Plan Review Details - Permit 02031841
Plan Review Stops For Permit 02031841
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-03 Cont ID  
Sent By btrobaug Date 2002-04-03 Time 17:23 Rev Time 0.00
Received By btrobaug Date 2002-04-03 Time 17:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-01 Cont ID  
Sent By btrobaug Date 2002-04-01 Time 13:09 Rev Time 0.00
Received By btrobaug Date 2002-04-01 Time 13:07 Sent To  
Notes
2002-04-01 00:00:00****************** UNSAT ***************
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392