Plan Review Details - Permit 02040100
Plan Review Stops For Permit 02040100
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-01 Cont ID  
Sent By dpalmer Date 2002-05-01 Time 11:05 Rev Time 0.00
Received By dpalmer Date 2002-05-01 Time 10:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-25 Cont ID  
Sent By dpalmer Date 2002-04-25 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2002-04-25 Time 13:51 Sent To P
Notes
2002-04-25 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT PLANS STILL
 SHOW NEC ARTS FROM 96 NEC. PLEASE
 CORRELATE #`S WITH 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT FOR AIC
 RATING OF MAIN.22.00? INSTEAD OF 22,000.
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS PRE 210-12.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-03 Cont ID  
Sent By hmoser Date 2002-12-03 Time 18:44 Rev Time 0.50
Received By hmoser Date 2002-12-03 Time 18:44 Sent To  
Notes
2002-12-03 00:00:00PASS/PRIVISO
 NEED ENERGY CALCS.& MANUAL (J)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-24 Cont ID  
Sent By hmoser Date 2002-04-24 Time 18:55 Rev Time 0.50
Received By hmoser Date 2002-04-24 Time 18:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-27 Cont ID  
Sent By dpalmer Date 2002-04-25 Time 13:52 Rev Time 0.33
Received By jleech Date 2002-04-27 Time 11:16 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-05-13 Cont ID  
Sent By lhatten Date 2002-05-13 Time 17:40 Rev Time 2.50
Received By lhatten Date 2002-05-12 Time 17:39 Sent To  
Notes
2002-05-13 00:00:00REVIEW & STAMPED PLANS 05/12/2002
 CALC. FEES & PRINT CARDS 05/13/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-08 Cont ID  
Sent By sgraham Date 2002-04-08 Time 07:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***