Plan Review Details - Permit 02040429
Plan Review Stops For Permit 02040429 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-05-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-05-01 |
Time |
07:53 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-05-01 |
Time |
07:53 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-05-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-04-19 |
Time |
12:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-04-19 |
Time |
12:26 |
Sent To |
B |
|
Notes |
2002-04-19 00:00:00 | ************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT CODES FROM THE | | 96 NEC ARE STILL BEING REFERENCED ON | | PLANS. PLEASE NOTE THAT THESE ITEMS | | HAVE BEEN REDLINED FOR SOMETIME NOW AND | | NEED TO BE CORRECTED AND CORRELATE WITH | | THE 99 NEC. | | | | 2))NOTE: PLEASE CLARIFY EQUIPMENT | | GROUNDING METHOD BETWEEN FIRST MEANS | | OF DISCONNECT AND PANELS. PLEASE SIZE | | CONDUCTORS PER 250-122. | | | | 3 )NOTE: PLEASE LIST THE REQ`D ARC | | FAULT PROECTED CIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | PLEASE NOTE MISPRINT FOR AIC RATING, | | SHOWN AS 22.00 JUST A NOTE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICLA PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2002-11-25 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-11-25 |
Time |
12:15 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-11-25 |
Time |
11:41 |
Sent To |
|
|
Notes |
2002-11-25 00:00:00 | MECH REV PERMIT 02040446 | | PLAN INDICATES A 4 TON SYSTEM - PROVIDE | | REVISED ENERGY & MANUAL J CALCS TO | | COINCIDE WITH PLAN. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-05-30 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-05-30 |
Time |
17:02 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2002-05-30 |
Time |
17:02 |
Sent To |
|
|
Notes |
2002-05-30 00:00:00 | PASS/PRIVISO | | 1) VERIFY TYPE OF VENTILATION USED FOR | | FRESH AIR 402 NATURAL OR 403 | | MECHANICAL | | 2) NEED CALCULATION FOR TYPE OF | | VENTILATION USED | | PLAN REVIEW BY HAROLD MOSER | | (561)659-8096 EXT 8390 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-04-16 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-04-16 |
Time |
20:00 |
Rev Time |
0.50 |
Received By |
hmoser |
Date |
2002-04-16 |
Time |
19:59 |
Sent To |
|
|
Notes |
2002-04-16 00:00:00 | PLSN DENIED | | CFM.IN LIVINGROOM 200 OR 220 | | SIZE OF FLEX IN RISER FAMILYROOM ARIA | | PLAN REVIEW BY HAROLD MOSER | | [561]659-8096 EXT 8390 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-04-13 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-04-13 |
Time |
13:47 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2002-04-13 |
Time |
13:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2002-05-13 |
|
|
Cont ID |
|
Sent By |
lhatten |
Date |
2002-05-13 |
Time |
18:44 |
Rev Time |
2.50 |
Received By |
lhatten |
Date |
2002-05-12 |
Time |
18:44 |
Sent To |
|
|
Notes |
2002-05-13 00:00:00 | REVIEW & STAMPED PLANS 05/12/2002 | | CALC. FEES & PRINT CARDS 05/13/2002 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-04-09 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-04-09 |
Time |
11:48 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|