2002-04-12 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| |
| 1) COMPLY WITH FBC-2001 SEC 424.2 |
| PRIVATE SWIMMING POOLS. |
| 2) FBC-2001 SEC 424.2.6.1 ENGINEERING |
| DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| ANSI/NSPI-5. CHANGE NOTE NOT READ AS |
| ABOVE |
| 3) |
| FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE |
| WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) |
| 4) |
| FBC-2001 SEC 424.2.6.6.3 (1,2,3) ENTRAP- |
| MENT AVOIDANCE. (DETAIL) |
| 5) |
| FBC-2001 SEC 424.2.6.6.5 WHERE PROVIDED, |
| THE VACUUM OR PRESSURE CLEANER FITTING |
| SHALL BE LOCATED AT LEAST 6" AND NOT |
| GREATER THAN 12" BELOW THE MINIMUM OPER- |
| ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| THE SKIMMER. |
| 6) |
| FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL |
| ORD. #2853-95, BACKFLOW REQUIRED ON |
| WATER SERVICE. (ADD TO NOTES) |
| 7) |
| FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. |
| PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| TEST SHALL BE APPROVED FOR PVC PIPE AND |
| FITTINGS. (ADD TO NOTES) |
| 8) |
| FBC-2001 SEC 424.2.13.2JOINTS AND CON- |
| NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| NOTES) |
| |
| REVIEW BY KEN STEVENS |