROUND FORM
 COLUMNS SHOWN ON A3.01.
  
 10) KNOX-BOXES ARE TO BE INSTALLED ON
 THE EXTERIOR OF THE BUILDING.
  
 11) EXIT ACCESS ON MAIN ROOF LEVEL PLAN
 NOTED THRU DEDICATED AREA FOR LEASABLE
 SPACE.
  
 12) EXPANDED POLYSTYRENE NOTED IN
 BUILDING SECTIONS 3 & 3A.
  
 13) PLEASE PROVIDE INFO ON 1" INSULATION
 AROUND TRASH CHUTE.
  
 14) PLEASE EXPLAIN WHY EXITING ON LS 102
 GOES THRU BICYCLE STORAGE AND WHAT CODE
 REFERENCE ALLOWS THIS.
  
 15) SMOKE DETECTORS ARE REQUIRED IN ALL
 MECHANICAL, ELECTRICAL, TRANSFORMER AND
 TELEPHONE EQUIPMENT ROOMS PER 412.2 .
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-03-14 Cont ID  
Sent By mcarsill Date 2003-03-14 Time 14:04 Rev Time 0.00
Received By mcarsill Date 2003-03-14 Time 14:04 Sent To  
Notes
2003-03-14 00:00:001) UNABLE TO LOCATE WRITTEN COMMENTS
 FOR PREVIOUS PLAN REVIEW NOTES
 PROVIDED BY FIRE RESCUE.
  
 2) PLEASE PROVIDE MORE INFORMATION WITH
 REGARDS TO GLASS IN LOBBY DOORS THAT
 ARE PROTECTED WITH A SPRINKLER HEAD ON
 EACH SIDE OF THE GLASS. WATER CURTAINS
 ARE NOT DESIGNED TO PROTECT DOORS.
 PROVIDE RECOGNIZED TEST DATA.
  
 3) ALL EXIT STAIR DOORS SHALL HAVE
 TACTILE SIGNAGE.
  
 4) ALL EXIT STAIRS THAT TERMINATE INTO
 EXIT PASSAGEWAYS SHALL HAVE THE SAME
 FIRE PROTECTION RATING AS THE STAIR.
 PLEASE DEMONSTRATE THIS.
  
 5) THE ORIGNIAL PLANS PROPOSED A 1000
 GPM FIRE PUMP. THIS INFORMATION DOES
 NOT APPEAR TO BE CORRECT. ALL REQUIRED
 STAIRS FOR THE BUILDING SHALL HAVE
 STANDPIPE CONNECTIONS. IF EIGHT STAIRS
 ARE REQUIRED, THEN IN REALITY A 1000
 GPM FIRE PUMP IS NOT LARGE ENOUGH.
 PLEASE ADVISE.
  
 6) PLEASE EXPLAIN GATES AND CARD
 READERS AND HOW DO THEY EFFECT EXITING.
  
 7) PLEASE EXPLAIN OPEN UNPROTECTED
 STAIRS.
  
 8) STAIR # 10 IS NOT IDENTIFIED ON
 STAIR TERMINATION POINT BOX.
  
 9) STAIR # 9 IS NOT IDENTIFIED ON
 STAIR TERMINATION POINT BOX.
  
 10) PLEASE PROVIDE FIRE RATINGS FOR
 STAIR # 10.
  
 11) STAIR # 5 APPEARS TO BE OPEN.
 PLEASE EXPLAIN RATIONALE.
  
 12) HOW DO YOU DIRECT PERSONS VIA
 STAIRS ACROSS AREAS OF PARKING TO
 REACH ENCLOSED EXIT STAIRS.
  
 13) HOW ARE PATHS OF TRAVEL DEFINED ON
 THE LANAI LEVEL.
  
 14) PLEASE EXPLAIN NOTES ON PAGE LS-109
 "GATE AUTOMATICALLY UNLOCKS IN FIRE
 MODE PER FBC 1012.7.
  
 15) MORE DETAILS NEEDED ON ROUND FOAM
 COLUMNS SHOWN ON A3.01.
  
 16) THE KNOX-BOX IS NOTED TO BE
 INSTALLED ON THE INSIDE OF THE BUILDING.
 KNOX-BOXES ARE TO BE INSTALLED ON
 THE EXTERIOR OF THE BUILDING.
  
 17) EXIT ACESS ON MAIN ROOF LEVEL PLAN
 NOTED THRU DEDICATED AREA FOR
 LEASABLE SPACE.
  
 18) EXPANDED POLYSTYRENE NOTED IN
 BUILDING SECTIONS 3 & 3A.
  
 19) PLEASE PROVIDE INFO ON 1" INSULATION
 AROUND TRASH CHUTE.
  
 20) EXIT SIGN MISSING IN CORRIDOR,
 GROUND LEVEL LOBBY AREA ON PAGE E2.01
 TO DIRECT PERSONS TO EXIT BEYOND STAIR
 ENCLOSURE.
  
 21) NO EXIT SIGN SHOWN ON GROUND LEVEL,
 LOBBY AREA II ON PAGE E2.02.
  
 22) NO EXIT SIGNS SHOWN ON GROUND LEVEL,
 LOBBY AREA III ON E2.03.
  
 23) PLEASE EXPLAIN WHY EXITING ON LS 102
 GOES THRU BICYCLE STORAGE AND WHAT
 CODE REFERENCE ALLOWS THIS.
  
 24) ONLY ONE EXIT SIGN SHOWN ON GROUND
 LEVEL LOBBY AREA IV.
  
 25) IT APPEARS THAT DOOR FROM STAIR # 10
 OPENS INTO TENANT STORAGE ROOM A ON
 PAGE E2.10.
  
 26) COULD NOT LOCATE ANY EXIT SIGNS
 IN CORRIDOR ON PAGE E2.12.
  
 27) ONLY ONE EXIT SIGN SHOWN IN CORRIDOR
 ON PAGE E2.13.
  
 28) NO DIRECTIONAL EXIT SIGNS SHOWN
 IN CORRIDOR, TOWER 6TH LEVEL, AREA I
 PAGE E2.19.
  
 29) NO EXIT SIGNS SHOWN IN CORRIDOR
 ON PAGE E2.23.
  
 30) NO EXIT SIGNS SHOWN IN FITNESS
 AREA/YOGA AEROBICS ROOM.
  
 31) EMERGENCY GENERATOR DETAIL INDICATES
 A SUB-BASE FUEL TANK. ROOM IF
 CONTAINING FUEL IS TO BE PROPERLY
 FIRE RATED.
  
 32) SMOKE DETECTORS ARE REQUIRED IN
 EVERY MECHANICAL,ELECTRICAL,TRANSFORMER,
 AND TELEPHONE EQUIPMENT PER 412.2.
  
 33) ONLY ONE EXIT SIGN SHOWN ON PAGE
 E2.49.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-05-07 Cont ID  
Sent By mcarsill Date 2002-05-07 Time 10:47 Rev Time 0.00
Received By mcarsill Date 2002-05-07 Time 10:47 Sent To  
Notes
2002-05-07 00:00:001) ADDRESS FOR BUILDING REQUIRED. A
 MINIMUM OF SIX INCH NUMERALS REQUIRED.
  
 2) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE STORIES
 OR THIRTY FEET IN HEIGHT.
  
 3) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 4) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 5) PLEASE BE ADVISED THAT THIS BUILDING
 IS LOCATED WITHIN THE CITY FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY. PLEASE
 SEE CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE.
  
 6) PLEASE PROVIDE PRODUCT APPROVALS FOR
 THE WON ELEVATOR DOORS.
  
 7) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS OF THE BUILDING.
  
 8) CEDER TRELLISES NOTED ON LOWER ROOF
 POOL DECK. AGAIN, THE BUILDING IS
 LOCATED WITHIN THE CITY FIRE LIMITS
 CERTAIN RESTRICTIONS APPLY.
  
 9) EIFS NOTED ON BUILDING ELEVATIONS.
 PLEASE SEE LOCAL AMENDMENTS REGARDING
 ARCHITECTURAL TRIM IN THE FIRE LIMITS.
  
 10) THE USE OF PROPANE BARBECUE GRILLS
 ABOVE THE FIRST FLOOR ON THE BALCONIES
 ARE PROHIBITED.
  
 11) ALL SHAFTWAYS THAT ARE ACCESSIBLE
 TO THE FIRE RESCUE DEPARTMENT WHICH
 PERSONS CAN FALL INTO ARE TO BE MARKED
 "SHAFTWAY IN RED LETTERS, SIX INCHES
 HIGH ON A WHITE BACKGROUND" PER NFPA 1.
  
 12) A KNOX-BOX WILL BE REQUIRED FOR
 FIRE RESCUE ACCESS.
  
 13) ALL STAIRS ARE TO BE PROVIDED WITH
 SIGNAGE TO INDICATE THE STAIR, THE
 STORY, THE TERMINUS TOP AND BOTTOM.
  
 14) ALL CANVAS CANOPIES ARE TO BE FIRE
 RETARDENT.
  
 15) NO COMBUSTIBLE MATERIALS ARE ALLOWED
 WITHIN THE RETURN AIR PLENUMS.
  
 16) PLEASE INDICATE THAT ALL OF THE
 PRESCRIPTIVE CODE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, SECTION 412.4.3
 "FIRE COMMAND STATIONS" ARE BEING MET.
  
 17) SITE PLAN INDICATES A SIX INCH FIRE
 LINE ENTERING THE BUILDING. ON ANOTHER
 SHEET, IT DISPLAYS AN EIGHT INCH LINE.
 PLEASE BE ADVISED THAT AN EIGHT INCH
 LINE IS THE MINIMUM THAT WILL BE ALLOWED
 FOR A 1000 GPM FIRE PUMP THAT HAS BEEN
 PROPOSED.
  
 18) SITE PLAN DOES NOT SHOW FIRE MAIN
 SIZE ON OKEECHOBEE BOULEVARD.
  
 19) THE FIRE LINE SHOWN RUNNING UNDER
 THE BUILDING'S FOUNDATION IS NOT ALLOWED
 BY THE CODE UNLESS NO OTHER ALTERNATIVE
 IS AVAILABLE.
  
 20) NO DETAILS PROVIDED FOR PRESSURE
 RELIEF DEVICES PROPOSED.
  
 21) PLEASE VERIFY THAT THE CENTRAL FIRE
 SPRINKLER HEADS THAT ARE PLANNED FOR
 USE ARE NOT ON THE VOLUNTARY RECALL
 LIST, PLEASE SEE WWW.
 SPRINKLERREPLACEMENT.COM.
  
 22) FIRE SPRINKLER PLANS DO NOT NOTE
 THAT PRESSURE TESTING IS REQUIRED FOR
 ALL UNDERGROUND FIRE MAINS AND ABOVE
 GROUND FIRE SPRINKLER PIPING.
  
 23) AREAS OF THE FIRE SPRINKLER PLANS
 ARE MISSING FIRE SPRINKLER PROTECTION.
  
 24) PLEASE EXPLAIN EXITING RATIONALE
 FROM THE PARKING GARAGE.
  
 25) PLEASE INDICATE ON THE ELECTRICAL
 PLANS THAT ALL SMOKE DETECTORS ARE TO
 BE INSTALLED A MINIMUM OF THREE FEET
 FROM AIR CONDITIONER DIFFUSERS.
  
 26) PLEASE EXPLAIN PURPOSE OF
 DIRECTIONAL EXIT SIGN NEAR OPEN STAIRWAY
 ACCROSS FROM TOWNHOUSE SIX IN CORRDIOR.
  
 27) MANUAL PULL STATION AND HORN STROBE
 NOTED IN MIDDLE OF STAIRWAY ON PAGE
 E1.08.
  
 28) PLEASE EXPLAIN LEDGES.
  
 29) IT WAS NOTED THAT SMOKE DETECTORS
 ARE SHOWN IN THE CORRIDORS OF THE
 BUILDING. PLEASE BE ADVISED THAT SPACING
 OF THESE DETECTORS ARE NOT TO EXCEED
 CODE REQUIREMENTS. PLEASE CHECK THE
 SPACING OF THESE DEVICES.
  
 30) NO ILLUMINATED EXIT SIGNS LOCATED
 FOR THE SECOND LEVEL PARKING AREA.
  
 31) FIRE ALARM NOTES SECTION NUMBER
 TWELVE INDICATES THAT THE BUILDING WILL
 BE CONSIDERED TWO SEPARATE BUILDINGS
 ABOVE THE FIFTH FLOOR. PLEASE EXPLAIN
 RATIONALE.
  
 32) PLEASE INDICATE WHAT THE VOICE
 EVACUATION PORTION OF THE FIRE ALARM
 SYSTEM WILL INDICATE TO PERSONS WITHIN
 THE BUILDING.
  
 33) THE MECHANICAL PLANS MAKE REFERENCE
 TO SECTION 412.5. HOW ARE THE OPERABLE
 WINDOWS GOING TO BE IDENTIFIED.
  
 34) PLEASE INDICATE THAT THE FUEL
 SUPPLY TO OPERATE EMERGENCY POWER
 IS AMPLE TO SUPPLY A MINIMUM OF TWO
 HOURS PER FBC 412.7.1.2.
  
 35) EMERGENCY LIGHTING REQUIRED FOR
 FIRE PUMP ROOM.
  
 36) THE PLANS SUBMITTED APPEAR TO BE
 INCOMPLETE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 123 Status N Date 2006-04-07 Cont ID  
Sent By shill Date 2006-04-07 Time 09:56 Rev Time 0.00
Received By shill Date 2006-04-07 Time 09:56 Sent To E
Notes
2006-04-07 00:00:00ELECTRIC REVISION, (3 ROLLS) ROUTED TO
 JAKE LEAHY DESK PER JL

Review Stop I INCOMING/PROCESSING
Rev No 122 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 18:17 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 18:17 Sent To E
Notes
2006-03-24 00:00:00REV'S SENT TO JL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 121 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 08:44 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 08:44 Sent To E
Notes
2005-12-29 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 120 Status N Date 2005-12-28 Cont ID  
Sent By adarroug Date 2005-12-28 Time 10:55 Rev Time 0.00
Received By adarroug Date 2005-12-28 Time 10:55 Sent To M
Notes
2005-12-28 00:00:00TO "HMOSER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 119 Status N Date 2005-12-06 Cont ID  
Sent By adarroug Date 2005-12-06 Time 08:49 Rev Time 0.00
Received By adarroug Date 2005-12-06 Time 08:49 Sent To B
Notes
2005-12-06 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 118 Status N Date 2005-11-18 Cont ID  
Sent By adarroug Date 2005-11-18 Time 10:37 Rev Time 0.00
Received By adarroug Date 2005-11-18 Time 10:37 Sent To E
Notes
2005-11-18 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 117 Status N Date 2005-09-26 Cont ID  
Sent By adarroug Date 2005-09-26 Time 08:37 Rev Time 0.00
Received By adarroug Date 2005-09-26 Time 08:37 Sent To B
Notes
2005-09-26 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 116 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 10:11 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 10:11 Sent To E
Notes
2005-09-12 00:00:00TO "JLEAHY" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 115 Status N Date 2005-08-31 Cont ID  
Sent By adarroug Date 2005-08-31 Time 13:29 Rev Time 0.00
Received By adarroug Date 2005-08-31 Time 13:28 Sent To  
Notes
2005-08-31 00:00:00TO "COMM" BD#54

Review Stop I INCOMING/PROCESSING
Rev No 114 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 18:37 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 18:37 Sent To B
Notes
2005-08-18 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 113 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 14:48 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 14:48 Sent To E
Notes
2005-07-20 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 112 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 09:52 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 09:52 Sent To B
Notes
2005-07-12 00:00:00TO "SHILL" DESK

Review Stop I INCOMING/PROCESSING
Rev No 111 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 16:39 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 16:39 Sent To E
Notes
2005-07-05 00:00:00TO "DPALMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 110 Status N Date 2005-06-27 Cont ID  
Sent By adarroug Date 2005-06-27 Time 11:49 Rev Time 0.00
Received By adarroug Date 2005-06-27 Time 11:49 Sent To E
Notes
2005-06-27 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 109 Status N Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 11:14 Rev Time 0.00
Received By shill Date 2005-06-09 Time 11:14 Sent To E
Notes
2005-06-09 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 108 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 11:30 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 11:30 Sent To P
Notes
2005-05-31 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 107 Status N Date 2005-05-26 Cont ID  
Sent By adarroug Date 2005-05-26 Time 09:39 Rev Time 0.00
Received By adarroug Date 2005-05-26 Time 09:39 Sent To B
Notes
2005-05-26 00:00:00TAKEN FROM BD#31-TO SHILL DESK 3
 REVISIONS

Review Stop I INCOMING/PROCESSING
Rev No 106 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 18:10 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 18:10 Sent To E
Notes
2005-05-24 00:00:00TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 105 Status N Date 2005-05-19 Cont ID  
Sent By adarroug Date 2005-05-19 Time 13:27 Rev Time 0.00
Received By adarroug Date 2005-05-19 Time 13:27 Sent To M
Notes
2005-05-19 00:00:00TO "PKRAUSS" DESK

Review Stop I INCOMING/PROCESSING
Rev No 104 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-05 Time 08:20 Rev Time 0.00
Received By adarroug Date 2005-05-05 Time 08:20 Sent To  
Notes
2005-05-18 00:00:00TO "COMM" BD#31/PLANS ON RACK10 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 103 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 10:39 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 10:39 Sent To E
Notes
2005-05-16 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 102 Status N Date 2005-05-13 Cont ID  
Sent By adarroug Date 2005-05-13 Time 13:33 Rev Time 0.00
Received By adarroug Date 2005-05-13 Time 13:33 Sent To B
Notes
2005-05-13 00:00:00TAKEN FROM "COMM" BD#15, TO "SHILL" DESK

Review Stop I INCOMING/PROCESSING
Rev No 101 Status N Date 2005-05-02 Cont ID  
Sent By adarroug Date 2005-05-02 Time 09:28 Rev Time 0.00
Received By adarroug Date 2005-05-02 Time 09:28 Sent To  
Notes
2005-05-02 00:00:00TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 100 Status N Date 2005-04-20 Cont ID  
Sent By adarroug Date 2005-04-20 Time 10:07 Rev Time 0.00
Received By adarroug Date 2005-04-20 Time 10:07 Sent To B
Notes
2005-04-20 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 99 Status N Date 2005-03-21 Cont ID  
Sent By adarroug Date 2005-03-21 Time 08:11 Rev Time 0.00
Received By adarroug Date 2005-03-21 Time 08:11 Sent To  
Notes
2005-03-21 00:00:00TO "COMM" BD#3/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 98 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 11:05 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 11:05 Sent To  
Notes
2005-03-17 00:00:00TO "COMM" BD#3/PLANS ON RACK 1 ROLL

Review Stop I INCOMING/PROCESSING
Rev No 97 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 10:53 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 10:53 Sent To  
Notes
2005-03-09 00:00:00TO "COMM" BD#33/PLANS ON RACK 3 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 96 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 10:33 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 10:33 Sent To M
Notes
2005-03-09 00:00:00TO "PKRAUSS" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 95 Status N Date 2005-03-03 Cont ID  
Sent By adarroug Date 2005-03-03 Time 10:39 Rev Time 0.00
Received By adarroug Date 2005-03-03 Time 10:39 Sent To  
Notes
2005-03-03 00:00:00TO "COMM" BD#33/
 COMM RACK 6PLANS

Review Stop I INCOMING/PROCESSING
Rev No 94 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-03-03 Time 09:47 Sent To  
Notes
2005-03-03 00:00:00TO "COMM" BD#33/
 COMM RACK 6 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 93 Status N Date 2005-02-10 Cont ID  
Sent By mjacobs Date 2005-02-10 Time 10:44 Rev Time 0.00
Received By mjacobs Date 2005-02-10 Time 10:43 Sent To  
Notes
2005-03-02 00:00:003/2/05 MOVED TO BD#23-ADARROUGH
2005-02-10 00:00:00TO "COMM BD#54/REV."

Review Stop I INCOMING/PROCESSING
Rev No 92 Status N Date 2005-02-03 Cont ID  
Sent By adarroug Date 2005-02-03 Time 13:18 Rev Time 0.00
Received By adarroug Date 2005-02-03 Time 13:18 Sent To E
Notes
2005-02-03 00:00:00TO DPALMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 91 Status N Date 2004-12-17 Cont ID  
Sent By mjacobs Date 2004-12-17 Time 14:48 Rev Time 0.00
Received By mjacobs Date 2004-12-17 Time 14:48 Sent To P
Notes
2004-12-17 00:00:00SENT TO "P" BOX,.

Review Stop I INCOMING/PROCESSING
Rev No 90 Status N Date 2004-11-18 Cont ID  
Sent By mjacobs Date 2004-11-18 Time 08:13 Rev Time 0.00
Received By mjacobs Date 2004-11-18 Time 08:13 Sent To B
Notes
2004-11-18 00:00:00SENT TO LYNN'S INBOX

Review Stop I INCOMING/PROCESSING
Rev No 89 Status N Date 2004-11-18 Cont ID  
Sent By mjacobs Date 2004-11-18 Time 08:08 Rev Time 0.00
Received By mjacobs Date 2004-11-18 Time 08:08 Sent To P
Notes
2004-11-18 00:00:00TO "P" BOX/SHOP DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 88 Status   Date   Cont ID  
Sent By mjacobs Date   Time 08:06 Rev Time 0.00
Received By mjacobs Date   Time 08:05 Sent To  
Notes
2004-11-18 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 87 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 13:52 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 17:03 Sent To  
Notes
2004-10-20 00:00:00TO DON NEELY DESK/SUBMITTAL
 LETTER RE:CITY REPORT DATED 9/23/04

Review Stop I INCOMING/PROCESSING
Rev No 86 Status N Date 2004-10-06 Cont ID  
Sent By csiegber Date 2004-10-06 Time 10:12 Rev Time 0.00
Received By csiegber Date 2004-10-06 Time 10:12 Sent To B
Notes
2004-10-06 00:00:00TO SH DESK/SUBMITTAL
 POST TENSION SHOP DRAWING
 PT-000,10,11,20,21,30,31,40,41,50,51,60.
 61,70,71,80,81

Review Stop I INCOMING/PROCESSING
Rev No 85 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:53 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:53 Sent To P
Notes
2004-10-05 00:00:00TO KS BOX/SUBMITTAL
 DESIGN FOR HANDICAP GRAB BAR SUPPORT
 FRAME AS REQUESTED BY P INSPECTOR

Review Stop I INCOMING/PROCESSING
Rev No 84 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 12:23 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 12:23 Sent To B
Notes
2004-10-04 00:00:00TO SH DESK/4 SUBMITTALS
 LANAI LEVER TENDON & SUPPORT PLAN
 11TH LEVEL TENDON & SUPPORT PLAN
 12-16 LEVELS TENDON & SUPPORT PLAN
 ROOF LEVEL TENDON & SUPPORT PLAN

Review Stop I INCOMING/PROCESSING
Rev No 83 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:24 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 15:24 Sent To B
Notes
2004-09-15 00:00:00TO SH DESK/SUBMITTAL
 PT 000,10,11,20,21,31,31,40,41
 50,51,60,61,70,71,80,81

Review Stop I INCOMING/PROCESSING
Rev No 82 Status N Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-08-25 Time 13:29 Rev Time 0.00
Received By csiegber Date 2004-08-25 Time 13:29 Sent To B
Notes
2004-08-25 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 81 Status N Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-08-25 Time 13:26 Rev Time 0.00
Received By csiegber Date 2004-08-25 Time 13:26 Sent To B
Notes
2004-08-25 00:00:00TO SH DESK/2 SUBMITTALS
 POUR #66 ROOF EAST SIDE/PUMP #2/CHM
 POUR #67 MAIN ROOF/

Review Stop I INCOMING/PROCESSING
Rev No 80 Status N Date 2004-08-18 Cont ID  
Sent By csiegber Date 2004-08-18 Time 15:02 Rev Time 0.00
Received By csiegber Date 2004-08-18 Time 15:02 Sent To B
Notes
2004-08-18 00:00:00TO SH DESK/SUBMITTAL
 SHEET 1 COLUMN ELEVATION AS BUILT SURVEY
 SHEET 1 9TH FLOOR AS-BUILTS
 SHEET 1 12TH FLOOR AS BUILTS

Review Stop I INCOMING/PROCESSING
Rev No 79 Status N Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-08-11 Time 15:36 Rev Time 0.00
Received By csiegber Date 2004-08-11 Time 15:36 Sent To B
Notes
2004-08-11 00:00:00TO SH DESK/SUBMITTAL
 POUR #65 SOUTH SIDE

Review Stop I INCOMING/PROCESSING
Rev No 78 Status N Date 2004-08-10 Cont ID  
Sent By shill Date 2004-08-10 Time 08:33 Rev Time 0.00
Received By shill Date 2004-08-10 Time 08:33 Sent To B
Notes
2004-08-10 00:00:00SUBMITTAL TO AL

Review Stop I INCOMING/PROCESSING
Rev No 77 Status N Date 2004-08-09 Cont ID  
Sent By csiegber Date 2004-08-09 Time 15:43 Rev Time 0.00
Received By csiegber Date 2004-08-09 Time 15:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2004-08-09 Cont ID  
Sent By csiegber Date 2004-08-09 Time 15:43 Rev Time 0.00
Received By csiegber Date 2004-08-09 Time 15:43 Sent To B
Notes
2004-08-09 00:00:00TO SH DESK/
 POUR#64/16 FLOOR/NORTH SIDE

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2004-08-04 Cont ID  
Sent By csiegber Date 2004-08-04 Time 14:20 Rev Time 0.00
Received By csiegber Date 2004-08-04 Time 14:20 Sent To B
Notes
2004-08-04 00:00:00TO SH DESK/2 SUBMITTALS
 POUR #63, 16 FLR EAST
 POUR 62, 16 FLR SOUTH

Review Stop I INCOMING/PROCESSING
Rev No 74 Status N Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-07-28 Time 12:31 Rev Time 0.00
Received By csiegber Date 2004-07-28 Time 12:31 Sent To B
Notes
2004-07-28 00:00:00TO SH DESK/14 SUBMITTALS
 POUR #61 15 FLR NORTH SIDE
 DO315-3/DO315-13/DO315-15/DO315-24
 DO315-27/DO315-33/DO315-36/DO315-40
 DO315-41/DO315-49/DO315-64/DO315-66
 DO315-73

Review Stop I INCOMING/PROCESSING
Rev No 73 Status N Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 14:58 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 14:58 Sent To B
Notes
2004-07-21 00:00:00TO SH DESK/SUBMITTAL/
 POUR #60

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-07-16 Time 16:34 Rev Time 0.00
Received By shill Date 2004-07-16 Time 16:34 Sent To B
Notes
2004-07-16 00:00:00TO SH DESK/69 SUBMITTALS
 TO MJ DESK

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2004-07-14 Cont ID  
Sent By mjacobs Date 2004-07-14 Time 14:38 Rev Time 0.00
Received By mjacobs Date 2004-07-14 Time 14:38 Sent To B
Notes
2004-07-14 00:00:00SENT TO "SH" DESK SUBMITTALS/POOR#58

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2004-07-14 Cont ID  
Sent By mjacobs Date 2004-07-14 Time 11:42 Rev Time 0.00
Received By mjacobs Date 2004-07-14 Time 11:42 Sent To  
Notes
2004-07-14 00:00:00TO COMM BOARD #45

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2004-07-07 Cont ID  
Sent By csiegber Date 2004-07-07 Time 11:28 Rev Time 0.00
Received By csiegber Date 2004-07-07 Time 11:28 Sent To B
Notes
2004-07-07 00:00:00TO SH DESK/SUBMITTAL/POUR 57

Review Stop I INCOMING/PROCESSING
Rev No 68 Status N Date 2004-07-06 Cont ID  
Sent By csiegber Date 2004-07-06 Time 14:16 Rev Time 0.00
Received By csiegber Date 2004-07-06 Time 14:16 Sent To B
Notes
2004-07-06 00:00:00TO SH DESK/POUR 56

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 14:50 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 14:50 Sent To B
Notes
2004-07-01 00:00:00TO SH DESK/2 SUBMITTALS
 ALUMINUM RAILINGS & CALCS/BALCONY RAILS
 &POUR 55 RESHORING

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 16:40 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 16:40 Sent To P
Notes
2004-06-25 00:00:00TO KS DESK/SUBMITTAL/PLUMBING MATERIALS

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 16:30 Sent To B
Notes
2004-06-25 00:00:00TO SH DESK/14 SUBMITTALS -03100-15;
 03200-31-32-35-36-39-43-46-47-48
 03200-49 (D0315-47) -49 (D0315-34)
 03200-50-59
 03365-3-4-5-6

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 12:04 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 12:03 Sent To B
Notes
2004-06-25 00:00:00TO SH DESK/POUR 54 12TH FLR

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2004-06-24 Cont ID  
Sent By csiegber Date 2004-06-24 Time 15:03 Rev Time 0.00
Received By csiegber Date 2004-06-24 Time 15:03 Sent To B
Notes
2004-06-24 00:00:00TO SH DESK/SUBMITTAL/POUR 53 FLOOR 12

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2004-06-17 Cont ID  
Sent By csiegber Date 2004-06-17 Time 14:20 Rev Time 0.00
Received By csiegber Date 2004-06-17 Time 14:20 Sent To B
Notes
2004-06-17 00:00:00TO SH DESK/SUBMITTALS/STEEL PLATE
 LANDINGS

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-06-16 Time 14:10 Rev Time 0.00
Received By csiegber Date 2004-06-16 Time 14:09 Sent To B
Notes
2004-06-16 00:00:00TO SH DESK/3 SUBMITTALS/POUR 50-PUMP 2
 & 11TH LEVEL
 RESUB POUR 46 LEVEL 9
 POUR #52

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2004-06-15 Cont ID  
Sent By csiegber Date 2004-06-15 Time 14:35 Rev Time 0.00
Received By csiegber Date 2004-06-15 Time 14:35 Sent To B
Notes
2004-06-15 00:00:00TO SH DESK/2 SUBMITTALS/ELEV MACH ROM
 CHM PLACEMENT OF POST TENSION CABLES/POU
 R #51

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2004-06-09 Cont ID  
Sent By csiegber Date 2004-06-09 Time 16:26 Rev Time 0.00
Received By csiegber Date 2004-06-09 Time 16:26 Sent To B
Notes
2004-06-09 00:00:00TO SH DESK/CHM-POST TENSIONED TENDS TO I
 IN SCCORDANCE WITH SHOP DRAWS

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2004-06-04 Cont ID  
Sent By csiegber Date 2004-06-04 Time 13:58 Rev Time 0.00
Received By csiegber Date 2004-06-04 Time 13:58 Sent To B
Notes
2004-06-04 00:00:00TO SH DESK/SUBMITTAL/CHM-POU 49 LEVEL 10

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2004-06-01 Cont ID  
Sent By csiegber Date 2004-06-01 Time 09:13 Rev Time 0.00
Received By csiegber Date 2004-06-01 Time 09:13 Sent To B
Notes
2004-06-01 00:00:00TO SH DESK/POUR 48/LEVEL 10

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2004-05-28 Cont ID  
Sent By csiegber Date 2004-05-28 Time 10:43 Rev Time 0.00
Received By csiegber Date 2004-05-28 Time 10:42 Sent To B
Notes
2004-05-28 00:00:00TO SH DESK/2 SUBMITTALS IN ENVELOPE
 CHM-POUR 46 LEVEL 9 DATE 5/21/04 &
 ALUM RAILINGSA-A00.1,A-4,A-0 SHEETS DEE

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2004-05-25 Cont ID  
Sent By alange Date 2004-05-25 Time 13:36 Rev Time 0.00
Received By alange Date 2004-05-25 Time 13:36 Sent To  
Notes
2004-05-25 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2004-05-21 Cont ID  
Sent By csiegber Date 2004-05-21 Time 11:26 Rev Time 0.00
Received By csiegber Date 2004-05-21 Time 11:26 Sent To B
Notes
2004-05-21 00:00:00TO SH DESK/CHM-POUR 46 LEVEL 9 POST
 TENSIONED TENDONS LETTER

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2004-05-19 Cont ID  
Sent By csiegber Date 2004-05-19 Time 13:47 Rev Time 0.00
Received By csiegber Date 2004-05-19 Time 13:47 Sent To B
Notes
2004-05-19 00:00:00TO SH DESK/SUBMITTAL/POUR 45 SHORING &
 RESHORING LETTER

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2004-05-13 Cont ID  
Sent By csiegber Date 2004-05-13 Time 09:00 Rev Time 0.00
Received By csiegber Date 2004-05-13 Time 09:00 Sent To B
Notes
2004-05-13 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-05-12 Time 16:52 Rev Time 0.00
Received By csiegber Date 2004-05-12 Time 16:52 Sent To B
Notes
2004-05-12 00:00:00TO SH DESK/POUR #43 8TH LEVEL/POUR #44

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2004-05-11 Cont ID  
Sent By csiegber Date 2004-05-11 Time 09:57 Rev Time 0.00
Received By csiegber Date 2004-05-11 Time 09:57 Sent To B
Notes
2004-05-11 00:00:00TO SH DESK/SUBMITTAL/POUR #43,8TH LEVEL

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-05-07 Time 15:09 Rev Time 0.00
Received By csiegber Date 2004-05-07 Time 15:09 Sent To B
Notes
2004-05-07 00:00:00TO SH DESK/SUBMITTAL/POUR #43

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-06 Time 14:25 Rev Time 0.00
Received By csiegber Date 2004-05-06 Time 14:25 Sent To B
Notes
2004-05-06 00:00:00TO SH DESK/SUBMITTAL
 INTERIOR STEEL RAILING

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2004-05-05 Cont ID  
Sent By csiegber Date 2004-05-05 Time 15:18 Rev Time 0.00
Received By csiegber Date 2004-05-05 Time 15:18 Sent To  
Notes
2004-05-05 00:00:00TO COMM BD#55/REV

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2004-05-05 Cont ID  
Sent By csiegber Date 2004-05-05 Time 14:55 Rev Time 0.00
Received By csiegber Date 2004-05-05 Time 14:54 Sent To B
Notes
2004-05-05 00:00:00TO SH DESK/POUR #41 & 42

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 15:11 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 15:11 Sent To B
Notes
2004-04-28 00:00:00TO SH DESK/POUR #40

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-04-27 Time 14:34 Rev Time 0.00
Received By csiegber Date 2004-04-27 Time 14:34 Sent To B
Notes
2004-04-27 00:00:00TO SH DESK/2 SUBMITTALS/FIRESTOPPING
 PLUMBING & MECH/PER LM

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-04-27 Time 13:55 Rev Time 0.00
Received By csiegber Date 2004-04-27 Time 13:55 Sent To E
Notes
2004-04-27 00:00:00TO SH DESK/SUBMITTAL/FIRE CAULKING

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 10:03 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 10:03 Sent To B
Notes
2004-04-20 00:00:00TO SH DESK/BOX W/WINDOW SHOP DRAWINGS &
 PA

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 08:52 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 08:52 Sent To B
Notes
2004-04-20 00:00:00TO SH DESK/2 SUBMITTALS
 ALUM HANDRAILS-CALCS
 STEEL HANDRAILS-CALCS

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 15:44 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 15:44 Sent To B
Notes
2004-04-13 00:00:00TO SH DESK/SUBMITTAL/METAL PAN STAIR
 SHOP DRAWINGS & CALCS

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2004-04-02 Cont ID  
Sent By csiegber Date 2004-04-02 Time 15:51 Rev Time 0.00
Received By csiegber Date 2004-04-02 Time 15:51 Sent To B
Notes
2004-04-02 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 15:19 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 15:19 Sent To B
Notes
2004-03-25 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 37 Status   Date 2004-03-17 Cont ID  
Sent By ptjomsto Date 2004-03-17 Time 12:26 Rev Time 0.00
Received By ptjomsto Date 2004-03-17 Time 12:26 Sent To  
Notes
2004-03-17 00:00:00PUT IN LYNN'S IN BASKET FOR NEIL
 (NOISE ORDINANCE/AFTER HOURS WORK PERMIT
 FOR APRIL)

Review Stop I INCOMING/PROCESSING
Rev No 36 Status   Date 2004-03-17 Cont ID  
Sent By ptjomsto Date 2004-03-17 Time 12:22 Rev Time 0.00
Received By ptjomsto Date 2004-03-17 Time 12:22 Sent To  
Notes
2004-03-17 00:00:00PLACED ON DON NEELY'S DESK (SHORING
 CERTIFICATION LETTERS - SHORING
 INSPECTION & POUR #32-6# LEVEL LOFT

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2004-03-05 Cont ID  
Sent By csiegber Date 2004-03-05 Time 08:04 Rev Time 0.00
Received By csiegber Date 2004-03-05 Time 08:04 Sent To B
Notes
2004-03-05 00:00:00TO SH DESK/SUBMITTAL/POUR #30

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-04 Time 13:31 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 13:31 Sent To B
Notes
2004-03-04 00:00:00TO SH DESK/SUBMITTAL/POUR #31

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 16:41 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 16:41 Sent To B
Notes
2004-02-25 00:00:00TO SH DESK/INSPECTIONS

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 12:21 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 12:21 Sent To B
Notes
2004-02-25 00:00:00TO SH DESK/SHORING & RESHORING/CABLE POS
 T TENSION PROFILE LETTER

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 14:23 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 14:23 Sent To  
Notes
2004-02-19 00:00:00TO

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-02-13 Time 15:17 Rev Time 0.00
Received By csiegber Date 2004-02-13 Time 15:17 Sent To  
Notes
2004-02-13 00:00:00TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 09:51 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 09:51 Sent To  
Notes
2004-02-06 00:00:00TO DON NEELY/LEVEL 7

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 10:25 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 10:24 Sent To B
Notes
2004-02-05 00:00:00TO SH DESK/SUBMITTAL/METAL PAN STAIR SHO
 P DRAWING,METAL PAN STAIR CALC/TOWER POU
 R #24 PUMP 1, 5TH LEVEL, TOWER 5TH FLR

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2004-01-30 Cont ID  
Sent By csiegber Date 2004-01-29 Time 16:33 Rev Time 0.00
Received By csiegber Date 2004-01-30 Time 08:11 Sent To  
Notes
2004-01-29 00:00:00TO COMM BD#59

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2004-01-29 Cont ID  
Sent By csiegber Date 2004-01-29 Time 15:55 Rev Time 0.00
Received By csiegber Date 2004-01-29 Time 15:54 Sent To  
Notes
2004-01-29 00:00:00TO DON NEELY DESK

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-13 Time 09:39 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 09:39 Sent To  
Notes
2004-01-13 00:00:00TO DON NEELY/POUR #20

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-13 Time 09:38 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 09:38 Sent To  
Notes
2004-01-13 00:00:00TO NEIL MELICK/AFTER HOURS PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2004-01-08 Cont ID  
Sent By csiegber Date 2004-01-08 Time 16:40 Rev Time 0.00
Received By csiegber Date 2004-01-08 Time 16:40 Sent To  
Notes
2004-01-08 00:00:00TO DON NEELY DESK

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2003-12-22 Cont ID  
Sent By csiegber Date 2003-12-22 Time 15:38 Rev Time 0.00
Received By csiegber Date 2003-12-22 Time 15:38 Sent To  
Notes
2003-12-22 00:00:00TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2003-12-19 Cont ID  
Sent By csiegber Date 2003-12-19 Time 15:07 Rev Time 0.00
Received By csiegber Date 2003-12-19 Time 15:07 Sent To  
Notes
2003-12-19 00:00:00TO NEIL MELICK/NOISE ORD.

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 10:14 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 10:14 Sent To  
Notes
2003-12-16 00:00:00TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2003-12-08 Cont ID  
Sent By csiegber Date 2003-12-08 Time 15:00 Rev Time 0.00
Received By csiegber Date 2003-12-08 Time 15:00 Sent To  
Notes
2003-12-08 00:00:00TO DON NEELY DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2003-12-03 Cont ID  
Sent By csiegber Date 2003-12-03 Time 15:09 Rev Time 0.00
Received By csiegber Date 2003-12-03 Time 15:09 Sent To  
Notes
2003-12-03 00:00:00TO DON NEELY SHORING LETTER OF PROFILE
 CABLES/POUR #15

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2003-12-01 Cont ID  
Sent By csiegber Date 2003-12-01 Time 16:03 Rev Time 0.00
Received By csiegber Date 2003-12-01 Time 16:03 Sent To  
Notes
2003-12-01 00:00:00TO DON NEELY DESK

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-11-26 Time 10:50 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 10:50 Sent To  
Notes
2003-11-26 00:00:00TO DON NEELY DESK

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2003-11-10 Cont ID  
Sent By csiegber Date 2003-11-10 Time 09:34 Rev Time 0.00
Received By csiegber Date 2003-11-10 Time 09:34 Sent To P
Notes
2003-11-10 00:00:00TO KS BOX/PLAN REVIEW COMMENTS

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 14:56 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 14:56 Sent To B
Notes
2003-09-30 00:00:00TO HP DESK/SHORING0MEZZ POUR 5

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 14:56 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 14:56 Sent To B
Notes
2003-09-30 00:00:00TO HP DESK/SHORING & RESHORING

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 14:54 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 14:54 Sent To B
Notes
2003-09-30 00:00:00TO HP DESK/MEZZ POUR 3 SHORING INSP
 FINA REL
 SITE FORMWORK INSP REP MEZZ POUR #3
 SHORING MOD @SOUTH BUILDING SECTION

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 14:53 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 14:53 Sent To B
Notes
2003-09-30 00:00:00TO HP DESK/SUBMITTAL 3200-51
 00315-50 POUR #2 COLS AREA 6 G5@ROOF

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 14:51 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 14:51 Sent To B
Notes
2003-09-30 00:00:00TO HP DESK/03200-29
 MEZZ POUR #4 SLAB BOTTOM & BEAMS
 03200-30
 MEZZ POUR #4 SLAB TOP & WALLS

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-24 Time 16:14 Rev Time 0.00
Received By csiegber Date 2003-09-24 Time 16:14 Sent To B
Notes
2003-09-24 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2004-05-05 Time 14:09 Rev Time 0.00
Received By csiegber Date 2003-09-24 Time 11:35 Sent To  
Notes
2003-09-24 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-09-10 Cont ID  
Sent By csiegber Date 2003-09-10 Time 08:11 Rev Time 0.00
Received By csiegber Date 2003-09-10 Time 08:10 Sent To  
Notes
2003-09-10 00:00:00ON COMM BD#54

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-08-28 Cont ID  
Sent By csiegber Date 2003-08-28 Time 15:42 Rev Time 0.00
Received By csiegber Date 2003-08-28 Time 15:42 Sent To  
Notes
2003-08-28 00:00:00ON COMM BD #18

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-27 Cont ID  
Sent By csiegber Date 2003-08-27 Time 14:42 Rev Time 0.00
Received By csiegber Date 2003-08-27 Time 14:41 Sent To B
Notes
2003-08-27 00:00:00TO HP DESK (PRODUCT APPROVALS)

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-27 Cont ID  
Sent By sthyng Date 2003-08-27 Time 11:14 Rev Time 0.00
Received By sthyng Date 2003-08-27 Time 11:14 Sent To P
Notes
2003-08-27 00:00:00PLANS ON RACK, MARKED CITY PLAZA

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 16:07 Rev Time 0.00
Received By alange Date 2003-08-04 Time 16:06 Sent To B
Notes
2003-08-04 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-17 Cont ID  
Sent By shernand Date 2003-07-17 Time 16:50 Rev Time 0.00
Received By shernand Date 2003-07-17 Time 16:50 Sent To  
Notes
2003-07-17 00:00:00COMM BOARD #44 , 3 SETS OF PLANS ON RACK
 NEXT TO CONF. ROOM.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-01 Cont ID  
Sent By shernand Date 2003-05-01 Time 10:03 Rev Time 0.00
Received By shernand Date 2003-05-01 Time 10:03 Sent To  
Notes
2003-05-01 00:00:00COMM BOARD #40. PLANS NEXT TO CONF ROOM
 AND SPECS IN BOX

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2006-01-05 Cont ID  
Sent By hmoser Date 2006-01-05 Time 08:59 Rev Time 0.00
Received By hmoser Date 2006-01-05 Time 08:59 Sent To  
Notes
2006-01-05 00:00:00CERTIFIED TEST AND BALANCE REPORT OK
 1/5/06 HM.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2005-05-30 Cont ID  
Sent By pkrauss Date 2005-05-30 Time 16:23 Rev Time 0.35
Received By pkrauss Date 2005-05-30 Time 16:23 Sent To  
Notes
2005-05-30 00:00:00SUBMITTAL LETTER, R/A PLENUMS DO NOT
 REQUIRE FIRE DAMPERS.COMMENTS FROM
 PREVIOUS REVIEW WERE NOT ADDRESSING THE
 RETURN AIR PLENUMS IN THE RESIDENCE.
 THE COMMENTS WERE IN REGARDS TO THE
 SHAFT PENETRATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2005-04-26 Cont ID  
Sent By pkrauss Date 2005-04-26 Time 13:36 Rev Time 0.00
Received By pkrauss Date 2005-04-26 Time 13:36 Sent To  
Notes
2005-04-26 00:00:00THE FOLLOWING MECHANICAL SHEETS ARE
 DENIED:
 M2.02, M2.04, M2.12, M2.13 RETURN AIR IS
 NOT INDICATED FROM BEDROOM #2.
  
 PROVISO:
 PLEASE NOTE, WHERE DUCTS PENETRATE A
 SHAFT, RATED WALLS OR FLOOR/CEILING
 ASSEMBLY A FIRE DAMPER IS REQUIRED.
 SHOULD THE SHAFT TERMINATE AT THE
 CEILING/FLOOR, A FIRE DAMPER AND ACCESS
 DOOR SHALL BE AT THE FLOOR PENETRATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2005-03-17 Cont ID  
Sent By pkrauss Date 2005-03-17 Time 15:20 Rev Time 0.40
Received By pkrauss Date 2005-03-17 Time 15:19 Sent To  
Notes
2005-03-17 00:00:00SUMITTAL SEF P1 & P2

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2004-08-20 Cont ID  
Sent By pkrauss Date 2004-08-20 Time 09:20 Rev Time 6.00
Received By pkrauss Date 2004-08-20 Time 09:12 Sent To  
Notes
2004-08-20 00:00:00DENIED:
 1.PLAN SHEET M2.02 INDICATES REV #3 ON
 THE PLAN BUT DOES NOT INDICATE THE DATE
 OF THE REVISION ON THE REVISION SCHEDULE
 OR THE DRAWING NARRATIVE.
  
 2.PLAN SHEET M2.04 UNIT 11L DOES NOT
 INDICATE RETURN AIR FROM BEDROOM #2.
  
 3.PLAN SHEET 2.35 & M5.05, PLANS
 INDICATE 2 COOLING TOWERS DELETED &
 MANUFACTURER CHANGED.PROVIDE SUBMITTAL
 FOR REVISED COOLING TOWER.
  
 4.PLEASE NOTE THIS CHANGE ALSO AFFECTS
 THE ENERGY CALCULATIONS PLEASE REVISE
 ENERGY CALCS.
  
 5.TONNAGE & GPM CHANGED ON THE COOLING
 TOWER, PLEASE PROVIDE CALCULATIONS
 DEMONSTRATING THAT THEY WILL MEET THE
 DEMAND.
  
 5.PLEASE NOTE MECHANICAL JOINTS
 (VICTALIC FITTINGS, COUPLINGS, ETC) ARE
 TO BE READYLY ACCESSIBLE. 2001 FBC(M)
 1209.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2004-05-10 Cont ID  
Sent By pkrauss Date 2004-05-10 Time 06:56 Rev Time 0.40
Received By pkrauss Date 2004-05-10 Time 06:56 Sent To  
Notes
2004-05-10 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVISION.SUBMITTAL LETTER DOES
 INDICATE THAT THE MECHANICAL WORK MAY
 BE AFFECTED BY CHANGES TO THE
 ARCHITECTICAL DRAWINGS.PLEASE PROVIDE
 REVISED MECHANICAL PLANS TO INCORPORATE
 CHANGES.PLEASE INDICATE ANY DELETION
 OR ADDITION OF FIRE DAMPERS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-07-29 Cont ID  
Sent By pkrauss Date 2003-07-29 Time 09:56 Rev Time 0.55
Received By pkrauss Date 2003-07-29 Time 09:56 Sent To  
Notes
2003-07-29 00:00:00PROVISO:
  
 AS PER OUR MEETING 7-25-03, GENERATOR
 EXHAUST SHALL TERMINATE A MINIMUM OF
 10 FT FROM ANY WINDOW, DOOR, OR FRESH
 AIR INTAKE.AFTER FURTHER RESEARCH
 NFPA 110 SECTION 7.10.2, EXHAUST
 INSTALLATION SHALL TERMINATE IN SUCH A
 MANNER THAT TOXIC FUMES CANNOT REENTER
 A BUILDING OR STRUCTURE, PARTICULARY
 THROUGH WINDOWS, AIR VENTILATION INLETS
 OR ENGINE AIR-INTAKE SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-05-19 Cont ID  
Sent By pkrauss Date 2003-05-19 Time 09:58 Rev Time 4.50
Received By pkrauss Date 2003-05-19 Time 09:56 Sent To  
Notes
2003-05-19 00:00:00DENIED:
  
 1.COMMENT #2, M.2.01 - FIRE DAMPER NOT
 INDICATED AT FLOOR (ONE ADDED AT WALL).
  
 2.COMMENT #12 FROM REVIEW DATED
 5-13-02, OUTSIDE AIR CALCS REQUIRED.
 PLEASE INDICATE OUTSIDE AIR CALCS FOR
 RESIDENTIAL & COMMON AREAS PER 2001 FBC
 (M) TABLE 403.3.
  
 3.PROVIDE VENTILATION REQUIREMENTS
 FOR GENERATOR ROOMS AND ALL MECHANICAL
 & PUMP ROOMS.INDICATE TERMINATION OF
 THE MUFFER EXHAUST AS WELL AS A DETAIL
 ON THE VENTILATION (INTAKE LOUVER &
 EXHUAST).
  
 4.ADDITIONAL PERMIT REQUIRED FOR FUEL
 OIL.PLEASE PROVIDE PLAN INDICATING
 PIPE SIZING & LAYOUT.PLEASE NOTE
 PRESSURE TEST REQUIRED ON PIPING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-03-19 Cont ID  
Sent By pkrauss Date 2003-03-10 Time 13:15 Rev Time 8.00
Received By pkrauss Date 2003-03-10 Time 13:15 Sent To  
Notes
2003-03-10 00:00:00DENIED:
  
 1.PLAN SHEET M1.02, INDICATES SMOKE
 REMOVAL DUCT TERMINATION.CLARIFY
 DISTANCE TO ANY FRESH AIR OPENINGS, I.E.
 DOORS, WINDOWS, O.A. INTAKES.
  
 2.PLAN SHEET M2.01, EXHAUST DUCT
 PASSING FROM CORRIDOR, BY STAIRS, THRU
 TO BREEZEWAY & UP TO MEZZANINE - NO
 DAMPERS INDICATED.
  
 3.PLAN SHEET M2.02, AHU R/A DUCT
 PENETRATES CORRIDOR WALL LEAVING AHU
 CLOSET & AGAIN GOING BACK INTO THE FOYER
 OF UNIT 16L & 18L, NO FIRE/SMOKE DAMPERS
 INDICATED.
  
 4.SHAFTS THAT ENCLOSE ENVIRONMENTAL
 AIR DUCTS SHALL NOT ENCLOSE ANY OTHER
 TYPE OF DUCTS (NFPA 90A 3-3.4.3).PLAN
 SHEET M2.02 SHOW SUPPLY AIR DUCTS IN THE
 SAME SHAFT AS EXHAUST DUCT, PLEASE
 CLARIFY.
  
 5.PLAN SHEET M2.03, DUCT CONTINUES UP
 TO MEZZANINE NO DUCT SIZE INDICATED.
  
 6.M2.08, O.A. DUCT TO WCACU-L.2-2,
 RATED WALL, NO FIRE DAMPER INDICATED.
  
 7.M2.08 O.A. DUCT, SUPPLY DUCT
 PENETRATES RATED WALL, PLEASE CLARIFY.
  
 8.SEE COMMENT # 3 FOR THE FOLLOWING
 UNITS: 11L, 27, 28, 29, B4, 16L.
  
 9.PLAN SHEET P2.45 INDICATES A FLOOR
 DRAIN IN THE PARKING GARAGE EXHAUST
 SHAFT.EXPLAIN HOW THIS IS GOING TO
 WORK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-13 Cont ID  
Sent By pkrauss Date 2002-05-13 Time 10:47 Rev Time 6.00
Received By pkrauss Date 2002-05-13 Time 08:31 Sent To  
Notes
2002-05-13 00:00:00 
 1.PLAN SHEET M1.06 - PLEASE CLARIFY
 DUCTS APPEAR TO BE IN ONE SHAFT.NOTE
 11 DRYER EXHAUST, NOTE 12 TRANSFER
 GRILLE AND THE 3RD IS NOT IDENTIFIED
 BUT APPEARS TO BE OUTSIDE AIR.AS PER
 2001 FBC(M) 603.8, CAVITIES IN FRAMED
 SPACES SHALL NOT BE USED TO DELIVER
 AIR FROM OR RETURN AIR TO CONDITIONING
 SYSTEM UNLESS THEY CONTAIN AN AIR DUCT
 INSERT INSULATED IN ACCORDANCE WITH
 TABLE 4-10 OR 6-10 CHAPTER 13 OF THE
 FBC.
  
 2.SHAFTS THAT CONSTITUTE AIR DUCTS OR
 ENCLOSE AIR DUCTS USED FOR ENVIRONMENTAL
 AIR SHALL NOT ENCLOSE: EXHAUST DUCTS
 USED FOR THE REMOVAL OF SMIKE & GREASE
 LADEN VAPORS FROM COOKING EQUIPMENT,
 DUCTS USED FOR CONVEYING VAPOR OR DUST,
 REFUSE & LINEN CHUTES, PIPING OR
 COMBUSTIBLE STORAGE.
  
 3.M1.07 CLARIFY DUCTWORK DOWN AT STAIR
 #2.NO FIRE DAMPERS ARE INDICATED.
 DUCTS SHALL NOT RUN IN THE STAIRWELL.
  
 4.M1.08 DUCTS TO THE CORRIDOR, FIRE
 DAMPERS ARE NOT INDICATED. 2001 FBC(M)
 607.6, SPECIFIC LOCATION & INSTALLATION
 DETAILS OF EACH FIRE DOOR, CEILING
 DAMPER AND FIRE & OR SMOKE DAMPERS
 SHALL BE SHOWN & PROPERLY IDENTIFIED ON
 PLANS.
  
 5.PLAN SHEET 4.11 DETAIL FOR GARAGE
 EXHAUST MUST HAVE A POSITIVE CONNECTION
 BETWEEN GRILLE & INTAKE TO FAN.
  
 6.OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3 & 307.2.4.
  
 7.PROVIDE DETAILS FOR THE GENERATOR
 EXHAUST.INDICATE TERMINATION IN
 COMPLIANCE WITH NFPA 110 5-10.
  
 8.PROVIDE STAIRWELL ELEVATION
 INDICATING LOCATION OF FAN, LOUVERS.
  
 9.INDICATE HOW DUCTWORK IS TO BE
 ACCESSED UNDER THE POOL AREA.WILL
 DUCTWORK HAVE ANY PROTECTION FROM
 MOISTURE, ELEMENTS OR DAMAGE?
  
 10. PROVIDE SEQUENCE OF OPERATION.
  
 11. PROVIDE TEST CRITERIA FOR SMOKE
 EVAC/CONTROL.
  
 12. OUTSIDE AIR CALCULATIONS SHALL
 PROVIDE COMPLIANCE WITH 402.2 (4% OF
 THE FLOOR AREA BDING VENTILATED) OR
 TABLE 403.3 (MECHANICAL VENTILATION NOT
 INFILTRATION).
  
 13. AS PER 2001 FBC(M) 602.2.1,
 MATERIALS EXPOSED WITHIN PLENUMS SHALL
 BE NONCOMBUSTIBLE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 18 Status P Date 2005-10-04 Cont ID  
Sent By kstevens Date 2005-10-04 Time 08:51 Rev Time 0.75
Received By kstevens Date 2005-10-04 Time 08:51 Sent To  
Notes
2005-10-04 00:00:00SUBMITTAL OK - PIPE, VALVES, FITTINGS,
 HANGARS/SUPPORTS, INSULATION, SLEEVES,
 BACKFLOW PREVENTERS

Review Stop P PLUMBING
Rev No 17 Status P Date 2005-06-15 Cont ID  
Sent By kstevens Date 2005-06-15 Time 07:51 Rev Time 0.28
Received By kstevens Date 2005-06-15 Time 07:51 Sent To  
Notes
2005-06-15 00:00:00SUBMITTAL OK - LETTER FROM STATE LINE
 PRODUCTS OF S. FLA. INC. FOR WARRANTY

Review Stop P PLUMBING
Rev No 16 Status F Date 2005-04-28 Cont ID  
Sent By kstevens Date 2005-04-28 Time 10:22 Rev Time 6.50
Received By kstevens Date 2005-04-27 Time 19:33 Sent To  
Notes
2005-04-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHTS P2.04 & P2.05 WATER HEATER PAN
 DRAINS SHALL EXTEND FULL SIZE AND
 TERMINATE OVER AN INDIRECT WASTE
 RECEPTOR, OR EXTEND TO THE EXTERIOR OF
 THE BUILDING. SECTION 504.8.2. PAN
 DRAINS ARE SHOWN DRAINING ONTO THE
 PARKING GARAGE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 15 Status F Date 2004-12-01 Cont ID  
Sent By kstevens Date 2004-12-01 Time 18:44 Rev Time 0.33
Received By kstevens Date 2004-12-01 Time 18:44 Sent To  
Notes
2004-12-01 00:00:00SUBMITTAL DENIED
  
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND THE CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. - CERTIFICATE OF
 AUTHROIZATION IS NOT SHOWN ON TITLE
 BLOCK OF EACH SHEET AS REQUIRED. FAC
 61G15-23.02(2) & FS 471.025
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 14 Status F Date 2004-10-23 Cont ID  
Sent By pschmitz Date 2004-10-23 Time 11:16 Rev Time 0.00
Received By pschmitz Date   Time   Sent To  
Notes
2004-10-23 00:00:00PLUMBING PLAN REVIEW FBCP 2001 DENIED
  
 SUBMITTAL FOR GRAB BARS, 3 COPIES
 REQUIRED.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 QUESTIONS CONTACT PERSON,561-805-6692

Review Stop P PLUMBING
Rev No 13 Status F Date 2004-08-16 Cont ID  
Sent By kstevens Date 2004-08-16 Time 15:35 Rev Time 7.00
Received By kstevens Date 2004-08-16 Time 15:21 Sent To  
Notes
2004-08-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) NUMEROUS SHEETS SHOW NOT CHANGES FROM
 THE LAST REVISION OR SINCE THE PLANS
 WERE STAMPED. PLEASE DELETE ALL SHEETS
 THAT HAVE NOT REVISION TO REVIEW. SECT-
 ION 104.2.1
 2) SHTS P2.01 & P3.13 RISER DIAGRAM DOES
 NOT REFLECT FLOOR PLAN. RISERS DOWN-
 STREAM OF 5" @ 302 FU SHOW 3" 4FU THEN
 2" 2FU ON FLOOR PLAN BUT RISER SHOWS THE
 2" 2FU & 3" 4FU IN REVERSE ORDER. THIS
 IS SHOWN AT 3 DIFFERENT AREAS. PLEASE
 CORRELATE PLANS. SECTION 104.2.1
 3) SHT P301 AIR CHAMBERS ARE NOT APPROV-
 ED IN MEN'S AND WOMEN'S BATHROOMS, AND
 A WATER HAMMER ARRESTOR IS REQUIRED AT
 THE DISH WASHER ON RISER FOR MEN'S BATH-
 ROOM. SECTION 604.9
 4) SHT P3.05 UNIT 25 WATER RISER DOES
 NOT REFLECT THE FLOOR PLAN ON SHT P2.16
 NO WATER SUPPLY SHOWN TO SHOWER.
 5) SHT P3.05 UNITS 1, 25, 28, & 38 WATER
 RISER DIAGRAMS. WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE DISH WASHER & ICE
 MAKER IN THE REFRIG. SECTION 604.9
 6) SHT P3.18 RISER 27/30 2ND/4TH FLOOR
 ISLAND VENT NOT APPROVED. VENT LINE
 SHOWN TIED BACK INTO THE VENT FROM THE
 ISLAND VENT IS A HORIZONTAL DRY VENT AND
 NOT APPROVED. SECTION 905.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 12 Status F Date 2004-07-15 Cont ID  
Sent By kstevens Date 2004-07-15 Time 11:09 Rev Time 1.50
Received By kstevens Date 2004-07-15 Time 11:09 Sent To  
Notes
2004-07-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 14
 FBC-2001 PLUMBING
  
  
 1) SECTION 1 AIR CHAMBERS ARE NOT APPRO-
 VED. DELETE FROM SUBMITTAL. SEC 604.9
 2) SECTION 2 HANGERS AND SUPPORTS. SUB-
 MITTAL INDICATES THAT THEY ARE UL LISTED
 PROVIDE UL LISTING IDENTIFICATION NUMBER
 FOR VERIFICATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 11 Status P Date 2003-12-01 Cont ID  
Sent By kstevens Date 2003-12-01 Time 14:27 Rev Time 1.00
Received By kstevens Date 2003-12-01 Time 14:27 Sent To  
Notes
2003-12-01 00:00:00REVISION OK - SHTS P2.45, P3.13, P3.15,
 P3.16, & P3.17

Review Stop P PLUMBING
Rev No 10 Status F Date 2003-10-10 Cont ID  
Sent By csiegber Date 2003-11-10 Time 09:34 Rev Time 3.00
Received By kstevens Date 2003-10-10 Time 17:15 Sent To  
Notes
2003-10-10 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P3.13 VENT REQUIRED FOR FLOOR
 DRAIN. (FROM PREVIOUS REVIEW)
 2) SHT P3.15 RISER 5/54/45/46, OFFSET
 VENT REQUIRED. SEE RED LINE
 3) SHT P3.16 RISER 14/41 OFFSET VENT
 REQUIRED. SEE RED LINE
 4) SHT P3.17 RISERS 23/36 & 22/57/37/38,
 OFFSET VENTS REQUIRED. SEE RED LINE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 9 Status P Date 2003-08-28 Cont ID  
Sent By kstevens Date 2003-08-28 Time 09:26 Rev Time 0.50
Received By kstevens Date 2003-08-28 Time 09:25 Sent To  
Notes
2003-08-28 00:00:00PASSED/PROVISO
  
  
 REVISIONS REQUIRED FOR ALL SHEETS WITH
 RED-LINE CORRECTIONS NOTED, AND FOR
 COMMENTS DATED 8-11-3.
 REVISIONS SHALL BE SUBMITTED BY 9-8-03
 KSTEVENS

Review Stop P PLUMBING
Rev No 8 Status F Date 2003-08-27 Cont ID  
Sent By kstevens Date 2003-08-27 Time 18:10 Rev Time 8.00
Received By kstevens Date 2003-08-27 Time 18:10 Sent To  
Notes
2003-08-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 SHEET P-3.14 IN ONE SET OF PLANS HAS A
 SINK ADDED. - PLEASE CHANGE OUT SHEET
 AND PROVISO WILL BE ISSUED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status F Date 2003-08-21 Cont ID  
Sent By sthyng Date 2003-08-27 Time 11:15 Rev Time 3.00
Received By kstevens Date 2003-08-21 Time 13:04 Sent To  
Notes
2003-08-21 00:00:00DENIED
 REFERENCE: FBC-2001 AMENDMENTS, CHAPTER
 ONE
  
 1) SECTION 104.2.1 AS REQUIRED BY 104.3.
 1.1 OF THE CODE, TWO OR MORE COPIES OF
 DRAWINGS SHALL ACCOMPANY THE APPLICATION
 FOR A PERMIT. (THREE SETS IF THRESHOLD
 INSPECTION SYSTEM). - ONE SET OF PLANS
 IS COMPLETE. - ONE SET OF PLANS HAS SHT
 P2.03 MISSING. - ONE SET OF PLANS HAS
 SHTS P3.13 VOIDED, P3.14 VOID, P3.16
 VOID, AND P3.18 VOID. SUBMIT LATEST
 REVISION FOR THIS SET.
 2) PLEASE PICK UP PLANS AND RESUBMIT FOR
 REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status F Date 2003-08-20 Cont ID  
Sent By kstevens Date 2003-08-15 Time 18:16 Rev Time 0.50
Received By kstevens Date 2003-08-15 Time 18:16 Sent To  
Notes
2003-08-15 00:00:00PASSED/PROVISO
  
 LAST COMMENTS HAVE BEEN ADDRESSED BY MR.
 WILLIAM GOMEZ. HE STATED THAT THE SIGNED
 AND SEALED SHEETS WILL BE SUBMITTED FOR
 FINAL APPROVAL. PLEASE SUBMIT WITHIN A
 WEEK FOR FINAL APPROVAL OF PLUMBING.

Review Stop P PLUMBING
Rev No 5 Status F Date 2003-08-11 Cont ID  
Sent By kstevens Date 2003-08-11 Time 15:39 Rev Time 4.00
Received By kstevens Date 2003-08-11 Time 15:38 Sent To  
Notes
2003-08-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) RISERS 43/55/44/12 6TH THROUGH 10TH
 FLOOR. WHEN A HORIZONTAL STACK OFFSET IS
 LOCATED MORE THAN FOUR BRANCH INTERVALS
 BELOW THE TOP OF THE STACK, A HORIZONTAL
 BRANCH SHALL NOT CONNECT WITHIN THE
 HORIZONTAL STACK OFFSET OR WITHIN 2 FEET
 ABOVE OR BELOW SUCH OFFSET. SEC 711.2
 SHT P3.16 (WASH MACHINE)
 2) RISER #1 SEE COMMENT #1 (BATHROOM AND
 SINK) SHT P3.14
 3) RISER #2 6TH FLOOR W/M DRAINS THROUGH
 BATHROOM GROUP. SEC 909.1 SHTP3.14 ALSO
 RISERS 53/50/51
 4) RISERS 34/58/25 KITCHEN SINK CONNECT-
 ED IN HORIZONTAL OFFSET. (SEE COMMENT #
 1)
 5) RISER #13 SHT P3.16 KITCHEN SINK
 CONNECTED IN OFFSET. (SEE COMMENT #1)
 6) RISER #52 SAME AS RISER #1.
 7) SECTION 917.3.2 RELIEF VENT REQUIRED
 TO AIR ADMITTANCE VALVES. ALL 8 A.A.V'S
 WILL WILL REQUIRE A RELIEF VENT.
 8) PLANS SHALL BE PICKED UP AND RESUB-
 MITTED. PER CITY CODE A 10% RESUB FEE
 WILL BE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2003-08-04 Cont ID  
Sent By kstevens Date 2003-08-04 Time 09:44 Rev Time 7.50
Received By kstevens Date 2003-07-31 Time 13:52 Sent To  
Notes
2003-08-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) FROM PREVIOUS REVIEW: ALL UNITS - WET
 VENTS IN BATHROOMS, ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 KICHEN SINKS, AND WASH MACHINES SHALL
 NOT DRAIN THROUGH BATHROOMS. SEC 909.1
 THE FOLLOWING LIST STILL NEEDS TO BE
 CORRECTED.
 SHT P2.11 UNITS 35 & 36 - RISERS 3 & 48
 SHT P2.12 UNIT 24RISERS 11/43/55/44/12
 SHT P2.14 UNIT 1 (RISER NOT SHOWN)
 SHT P2.19 UNIT Q - RISER 1
 SHT P2.19 UNIT B3 - RISERS 2/53
 SHT P2.19 UNIT B5 - RISERS 50/51
 SHT P2.20 UNIT B2 - RISER 13
 SHT P2.22 UNIT B6 - RISERS 34/58/25
 SHT P2.26 UNIT J2 - RISERS 31/32
 SHT P2.27 UNIT BD - RISER 5
 SHT P2.35 UNIT G1 - RISERS 1 & 2
 SHT P2.35 UNIT B7 - RISER 46
 SHT P2.35 UNITO - RISER 4
 SHT P2.35 UNITG - RISERS 51/52
 SHT P2.36 UNITL - RISER 45
 SHT P2.36 UNITN - RISER 43
 SHT P2.36 UNITM - RISER 12
 SHT P2.38 UNITC - RISER 28
 SHT P2.38 UNIT 01 - RISER 23
 2) SHT P3.13 FLOOR DRAIN IN TRASH TER-
 MINATION ROOM NOT VENTED. ALSO NEW LINE
 TO FLOOR DRAIN FOR FIRE SYSTEM HUB DRAIN
 NOT VENTED.
 3) SHT P.13 FLOOR DRAIN IN BREEZEWAY
 STILL SHOWN ON THE SANITARY RISER DIA-
 GRAM. THIS WAS CHANGED TO STORM.
 4) FROM THE PREVIOUS REVIEW: (#10 FROM
 LAST REVIEW) SHT P.13 SHOWS PIPING THAT
 IS NOT SHOWN ON THE GROUND LEVEL LOBBY
 AREAS, (PLAN VIEW). SUBMIT A SHEET THAT
 SHOWS THE PLAN VIEW AREA BETWEEN THE
 NORTH AND SOUTH SECTIONS THAT REFLECTS
 THE RISER DIAGRAM FOR THIS AREA.
 5) FROM PREVIOUS REVIEW: SHT P3.10 PIPE
 SIZE NOT SHOWN FOR RWL IN SOME AREAS.
 SOME PIPE SIZES STILL ARE NOT INDICATED
 AS REQUESTED. SEE RED LINE AREAS INDICA-
 TED ON PLANS.
 6) FROM PREVIOUS REVIEW: SEPARATE BACK-
 FLOWS REQUIRED FOR POOL AND IRRIGATION.
 7) FROM PREVIOUS REVIEW: SHT P2.43 THE
 WASTE FROM THE BACKWASH SHAL DRAIN TO
 SANITARY. DETAIL SHOWS BACKWASH DRAINING
 TO STORM. OVERFLOW ONLY TO STORM.
 8) FROM PREVIOUS REVIEW: (#30) RESPONSE
 INDICATES THAT STACK 30 IS NOW A CONVEN-
 TIONAL WASTE STACK AND VENT STACK, BUT
 THE STACK HAS BEEN DELETED. PLEASE
 CLAIRFY.
 9) SHT P3.15 RISER #8 DOES NOT REFLECT
 THE FLOOR PLAN. SHT P2.36 UNIT A SHOWS
 IN CLOUDED AREA 3" WASTE FROM ABOVE.
 RISER #8 SHOWS 3 LAVS AND NO 3" WASTE
 FROM ABOVE. PLEASE CLAIRFY. (IF 3" WASTE
 FROM ABOVE, IT SHALL TIE IN DOWNSTREAM
 OF THE BATHROOM GROUP. 909.1)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-06-03 Cont ID  
Sent By kstevens Date 2003-06-03 Time 10:39 Rev Time 18.00
Received By kstevens Date 2003-06-03 Time 10:39 Sent To  
Notes
2003-06-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 A) FROM PREVIOUS REVIEW: - NOT ADDRESSED
 1) SHT P2.01 VENT REQUIRED IN TRASH ROOM
 2) ALL UNITS - WET VENTS IN BATHROOMS,
 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. (KITCHEN SINKS AND WASH-
 MACHINES SHALL NOT DRAIN THROUGH BATH-
 ROOMS.) SEC 909.1 - THESE CONDITIONS
 SHALL BE CORRECTED ON THE SANITARY RISER
 DIAGRAMS AND ALL FLAT LAYOUTS.
 3) SHT P2.31 HORIZONTAL RWL NOT SIZED
 PROPERLY. SHOWS 4" @ 2900 SQ FT & 2800
 SQ FT. (ORIGINAL #16) RESPONSE NOTED,
 BUT NO CHANGE NOTED.
 4) SHT P2.39 PLEASE SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SHOW ALL AREAS OF ROOFS THAT DRAIN TO
 ROOF FROM ABOVE. (NOT SHOWN IN CALCULAT-
 IONS AS REQUESTED IN COMMENT #19 IN 1ST
 REVIEW.)
 5) SHTS P2.40 & P2.41 PIPE SIZING FOR
 VENT HEADER SHALL BE SIZED PER TABLE
 916.1. SECTION FROM VENT #10 BACK TO
 WHERE VENT #44 TIES IN PAST #12 SHALL
 BE 5". 4" PIPE SHOWN. (COMMENT TO RES-
 PONSE FROM COMMENT #21 1ST REVIEW).
 6) SHT P2.44 SHOW PIPE SIZE FOR RWL.
 SHOWS 6" @ 4000 SQ FT, BUT ITS ACTUALLY
 IT'S 5000 SQ FT AND SHOULD BE 8" PIPE.
 RESPONSE NOTED BUT NO CHANGE NOTED.
 (COMMENT #22 FROM 1ST REVIEW.)
 7) SHT P2.05 VENT REQUIRED FOR FLOOR
 DRAIN IN BREEZEWAY DRIVE. (RESPONSE
 NOTED, BUT VENT REQUIRED) #24 1ST REV.
 8) SHT P2.05 VENTS REQUIRED FOR FLOOR
 DRAINS IN TRASH ROOM AND TRASH TERMIN-
 ATION ROOM. (RESPONSE NOTED, BUT VENTS
 REQUIRED.) #25 1ST REV.
 9) SHTS P2.01 THRU P2.05 CLEANOUTS REQ-
 UIRED BY SECTIONS708.3, 708.3.1, 708.3.3
 & 708.3.4 SHALL BE SHOWN ON SHTS P2.01
 THRU P2.05, HORIZONTAL PLUMBING LAYOUT,
 AND NO SHT P3.13 HORIZONTAL SANT. RISER
 DIAGRAM. (NEW COMMENT)
 10) SHT P3.13 SHOW PIPING THAT IS NOT
 SHOWN ON GROUND LEVEL LOBBY AREAS.
 PLEASE SUBMIT A SHEET THAT SHOWS THE
 AREA BETWEEN THE NORTH SIDE AND THE
 SOUTH SIDE TO SHOW HOW PIPING TIES IN
 FOR AREA NOT SHOWN. SEC 104.2.1
 11) SHT P2.49 UNABLE TO VERIFY RESPONSE,
 SHEET IS COMPLETLY CHANGED AND ONE COPY
 OF ALL SHEETS THAT HAVE BEEN REMOVED AND
 OR REVISED FOR COMPARISON. #26 1ST REV.
 12) SHT P2.49 INFORMATION FOR FOUNTAIN
 SHALL BE SUBMITTED AT TIME FOR PERMIT
 APPLICATION. SEPARATE PERMIT REQUIRED.
 #27 1ST REV.
 13) SHTS P3.02,P3.03,P3.04,P3.05,P3.06,
 P3.07, & P3.08 WATER HAMMER ARRESTORS
 SHALL BE INSTALLED AT EVERY WASH MACHINE
 ICE MAKER & DISHWASHER. SOME W/M'S SHOW
 THEM AND SOME KITCHEN SINKS SHOW THEM,
 BUT NOT ALL HAVE THEM SHOWN WERE REQUIR-
 ED BY SECTION 604.9. #28 1ST REV.
 14) SHT P3.09 RWL SHOWS 4" @ 1900 SQ FT
 ON VERTICAL. BUT RISER ALSO RUNS HORIZ-
 ONTAL, (OFFSET). 5" RISER REQUIRED. RE-
 SPONSE NOTED BUT NOT ADDRESSED. #30 1ST
 REVIEW. TABLE 1106.3
 15) SHT P3.10 RWL BY DECK, NO PIPE SIZE
 SHOWN. RESPONSE NOTED BUT SIZE NOT SHOWN
 #31 1ST REV.
 16) SHT P3.10 RWL RISER ALSO RUNS HORIZ-
 ONTAL, 8" RISER REQUIRED. RESPONSE NOTED
 BUT SIZE NOT CORRECTED. #32 1ST REV.
 17)SHT P3.10 RWL RISER SHOWS 5" @3000 SQ
 FT PICKING UP 2 ROOF DRAINS. HORIZONTAL
 RUNS, 6" REQUIRED. RESPONSE NOTED BUT
 CORRECT SIZE NOT SHOWN. #33 1ST REV.
 18) SHT P3.10 PIPE SIZE NOT SHOWN FOR
 RWL IN SOME AREAS. RESPONSE NOTED BUT
 SOME PIPE SIZES STILL NOT SHOWN. PLEASE
 RECHECK ALL PIPING FOR RWL RISER DIAGRAM
 AND SIZE ALL PIPE AND RECHECK FOR CORR-
 ECT SIZE PER TABLE 1106.3#34 1ST REV.
 19) SHT P3.10 RWL RISER SHOWS 6" @ 6900
 SQ FT, REQUIRES 8" AT HORIZONTAL RUN.
 RESPONSE NOTED, BUT SIZE NOT CHANGED.
 #36 1ST REVIEW.
 20) SHT P3.10 RWL RISER SHOWS 5" @ 5700
 SQ FT HORIZONTAL RUNS REQUIRE 8" PIPE.
 RESPONSE NOTED BUT PIPE SIZE NOT CHANGED
 #37 1ST REV.
 21) SHT P3.13 FLOOR DRAIN NOT VENTED.
 RESPONSE NOTED, VENTS STILL REQUIRED.
 TABLE 906.1
 22) SHT A5.11 FOUNTAIN EQUIPMENT AREA
 MORE INFO REQD. RESPONSE REFERS TO SHT
 A5.11 WHICH REFERS TO L.S. PLANS. NO
 LS PLANS FOUND. PLEASE CLAIRFY. #44 1ST
 REVIEW.
 23) SHTS A8.01 THRU A8.14 RESPONSE NOTED
 FOR WATER COOLERS AT LIVE/WORK LOFTS.
 MANUF. INFO. REQUIRED FOR WATER COOLERS
 AT TIME OF FINAL. 410.1
 24) SHTS A8.12/A8.13 TERRACE DRAINS. RE-
 SPONSE NOTED, BUT SHTS P2.32 & P2.33 DO
 NOT REFLECT SHTS A8.12 & A8.13. 11TH FL
 AND 4TH FLOOR. PLEASE CLAIRFY. #49 1ST
 REVIEW.
 25) PLEASE SUBMIT TYPE OF MATERIAL USED
 FOR PAN DRAIN, RELIEF VALVE PIPING. RE-
 SPONSE NOTED BUT MATERIAL NOT SHOWN. #55
 1ST REVIEW.
 26) BACKFLOW REQUIRED FOR SWIMMING POOL,
 IRRIGATION, AND MAKE UP WATER FOR THE
 COOLING TOWERS. RESPONSE NOTED, BUT EACH
 SYSTEM SHALL BE PROVIDED WITH BACKFLOW
 PROTECTION. PLEAS INDICATE HOW EACH SYS-
 TEM HAS BACKFLOW PROTECTION. #58 1ST REV
 28) RESPONSE NOTED FOR POOL PUMP AND
 EQUIPMENT ROOM, SEPARATE PERMIT REQUIRED
 FOR POOL. WASTE SHALL DRAIN TO SANITARY
 AND OVERFLOW SHALL DRAIN TO STORM. PRO-
 VIDE DETAIL FOR EACH. #59 1ST REVIEW.
 29) SHTS P2.02 & P2.05 FIRE SPRINKLER
 SYSTEM DRAIN SHALL DRAIN TO SANITARY NOT
 STORM AS INDICATED. PLEASE REVISE
 30) SHT P3.14 WASTE STACK #30 SECTION
 910.2 THE STACK SHALL BE VERTICAL AND
 BOTH HORIZONTAL & VERTICAL OFFSETS SHALL
 BE PROHIBITED.
 31) SHT P2.44 TABLE 906.1 MAXIMUM DIS-
 TANCE OF FIXTURE TRAP FROM VENT FOR A
 3" TRAP IS 10'. FLOOR DRAINS FOR THE
 SAUNA AND THE STEAM ROOM SEEM TO EXCEED
 THIS AMOUNT.
 ********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-03-19 Cont ID  
Sent By kstevens Date 2003-03-18 Time 18:00 Rev Time 25.00
Received By kstevens Date 2003-03-15 Time 15:49 Sent To  
Notes
2003-03-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) SHT P2.01 VENT REQUIRED FOR FLOOR
 DRAIN IN TRASH ROOM.
 2) ALL UNITS - WET VENTS IN BATHROOMS,
 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDIDIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. (KITCHEN SINKS AND WASH-
 MACHINES SHALL NOT DRAIN THROUGH BATH-
 ROOMS) SECTION 909.1 - THESE CONDITIONS
 SHALL BE CORRECTED ON THE SANITARY RISER
 DIAGRAMS AND ALL FLAT LAYOUTS.
 3) SHT P2.01 RAIN WATER LEADER IS NOT
 SIZED PROPERLY. UNIT 27L
 4) SHT P2.01 PROVIDE AREA BEING DRAINED
 AT TRENCH DRAINS.
 5) SHT P2.01 SECTION 504.7.1 THE DIS-
 CHARGE PIPE SHALL NOT HAVE ANY TRAPPED
 SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP. (RELIEF VALVE FOR HEATER)
 6) SHT P2.01 PROVIDE CALCULATIONS FOR
 CONDENSATE FROM UNITS TO DETERMINE PIPE
 SIZE.
 7) P2.04 4" SANT. AT RISERS 37, 22, 57,
 & 38 SHOWS 4" @ 420 F.U. (MAX 180 F.U.)
 8) SHT P2.04 UNISEX TOILET - NO SANT. TO
 W/C AND LAV.
 9) SHT P2.05 SHOW PIPE SIZE FOR RWL PAST
 TRASH ROOM.
 10) SHT P2.05 SHOW PIPE SIZE FOR COND.
 TO TRASH ROOM.
 11) SHT P2.11 MAX DISTANCE FOR W/C IS 10
 FEET. TABLE 906.1
 12) SHT P2.18 UNIT #3, SHOW PIPE SIZE
 FOR HORIZONTAL RWL. (1900 SQ FT)
 13) SHT P2.19 UNIT B3 SHOW PIPE SIZE FOR
 HORIZONTAL RWL. (2900 SQ FT)
 14) SHT P2.22 UNIT B6, SHOW PIPE SIZE
 FOR HORIZONTAL RWL. (2000 SQ FT)
 15) NEAR UNIT B7, RWL NOT SIZED PROPERLY
 SHOULD BE 890 SQ FT FOR BOTH SIDES. 1980
 SQ FT TOTAL.
 16) SHT P2.31 HORIZONTAL RWL NOT SIZED
 PROPERLY. SHOWS 4" @ 2900 & 2800 SQ FT.
 17) SHT P2.33 UNIT M, 3 DD @ 600 SQ FT
 EACH = 1800 SQ FT. 1500 SQ FT SHOWN.
 PIPE SIZED WRONG.
 18) SHT P2.34 UNIT O, 6" RWL DOWN SHOWS
 600 SQ FT. ADDS UP TO 2900 SQ FT. PLEASE
 ADJUST PLANS.
 19) SHT P2.39 PLEASE SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SHOW ALL AREAS OF ROOFS THAT DRAIN TO
 ROOF FROM ABOVE.SHOW 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPET WALLS.
 INDICATE TOTAL AREA OF MAIN ROOF. SHOW
 LOCATION OF ALL SECONDARY ROOF DRAINS &
 INDICATE AREA BEING DRAINED BY EACH.
 PROVIDE A DETAIL FOR SCUPPERS SHOWING
 LENGTH - WIDTH - HEIGHT - SEE SECTIONS
 1106, 1106.4, 1106.5, 1107, 1107.1,
 1107,2 & 1107.3
 20) SHT P2.44 POOL DECK WATER RISERS,
 AIR CHAMBERS ARE NOT APPROVED. PLEASE
 DELETE FROM RISERS.
 21) SHTS P2.40 & P2.41, SHOW TOTAL F.U.
 FOR COMBINED SANITARY RISERS THAT VENT
 THRU ROOF TOGETHER.
 22) SHT P2.44 SHOW PIPE SIZE FOR RWL.
 SHOWS 6" @ 4000 SQ FT. WHEN ADDED IT
 COMES TO 5000 SQ FT AND 6" IS NOT SUFFI-
 CIENT.
 23) SHT P2.45 GARAGE EXHAUST CHASE, WHAT
 WILL BE DRAINING INTO THE FLOOR DRAIN IN
 THE BOTTOM?
 24) SHT P2.45 VENT REQUIRED FOR FLOOR
 DRAIN IN BREEZEWAY DRIVE.
 25) SHT P2.45 VENTS REQUIRED FOR FLOOR
 DRAINS IN TRASH ROOM AND TRASH TERMINA-
 TION ROOM.
 26) SHT P2.49 SQ FOOTAGE NOT CALCULATED
 PROPERLY FOR RWL BY PARKING SPACE 495.
 450 + 220 + 220 = 440 SQ FT ???
 890 + 890 = 1780 SQ FT NOT 1330. 5" PIPE
 IS REQUIRED.
 27) SHT P2.49 MORE INFORMATION REQUIRED
 FOR WATER WALL.
 28) SHTS P3.02, P3.03, P3.04, P3.05,
 P3.06, P3.07 & P3.08 AIR CHAMBERS ARE
 NOT APPROVED. PLEASE DELETE FROM RISERS.
 WATER HAMMER ARRESTORS REQUIRED BY SEC.
 406.9 SHALL BE LOCATED NEAR THE FIXTURE,
 NOT IN CEILING PER PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS. (WASH MACHINE
 ICE MAKER, & DISHWASHER).
 29) SHT P3.09 RWL RISER SHOWS 4" @ 1500
 SQ FT & 4" @ 2900 SQ FT ON SAME RISER.
 PLEASE CLAIRFY.
 30) SHT P3.09 RWL RISER SHOWS 4" @ 1900
 SQ FT ON VERTICAL. BUT RISER ALSO RUNS
 HORIZONTAL, (OFFSET). 5" RISER REQUIRED.
 31) SHT P3.10 RWL BY DECK, NO PIPE SIZE
 SHOWN.
 32) SHT P3.10 RWL RISER SHOWS 5" @ 5100
 SQ FT, BUT RISER ALSO RUNS HORIZONTAL.
 8" RISER REQUIRED.
 33) SHT P3.10 RWL RISER SHOWS 5" @ 3000
 SQ FT PICKING UP 2 ROOF DRAINS. RUNS
 HORIZONTAL, 6" REQUIRED.
 34) SHT P3.10 PIPE SIZE NOT SHOWN FOR
 RWL PIPE IN SOME AREAS.
 35) SHT P3.10 PROVIDE AREA BEING DRAINED
 BY TRENCH DRAINS.
 36) SHT P3.10 RWL RISER SHOWS 6" @ 6900
 SQ FT. RUNS HORIZONTAL, 8" RISER REQD.
 37) SHT P3.10 RWL RISER SHOWS 5" @ 5700
 SQ FT. RUNS HORIZONTAL, 8" RISER REQD.
 38) SHTS P3.11 & P3.12 RELIEF VENTS RE-
 QUIRED AS CONDENSATE EXITS BLDG.
 39) SHT P3.13 FLOOR DRAINS NOT VENTED.
 40) SHTS P3.14 & P3.15 SOIL AND WASTE
 STACKS IN BUILDINGS HAVING MORE THAN 10
 BRANCH INTERVALS SHALL BE PROVIDED WITH
 A RELIEF VENT AT EACH TENTH INTERVAL IN-
 STALLED, BEGINNING WITH THE TOP FLOOR.
 SECTION 914.1
 41) SHTS P3.14/P3.15 HORIZONTAL OFFSETS
 OF DRAINAGE STACKS SHALL BE VENTED WHERE
 FIVE OR MORE BRANCH INTERVALS ARE LOCAT-
 ED ABOVE THE OFFSET. THE OFFSET SHALL BE
 VENTED BY VENTING THE UPPER SECTION OF
 THE DRAINAGE AND THE LOWER SECTION OF
 THE DRAINAGE STACK. SECTION 915.1
 UPPER SECTION SECTION 915.2 LOWER 915.3
 ALSO SEE SECTION 903.4
 42) SHTS P3.14/P3.15 IF A HORIZONTAL
 BRANCH CONNECTS TO THE STACK WITHIN 2 FT
 ABOVE OR BELOW A VERTICAL AND THE OFFSET
 IS LOCATED MORE THAN FOUR BRANCH INTER-V
 ALS BELOW THE TOP OF THE STACK, THE OFF-
 SET SHALL BE VENTED IN ACCORDANCE WITH
 SECTION 915. SECTION 711.1
 43) SHTS P3.14/P3.15 WHEN A HORIZONTAL
 STACK OFFSET IS LOCATED MORE THAN FOUR
 BRANCH INTERVALS BELOW THE TOP OF THE
 STACK, A HORIZONTAL BRANCH SHALL NOT
 CONNECT WITHIN THE HORIZONTAL STACK OFF-
 SET OR WITHIN 2 FEET ABOVE OR BELOW SUCH
 OFFSET. SECTION 711.2 - SEE SECTIONS
 711.3, SECTION 914, 710.1.1, TABLE
 710.1(2) COL 4, SECTION 711.3.1 & SECT-
 ION 711.4.
 44) SHT A5.11 FOUNTAIN EQUIPMENT AREA
 NOT SHOWN ON PLUMBING. MORE INFORMATION
 AND DETAILS REQUIRED.
 45) SHT A5.11A SHOWS POOL EQUIPMENT AREA
 IN THE SAME AREA AS THE FOUNTAIN EQUIP.
 AREA SHT A5.11. PLEASE CLAIRFY.
 46) SHTS A8.01 THRU A8.05 DOOR SHALL NOT
 OPEN INTO THE CLEAR FLOOR SPACE OF ANY
 FIXTURE OR THE 5' TURNING CIRCLE. PLEASE
 CHANGE AS REQUIRED.
 47) SHTS A8.01 THRU A8.05 ALL LIVE/WORK
 LOFTS SHALL HAVE A DRINKING FOUNTAIN PER
 TABLE 403.1. (ALSO SEE 410.1)
 48) SHTS A8.01 THRU A8.14 SHOW CLEAR
 FLOOR SPACE FOR ALL FIXTURES PER FHA
 DESIGN MANUAL PAGE 7.43 & CHAPTER 11 FBC
 49) SHTS A8.12/A8.13 TERRACE DRAINS NOT
 SHOWN ON PLUMBING PLANS. SCUPPER DETAILS
 NOT SHOWN. PLEASE SUBMIT DETAILS AND
 CALL OUT DRAINS ON PLUMBING PLANS.
 50) SHTS A8.13, A8.14, A8.19 THRU A8.39
 PER FHA DESIGN MANUAL, INDICATE SPECI-
 FICATION "A" OR "B" PER REQUIREMENT #7
 FOR ALL UNITS.
 51) SHT A8.26 MENS RESTROOM L106, SHOW
 CLEAR FLOOR SPACE FOR URNAL.
 52) PLEASE SUBMIT ALL SANITARY RISER
 DIAGRAMS. 37 RISERS ARE NOT SHOWN.
 MISSING ARE #'S 8 THRU 10, 12 THRU 15,
 17 THRU 20, 22 THRU 29, 31, 32, 34 THRU
 44, & 55 THRU 59.
 53) PLEASE CONTACT RODNEY COMPO, ENVIRO-
 NMENTAL COMPLIANCE TO SEE IF AN OIL
 SEPARATOR IS REQUIRED FOR TRENCH DRAINS.
 54) SHT A5.16 PLEASE SUBMIT DETAILS FOR
 STEAM ROOM L117.
 55) PLEASE SUBMIT RISERS FOR RELIEF
 VALVE DISCHARGE,(T/P), AND EMERGENCY PAN
 DRAIN LINES FOR WATER HEATERS. INDICATE
 TYPE OF MATERIAL USED AND ALL PIPE SIZE-
 ING. - SHOW THERMAL EXPANSION CONTROL ON
 WATER HEATER DETAIL. SECTION 607.3.2
 56) SHT P6.02 FUEL TANK ROOM, CONTAIN-
 MENT IN CASE OF SPILLAGE?
 57) SEPARATE PLANS & PERMIT REQUIRED FOR
 POOL AND POOL EQUIPMENT ROOM. PLEASE
 ROUTE PLANS TO PALM BEACH HEALTH UNIT
 DIVISION OF ENVIRONMENTAL HEALTH 901
 EVERNIA ST WPB 33401 (561) 355-3018
 58) BACKFLOW REQUIRED FOR SWIMMING POOL
 WATER SERVICE SUPPLY LINE. BACKFLOW RE-
 QUIRED FOR IRRIGATION.
 59) PLEASE PROVIDE DETAILS FOR POOL PUMP
 AND EQUIPMENT ROOM PER SECTION 424.1.5
 AND ALL SUBSECTIONS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
  
  
  
  
  
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 (561) 653-2692 FAX

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-10 Cont ID  
Sent By kstevens Date 2002-05-10 Time 18:53 Rev Time 0.00
Received By kstevens Date 2002-05-10 Time 18:53 Sent To  
Notes
2002-05-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) PLANS ARE NOT COMPLETE FOR SUFFICIENT
 REVIEW. MORE INFORMATION IS REQUIRED FOR
 COMPLETE REVIEW.
 2) SHT P1.01 OIL INTERCEPTORS, PLEASE
 CONTACT RODNEY COMPO ENVIRONMENTAL COM-
 PLIANCE FOR SIZE OF OIL INTERCEPTORS
 (561) 837-4074.(SHT P1.05 ALSO)
 3) SHT P1.05 NOT SANITARY SHOWN FOR
 POWDER ROOM.
 4) SHT P1.07 BATH B2 NO SANITARY SHOWN
 TO WATER CLOSET.
 5) SHT P1.26 M/BATH UNIT K NO SANT TO
 TUB.
 6) SHT P1.28 SHOWS STEAM SAUNA IN MENS
 ROOM AND URNAL IN WOMENS ROOM ???
 7) SHT P1.40 BATHROOM B2 BY STAIR #4 TUB
 NOT VENTED PROPERLY
 8) SHT P1.42 RISER #5 W/C NOT VENTED.
 9) SHT UNIT R WASH MACHINE SHALL NOT
 DRAIN INTO BATHROOM GROUP.
 10) SHT P1/47 TUB NOT VENTED UNIT T
 11) SHT P1.56 RISERS ARE INCOMPLETE.
 PLEASE IDENTIFY EACH RISER. RELIEF VENT
 NOT SHOWN ON RISERS
 12) PLEASE SUBMIT RISER DIAGRAMS FOR
 STORM, WATER, CONDENSATE, RELIEF VALVE -
 (P/T) DISCHARGE, & EMERGENCY PAN DRAIN.
 ALSO GIVE A COMPLETE RISER DIAGRAM ISO-
 METRIC SHOWING COMPLETE SYSTEMS WITH
 HORIZONTAL PIPING, PIPE SIZE FIXTURE UN-
 IT LOADS AS THEY ACCUMULATE AT EACH RIS-
 ER ALL THE WAY OUT OF BLDG.
 13) SHOW ALL OFFSETS FOR EACH SANITARY R
 ISERS AND INDICATE IF VERITCAL OR HORIZ-
 ONTAL OFFSETS.
 14) VENTS NOT SHOWN THRU ROOF.
 15) SHT 1.64 LANAI ROOF - WHAT IS THE
 DESIGNATION PR REFER TO? NOT ALL PIPES
 ARE SIZED.
 16) SHT A1.05 TRANSFORMER VAULT, IS SUMP
 TO BE PIPED OR JUST FOR CONTAINMENT OF
 OILS IN CASE OF EMERGENCY?
 17) SHT A1.05 GARAGE EXHAUST AND AIR
 SUPPLY FLOOR DRAINS, TO STORM? WILL FIRE
 AND DOMESTIC PUMP RMS HAVE FLOOR DRAINS?
 18) SHT A1.05 FUEL TANK ROOM, CONTAIN-
 MENT IN CASE OF SPILLAGE?
 19) PLEASE SUBMIT CALCULATIONS FOR ALL
 PRIMARY AND SECONDARY ROOF DRAINS. ADD
 ALL AREAS OF ROOF THAT DRAIN FROM ABOVE
 AND 1/2 ALL AREA OF ALL VERTICAL WALLS.
 SHOW LOCATION OF ALL SECONDARY ROOF
 DRAINS. CALCULATE PER FBC PLMB SEC 1106
 & 1107, TABLES 1106.2, & 1106.3, FIGURE
 1106.1.
 20) PLEASE INDICATE MATERIALS USED FOR
 ALL PLUMBING SYSTEMS.
 21) PLEASE SHOW BACKFLOWS REQUIRED FOR
 MAKE UP WATER TO COOLING TOWERS, SWIMM-
 ING POOL, & IRRIGATION. PLEASE INDICATE
 MANUFACTURE AND MODEL NUMBER, AND LOCAT-
 ION OF EACH.
 22) SEPARATE PLANS AND PERMIT REQUIRED
 FOR POOL, & POOL EQUIPMENT ROOM. PLEASE
 ROUTE PLANS TO PALM BEACH HEALTH UNIT
 DIVISION OF ENVIRONMENTAL HEALTH 901
 EVERNIA STREET, WPB FL 33401 (561) 355-
 3018.
 23) PLEASE SUBMIT DETAILS FOR SAUNA AND
 STEAM ROOMS
 24) PLEASE SUBMIT WATER HEATER DETAILS.
 PROVIDE INFORMATION FOR SEC 504.7.1, THE
 DISCHARGE PIPE SHALL NOT HAVE ANY TRAPP-
 ED SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN THE
 SAME ROOM AS HEATER. SUBMIT INFO FOR
 THERMAL EXPANSION CONTROL, 607.3
 25) SHT A8.22 PLEASE SHOW CLEAR FLOOR
 SPACE FOR URNAL. (30"X48" MINIMUM)
 26) SHTS A8.33/A8.34 UNIT Q, FIREPLACE
 PLEASE SUBMIT DETAILS. SHOW EXHAUST DUCT
 IS THIS A GAS FIREPLACE?
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 4 Status F Date 2005-06-28 Cont ID  
Sent By aaponte Date 2005-06-28 Time 10:23 Rev Time 0.00
Received By aaponte Date 2005-06-28 Time 10:23 Sent To  
Notes
2005-06-28 00:00:00PLEASE ADDRESS COMMENTS ON PREVIOUS
 REVIEW.

Review Stop Z ZONING
Rev No 3 Status F Date 2005-04-19 Cont ID  
Sent By aaponte Date 2005-04-19 Time 13:44 Rev Time 0.00
Received By aaponte Date 2005-04-19 Time 13:43 Sent To  
Notes
2005-04-19 00:00:001. PLEASE PROVIDE A TABLE INDICATING THE
 TOTAL NUMBER OF PARKING SPACES ASSIGNED
 TO RESIDENTIAL UNITS AND THE TOTAL
 NUMBER OF PARKING SPACES ASSIGNED TO
 LIVE/WORK TYPE UNITS.
 2. PLEASE INDICATE LOCATION OR SPACE
 NUMBER OF THE PARKING SPACES ASSIGNED TO
 THE LIVE/WORK TYPE UNITS.
 3. PLEASE ADJUST THE HANDICAP PARKING
 SPACES TO MEET ADA AND CITY
 REQUIREMENTS.

Review Stop Z ZONING
Rev No 2 Status P Date 2003-07-25 Cont ID  
Sent By mmclean Date 2003-07-25 Time 08:51 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2003-07-25 00:00:007/25/03 OK PER ANGELLA VANN MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-06-06 Cont ID  
Sent By sgraham Date 2003-03-05 Time 09:44 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
2003-06-06 00:00:00DENIED, MEETING WITH DEVELOPER NEXT
 WEEK 6-6-03
2003-03-05 00:00:001. A VARIANCE FROMARTICLE VI SECTION
 33-47(A)(4) WAS GRANTED BY THE DAC ON
 JULY 11, 2001, HOWEVER, SINCE THE
 SETBACK FACING OLIVE AVE HAS CHANGED
 FROM THE APPROVED AMOUNT, IT REQUIRES
 ANOTHER HEARING. CONTACT ANTHEA
 GIANNIOTES AT 659-8031.
 2. FIRST FLOOR EXCEEDS MAX FLOOR TO
 FLOOR HGT REQUIREMENTS AS ART.VI-33-47
 (A)(4)
 3. PLEASE SUBMIT ROOF PLAN WITH PERCENT-
 AGE CALCULATIONS FOR COVERED AREAS AND
 LANDSCAPE AREAS. PLEASE LABEL CLEARLY
 WHICH SPACES WILL BE CLIMATE CONTROLLED
 AND WHICH SPPACES WILL NOT BE CLIMATE
 CONTROLLED.HVAC IS ONLY PERMITTED IN
 RESTROOMS,SAUNAS,AND STEAM RMS. ART.
 VISECTION33-47(A)(5).
 4. PARKING REQUIREMENTS HAS BEEN MET:
 LIVE-WORK UNITS REQUIRE 2.
 5. SUBMIT LANDSCAPE PLAN WITH IRRIGATION
 PLAN FOR PLANTING IN THE CITY ROW.
 MAINT WILL BE CITY PLAZA RESPONSIBILITY.
 APPLICABLE CODES SECTIONS
 SEE ATTACHMENTS