Plan Review Details - Permit 02031922
Plan Review Stops For Permit 02031922
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-02 Cont ID  
Sent By mcarsill Date 2002-05-02 Time 15:02 Rev Time 0.00
Received By mcarsill Date 2002-05-02 Time 15:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-02 Cont ID  
Sent By mcarsill Date 2002-04-02 Time 12:41 Rev Time 0.00
Received By mcarsill Date 2002-04-02 Time 12:41 Sent To  
Notes
2002-04-02 00:00:00A) PERMIT APPLICATION INDICATES A VALUE
 OF 1,000 DOLLARS WHICH APPEARS TO BE
 TOO LOW FOR THE EQUIPMENT AND AMOUNT OF
 WORK. PLEASE PROVIDE COPY OF CONTRACT.
 B) FIRE ALARM NOTES SECTION INDICATES
 THAT DUCT DETECTORS WILL BE SUPERVISORY
 ONLY. DUCT DETECTORS ARE TO ACTIVATE
 THE FIRE ALARM SYSTEM.
 C) PLEASE INDICATE MONITORING COMPANY
 WHO WILL BE RECEIVING SIGNALS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910