Plan Review Details - Permit 02040429
Plan Review Stops For Permit 02040429
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-01 Cont ID  
Sent By dpalmer Date 2002-05-01 Time 07:53 Rev Time 0.00
Received By dpalmer Date 2002-05-01 Time 07:53 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-01 Cont ID  
Sent By dpalmer Date 2002-04-19 Time 12:38 Rev Time 0.00
Received By dpalmer Date 2002-04-19 Time 12:26 Sent To B
Notes
2002-04-19 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT CODES FROM THE
 96 NEC ARE STILL BEING REFERENCED ON
 PLANS. PLEASE NOTE THAT THESE ITEMS
 HAVE BEEN REDLINED FOR SOMETIME NOW AND
 NEED TO BE CORRECTED AND CORRELATE WITH
 THE 99 NEC.
  
 2))NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 3 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 PLEASE NOTE MISPRINT FOR AIC RATING,
 SHOWN AS 22.00 JUST A NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICLA PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-11-25 Cont ID  
Sent By pkrauss Date 2002-11-25 Time 12:15 Rev Time 0.35
Received By pkrauss Date 2002-11-25 Time 11:41 Sent To  
Notes
2002-11-25 00:00:00MECH REV PERMIT 02040446
 PLAN INDICATES A 4 TON SYSTEM - PROVIDE
 REVISED ENERGY & MANUAL J CALCS TO
 COINCIDE WITH PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-30 Cont ID  
Sent By hmoser Date 2002-05-30 Time 17:02 Rev Time 0.33
Received By hmoser Date 2002-05-30 Time 17:02 Sent To  
Notes
2002-05-30 00:00:00PASS/PRIVISO
 1) VERIFY TYPE OF VENTILATION USED FOR
 FRESH AIR 402 NATURAL OR 403
 MECHANICAL
 2) NEED CALCULATION FOR TYPE OF
 VENTILATION USED
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT 8390

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-16 Cont ID  
Sent By hmoser Date 2002-04-16 Time 20:00 Rev Time 0.50
Received By hmoser Date 2002-04-16 Time 19:59 Sent To  
Notes
2002-04-16 00:00:00PLSN DENIED
 CFM.IN LIVINGROOM 200 OR 220
 SIZE OF FLEX IN RISER FAMILYROOM ARIA
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-13 Cont ID  
Sent By jleech Date 2002-04-13 Time 13:47 Rev Time 0.33
Received By jleech Date 2002-04-13 Time 13:47 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-05-13 Cont ID  
Sent By lhatten Date 2002-05-13 Time 18:44 Rev Time 2.50
Received By lhatten Date 2002-05-12 Time 18:44 Sent To  
Notes
2002-05-13 00:00:00REVIEW & STAMPED PLANS 05/12/2002
 CALC. FEES & PRINT CARDS 05/13/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-09 Cont ID  
Sent By sgraham Date 2002-04-09 Time 11:48 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***