Plan Review Details - Permit 02040426
Plan Review Stops For Permit 02040426
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-01 Cont ID  
Sent By dpalmer Date 2002-05-01 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2002-05-01 Time 07:48 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-19 Cont ID  
Sent By dpalmer Date 2002-04-19 Time 11:58 Rev Time 0.00
Received By dpalmer Date 2002-04-19 Time 11:58 Sent To B
Notes
2002-04-19 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT THE CODES
 REFERENCED ARE STILL FROM THE "96" NEC.
 PLEASE NOTE THE WE HAVE BEEN REDLINING
 THE 99 ARTS FOR SOMETIME. PLEASE MAKE
 CORRECTIONS TO CORRELATE WITH THE 99 NEC
  
 2)NOTE: PLEASE NOTE AIC RATING SHOWN AS
 22.00. PLEASE NOTE THIS MUST BE A
 MISPRINT.
  
 3))NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
  
 4))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-03 Cont ID  
Sent By hmoser Date 2002-12-03 Time 19:11 Rev Time 0.50
Received By hmoser Date 2002-12-03 Time 19:11 Sent To  
Notes
2002-12-03 00:00:00NEED ENERGY CALCS.&MANUAL (J)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-16 Cont ID  
Sent By hmoser Date 2002-04-16 Time 20:28 Rev Time 0.33
Received By hmoser Date 2002-04-16 Time 20:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-13 Cont ID  
Sent By jleech Date 2002-04-13 Time 13:48 Rev Time 0.33
Received By jleech Date 2002-04-13 Time 13:48 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-05-13 Cont ID  
Sent By lhatten Date 2002-05-13 Time 18:20 Rev Time 2.50
Received By lhatten Date 2002-05-10 Time 18:19 Sent To  
Notes
2002-05-13 00:00:00REVIEW & STAMPED PLANS 05/10/2002
 CALC. FEES & PRINT CARDS 05/13/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-09 Cont ID  
Sent By sgraham Date 2002-04-09 Time 11:50 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***