Plan Review Details - Permit 02040398
Plan Review Stops For Permit 02040398
Review Stop P PLUMBING
Rev No 2 Status P Date 2002-04-17 Cont ID  
Sent By kstevens Date 2002-04-17 Time 14:26 Rev Time 0.00
Received By kstevens Date 2002-04-17 Time 14:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-12 Cont ID  
Sent By kstevens Date 2002-04-12 Time 09:15 Rev Time 0.00
Received By kstevens Date 2002-04-12 Time 09:15 Sent To  
Notes
2002-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-FUEL
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 GAS CODE SECS. 402.1 THRU
 402.5.2 & TABLES 402(1) THRU 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A.
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SEC 304.1 THRU 304..7
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE APPENDIX A.
 IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC 301.
 9) SINCE A SIGNED AND SEALED RISER DIA-
 GRAM WAS SUBMITTED ON A REVISION, THE
 ISOMETRIC REFERENCED IN REVIEW COMMENT
 #1 THIS REVIEW SHALL BE SIGNED AND SEAL-
 ED BY ENGINEER OF RECORD.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved