Plan Review Details - Permit 02031652
Plan Review Stops For Permit 02031652
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-26 Cont ID  
Sent By hpiskura Date 2002-04-26 Time 14:25 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-26 00:00:00THE GENERAL NOTES ON SHEET A1 OF THE
 PLANS DECLARE TYPE V UNPROTECTED
 CONSTRUCTION AND A NFPA 13D FIRE
 SPRINKLER SYSTEM.FOOTNOTE (D) TO
 TABLE500 PROHIBITS A 13D OR 13R SYSTEM
 FOR HEIGHT MODIFICATIONS.
  
 THE BUILDINGS MUST BE EITHER 1 HOUR
 PROTECTED WITH A 13D SYSTEM OR A FULL
 13 SYSTEM TO BE THREE STORIES.PLEASE
 REVISE AS NECESSARY.
  
 SECTIONS ON SHEET A6 SHOW AN EXISTING
 RETAINING WALL.THE PROPOSED PROBERTY
 LINES SHOW THE RETAINING WALL FOOTING
 TO BE ENCROACHING ON THE NEIGHBORING
 PROPERTY.PROVIDE A METHOD TO RESOLVE
 OWNERHIP AND RESPONSIBILITY.
  
 SAME.PROVIDE AN ENGINEERING ANALYSIS
 OF THE SUITABILITY OF THE EXISTING
 WALL TO ASSUME THE ADDED FOUNDATION
 LOADS OF THE BUILDINGS.INCLUDE THE
 WATER PROOFING AND/OR DAMP PROOFING
 REQUIRED BY SBC 1814.1
  
 BUILDINGS NUMBERED 1,4,6, AND 7 HAVE
 EXTERIOR WALL OPENINGS EXCEEDING THE
 40% ALLOWED BY SBC TABLE 600 ON UNITS
 LABELED "E".PLEASE REVISE AS
 NECESSARY.
  
 WITH AN ASSUMED PROPERTY, THERE IS NONE
 INDICATED ON THE PLANS, BETWEEN
 BUILDINGS PAIRED, 1&2 2&3 3&4 ETC. THE
 ALLOWABLE EXTERIOR WALL OPENINGS FOR
 TABLE 600 ARE EXCEEDED.PLEASE REVISE
 AS NECESSARY.
  
 PLEASE PROVIDE THE SOIL REPORTS FOR
 THESE BUILDINGS.SEE SBC 104.2.
  
 PROVIDE THE NOTICE OF ACCEPTANCE AND
 TEST REPORTS FOR THE WINDOWS, DOORS AND
 ROOF COVERING.
  
 SHOW THE SOIL TERMITE TREATMENT IN
 ACCORDANCE WITH SBC 2304 AS AMENDED BY
 THE CITY.
  
 SHEET S2 CITES ASCE 7-98, THE 1997 SBC
 INVOKES ASCE 7-95.PLEASE REVISE
 ACCORDINGLY AND DEMONSTRATE COMPLIANCE
 WITH 7-95.ALTERNATIVELY, REVISE THE
 BUILSDINGS TO COMPLY WITH THE 2001 FBC.
  
 THE EMERGENCY EGRESS FOR BUILDINGS 8
 AND12 INTO THE ENCLOSED COURTYARD DOES
 NOT MEET THE RESCUE REQUIREMENTS OF SBC
 1005.4.PLEASE REVISE AS NECESSARY.
  
 SEPARATE SURVEYS ARE REQUIRED FOR EACH
 TOWNHOUSE UNIT.
  
 GIVEN THE SIZE AND SCOPE OF THIS PROJECT
 A RESIDENT INSPECTOR WILL BE REQUIRED.
 CONTACT DON NEELY AT 561-659-8096 EXT
 8333 FOR MORE INFORMATION.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY, THE PERMIT PLANS
 STAMPEDBY THAT OFFICE, AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-18 Cont ID  
Sent By dpalmer Date 2002-04-18 Time 15:44 Rev Time 0.00
Received By dpalmer Date 2002-04-18 Time 15:44 Sent To  
Notes
2002-04-18 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT A LOCK OUT
 DEVICE SHOWN FOR WATER HEATERS IS NOT
 CONSIDERED PERMANENT. PLEASE NOTE THAT
 ANY WATER HEATER NOT WITHIN SIGHT REQ`S
 A MEANS OF DISCONNECT.
  
 2)NOTE: PLEASE NOTE MISSING SD`S INSIDE
 BEDRROMS. NFPA-72 2-2.1.1.1.
  
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 4)) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-05-02 Cont ID  
Sent By mcarsill Date 2002-05-02 Time 10:56 Rev Time 0.00
Received By mcarsill Date 2002-05-02 Time 10:56 Sent To  
Notes
2002-05-02 00:00:001) SITE PLAN DOES NOT INDICATE FIRE
 HYDRANT LOCATIONS. PLEASE INDICATE FIRE
 HYDRANT LOCATIONS ON SITE PLAN. WET
 FIRE HYDRANTS ARE REQUIRED PRIOR TO,
 DURING AND AFTER CONSTRUCTION.
 2) BUILDING ADDRESSES REQUIRED ON THE
 TOWNHOUSES. NUMBERS ARE TO BE AT LEAST
 3" HIGH.
 3) ELECTRIC POWERED SMOKE DETECTORS
 SHALL BE INSTALLED OUTSIDE EVERY
 SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS AND ALL LEVELS OF THE
 DWELLING.
 4) STORAGE UNDER STAIRS NOT ALLOWED. IF
 ALLOWED, STORAGE AREA TO BE AT LEAST
 ONE HOUR FIRE RATED.
 5) NFPA 1 DEFINES "THAT WHEREVER THERE
 ARE THREE OR MORE LIVING UNITS IN A
 BUILDING, THE BUILDING IS CONSIDERED AN
 APARTMENT BUILDING. THE FIRE SPRINKLER
 SYSTEMS IN THESE UNITS MUST BE 13R
 TYPES.
 6) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR THE BALCONY RAILINGS.
 7) NO FIRE DEPARTMENT CONNECTION COULD
 BE LOCATED FOR BUILDING 6.
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEMS.
 9) PLEASE EXPLAIN VOID UNDER STAIRS.
 10) PLEASE EXPLAIN 10" TREADS. NEW
 STAIRS ARE TO HAVE 11" TREADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-03 Cont ID  
Sent By pkrauss Date 2002-04-22 Time 09:22 Rev Time 5.00
Received By pkrauss Date 2002-04-18 Time 12:34 Sent To  
Notes
2002-05-03 00:00:00PROVISO:MECHANICAL PERMIT 02031769
  
 AHU DETAIL PLAN SHEET AC-7
 PROVIDE OVERFLOW PROTECTION AS PER
 1997 SMC 304.8.6.1.
 - AUXILIARY DRAIN PAN
 - DRAIN LINE TERMINATING AT A
 CONSPICUOUS POINT OR FLOAT SWITCH.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-20 Cont ID  
Sent By kstevens Date 2002-04-20 Time 12:37 Rev Time 0.00
Received By kstevens Date 2002-04-20 Time 12:37 Sent To  
Notes
2002-04-20 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT P-1 WATER HEATER DETAIL, 1" PAN
 DRAIN REQUIRED.
 2) SHT P-2 DRAIN PAN DETAIL, 1" PAN
 DRAIN REQUIRED.
 3) SHT P-3 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE A QUICK FIX AND DO NOT WORK
 BUT IF USED THEY SHALL BE ACCESSIBLE AND
 RECHARGEABLE PER SEC 607.8.3. (SEE ATT-
 ACHED SHEETS FOR APPROVED AIR CHAMBER)
 APPROVED WATER HAMMER ARRESTORS DO NOT
 REQUIRE ACCESS AND DO NOT REQUIRE SERV-
 ICE AND IF USED THEY SHALL BE LOCATED IN
 AN "EFFECTIVE RANGE" CLOSE TO FIXTURE
 NOT AT TOP OF DROP. THIS IS TYPICAL ON
 SHTS P-4, P-5, & P-6 ALSO.
 4) SHT P-4 SANITARY RISER DIAGRAM, 3RD
 FLOOR BATHROOM SHALL BE TAKEN OFF STACK
 BELOW KITCHEN SINK. THIS IS TYPICAL ON
 SHT P-5, SHT P-6 AND P-7 AT WASH MACHINE
 5) SHT P-4 SANITARY RISER DIAGRAM,
 PIPING BELOW 2ND FLOOR CONFUSING. SEEMS
 THE 3" RUNS INTO A TEE WITH FLOW COMMING
 FROM TWO DIRECTIONS. THEN WHEN IT SHOULD
 TURN TO THE WASH MACHINE IT TEES AGAIN.
 WHERE DOES THE PIPE TO THE RIGHT OF THE
 TEE GO??
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-04 Cont ID  
Sent By sgraham Date 2002-04-04 Time 12:05 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***