2002-05-13 00:00:00 | CHECKLIST: |
| 1-DESIGN CRITERIA: |
| FBC 2001 SEC. 1606.2 SHALL NOT BE USED |
| TO DESIGN A "PARTIALLY ENCLOSED" BLDG. |
| SEE SEC. 1606.1.4.1 FBC 2001. |
| 2-TWO HR OVERHANG DETAIL FOR WD ASSEMBLY |
| USING CALCULATED RATINGS IS NOT |
| PERMITTED. SEE SEC. 709.6.1.2 FBC 2001 |
| 3-UPDATE ALL PLANS AND SPECIFICATIONS. |
| SEE COMMENTS ON PLANS AND RETURN |
| REVIEWED SET TO EXPEDITE REVIEW. |
| 4-REVISE STRUCTURAL BUCK DETAILS TO |
| SATISFY THE REQUIREMENTS OF SECTION |
| 1707.4.4 FBC 2001. |
| 5-PROVIDE COMPLETE SPECIFICATIONS FOR |
| CEILING INSTALLATION AT FRONT AND BACK |
| PORCHES. SEE ASTM C-1063 FOR SPECIFIC |
| FASTENERS AND SPACING. & ASTM C-926. |
| SECTION 2504.2 FBC 2001. |
| 6-CLARIFY FASTENING OF GARAGE DOOR BUCK. |
| SEE DRAWING 1 ON DS-1 AND DET. 4 ON S4 |
| 7-REVISE ENERGY CALCULATIONS: |
| A)REVISE UNDER ATTIC AREA. SEE SECTION |
| 604.1.A.1 OF CHAPTER 13 OF FBC 2001. |
| B)THIS IS MULTIFAMILY BLDG NOT SINGLE |
| FAMILY. SEE DEFINITIONS ON CHAPTER |
| 13 OF FBC 2001.SPECIFY # OF UNITS. |
| 8-PROVIDE PRODUCT APPROVAL FOR: |
| A)ROOF TILE REPORT SUBMITTED WAS DELETED |
| FROM SBCCI. NEED UPDATED ONE. |
| 9-CONCRETE SLAB NOTES: ADD SPECIFICATION |
| FOR SUPPORTS AS REQUIRED BY SECTION |
| 1909.3 FBC 2001. |
| 10-UPDATE ALL CONNECTORS SPECIFIED |
| THROUGHOUT DRAWINGS. "HUGHES" AND |
| "SEMCO" ARE OUT OF BUSINESS. |
| 11-CLARIFY SPECIFICATIONS FOR SOIL |
| BEARING CAPACITY IS IT 2000PSF OR |
| 2500PSF. SEE SHEET S-11 AND TITLE |
| SHEET. REVISE AS REQUIRED. |
| |
| |
| NOTES: |
| -THESE COMMENTS APPLY TO PERMIT #S |
| 02040386, 02040391, 02040393 & 02040395 |
| -DRAWINGS AND PERMITS TO BE FILED UNDER |
| PERMIT #02040386. |