Plan Review Details - Permit 02040377
Plan Review Stops For Permit 02040377
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-24 Cont ID  
Sent By jwitmer Date 2002-06-24 Time 19:05 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-22 Cont ID  
Sent By jwitmer Date 2002-04-22 Time 15:17 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-22 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02040377
 3222 S DIXIE
 CONT: ALL CLAIMS INSURANCE
 REPAIR
 TEL:(954) 456-6060
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)- PLANS TO COMPLY TO THE 2001 FL BLD
 CODE.
 2)- FL BLD CODE CHAP 13 SHOW COMPLIANCE
 WITH ENERGY CODE, PRESCRIPTIVE REQUIRE-
 MENT 400.3C/ W/MANUAL J.
 3)- FL BLD CODE 104.2.1.2 ADDITIONAL
 INFORMATION REQUIRED, PLANS INDICATE THE
 USE OF HUGH STRAPPING, THEY HAVE NOT
 BEEN IN BUSINESS FOR OVER 2 YEARS.PRO-
 VIDE THE CURRENT INFORMATION AS OF
 WHICH SUPPLIER YOU ARE USING.
 4)- FL BLD CODE 704.3.1 INDICATE CODE
 COMPLIANCE, PROVIDE INFO FOR 1 HR TENANT
 SEPERATION UL # OR GYPSUM ASSOC #.
 5)- TYPES OF OCCUPANCIES ON EITHER
 SIDE OF THIS UNIT?
 6)- FL BLD CODE 11-4.1.6(2) ACCESSIBIL-
 ITY CODE: ALTERATIONS TO AN AREA CONTAIN
 ING A PRIMARY FUNCTION. ALTERATIONS MADE
 TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL
 TO ALTERED AREAS SHALL BE DEEMED DISPRO-
 PORTIONATE TO THE OVERALL ALTERATION
 WHEN THE COST EXCEEDS 20%.
 A- ACCESSIBLE ENTRANCE
 B- ACCESSIBLE ROUTE
 C- AT LEAST 1 ACCESSIBLE RESTROOM FOR
 EACH SEX OR A SINGLE UNISEX RESTROOM.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-16 Cont ID  
Sent By dpalmer Date 2002-04-16 Time 08:10 Rev Time 0.00
Received By dpalmer Date 2002-04-16 Time 08:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-04-11 Cont ID  
Sent By mcarsill Date 2002-04-11 Time 09:14 Rev Time 0.00
Received By mcarsill Date 2002-04-11 Time 09:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-26 Cont ID  
Sent By pkrauss Date 2002-04-26 Time 13:23 Rev Time 0.30
Received By pkrauss Date 2002-04-26 Time 13:22 Sent To  
Notes
2002-04-26 00:00:00NEW RTU & DUCTWORK DUE TO FIRE
 DAMAGE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-18 Cont ID  
Sent By jleech Date 2002-06-18 Time 17:15 Rev Time 0.50
Received By jleech Date 2002-06-18 Time 17:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-29 Cont ID  
Sent By jleech Date 2002-04-29 Time 18:06 Rev Time 0.75
Received By jleech Date 2002-04-29 Time 18:06 Sent To  
Notes
2002-04-29 00:00:00DENIED;
 TOILET ROOM SHALL COMPLY WITH 2001 FACBC
 SEC.11.4.22. SHOW CLEAR FLOOR SPACE FOR
 FIXTURES AND TURNING SPACE ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369