Plan Review Details - Permit 02031551
Plan Review Stops For Permit 02031551
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-05-29 Cont ID  
Sent By jwitmer Date 2002-05-29 Time 14:23 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-05-16 Cont ID  
Sent By jwitmer Date 2002-05-16 Time 12:48 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2002-05-16 00:00:00BUIDING PLAN REVIEW
 PERMIT# 02031551
 525 29TH ST
 CONT: INTEGRITY BUILDING CONTRACTOR
 TEL: 841-1666
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR: MULLION/ WINDOWS
 2) SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE DESIGN
 PROFESSIONAL OF RECORD.
 NORANDEX REPORT REQUIRES SITE SPECIF-
 IC ENGINEERING, NOT A DADE COUNTY OR
 SBCCI REPORT.(MULLION REPORT).
 3)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
 4)2304.3.4 WOOD JOIST SHALL HAVE 18"
 CLEARENCE FROM THE BOTTOM OF JOIST TO
 EARTH OR ELSE BE PRESSURE TREATED WOOD.
 5) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 6) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412
  
 3RD REVIEW FEES ARE 10% OF PERMIT FEE.
 4TH REVIEW FL.S.S. 553.80(2)B THE LOCAL
 GOVERNMENT SHALL IMPOSE EACH TIME AFTER
 THE THIRD SUCH REVIEW THE PLANS ARE
 REJECTED FOR THAT SAME VIOLATION, A FEE
 OF FOUR TIMES THE AMOUNT OF THE PROPOR-
 TION OF THE PERMIT FEE ATTRIBUTED TO
 PLAN REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-25 Cont ID  
Sent By kstevens Date 2002-04-12 Time 19:59 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-26 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02031551
 525 29TH ST
 CONT: INTEGGRITY BUILD CONT
 TEL: 841-1666
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 METAL EXTERIOR SWING DOOR
 MULLION
 TRANSOM
 WINDOWS
  
 3)1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 4)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 5)1804.6.2.3 CRAWL SPACE ACCESS UNDER
 BUILDINGS WITHOUT ABSSEMENTS SHALL PRO-
 VIDE ONE OPENING NOT LESS THAN 18X24".
 EXISTING ACCESS WILL BE COVERED BY NEW
 STEM WALL ADDITION.
  
 6)-2304.3.4 WOOD JOIST SHALL HAVE 18"
 CLEARENCE FROM THE BOTTOM OF JOIST TO
 EARTH OR ELSE BE PRESSURE TREATED WOOD.
  
 7)- 1007.5.1 STAIRS WITH A MINIMUM OF
 4 RISERS SHALL BE EQUIPPED WITH HAND-
 RAILS LOCATED NO LESS THAN 34" NOR MORE
 THAN 38" ABOVE THE LEADING EDGE OF A
 TREAD.
  
 8)- 1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.
 EXCEPTION-(2) STAIRS WITHIN DWELLING
 UNITS ONLY NEED A HANDRAIL ON ONE SIDE.
  
 9) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 10)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-01 Cont ID  
Sent By btrobaug Date 2002-04-01 Time 12:27 Rev Time 0.00
Received By btrobaug Date 2002-03-29 Time 16:41 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-28 Cont ID  
Sent By pkrauss Date 2002-05-28 Time 11:05 Rev Time 0.45
Received By pkrauss Date 2002-05-28 Time 10:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-02 Cont ID  
Sent By kstevens Date 2002-05-22 Time 14:09 Rev Time 0.35
Received By pkrauss Date 2002-04-02 Time 07:43 Sent To P
Notes
2002-04-02 00:00:00 
 PLEASE PROVIDE MAKE, MODEL, & BTU OF
 EXISTING UNIT WITH RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.
  
 EXISTING HOUSE 1200 SQ FT
 ADDITION 288 SQ FT

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-22 Cont ID  
Sent By kstevens Date 2002-05-22 Time 14:09 Rev Time 0.00
Received By kstevens Date 2002-05-22 Time 14:09 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-12 Cont ID  
Sent By pkrauss Date 2002-04-26 Time 14:26 Rev Time 0.00
Received By kstevens Date 2002-04-12 Time 19:53 Sent To B
Notes
2002-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DOES NOT MEET CODE RE-
 QUIREMENTS. DRY HORIZONTAL VEN NOT APP-
 ROVED. TUB AND LAV NOT VENTED PROPERLY.
 SEC 905.3.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-29 Cont ID  
Sent By sgraham Date 2002-03-29 Time 15:01 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***