Plan Review Details - Permit 02031511
Plan Review Stops For Permit 02031511
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-02 Cont ID  
Sent By btrobaug Date 2002-04-02 Time 16:56 Rev Time 0.00
Received By btrobaug Date 2002-04-02 Time 16:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-26 Cont ID  
Sent By btrobaug Date 2002-03-26 Time 13:21 Rev Time 0.00
Received By btrobaug Date 2002-03-26 Time 10:12 Sent To  
Notes
2002-03-26 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND RESUBMIT:
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} AMPERAGE RATING ON THE "METER/MAIN"
  
 3} GROUNDING METHOD USED FOR NEW AND
 EXISTING SERVICES.MUST COMPLY WITH
 250-30.
  
 4} WHAT IS THE OCP ON THE CONDUCTORS
 REFEEDING THE HOUSE PANEL?
  
 5} INDICATE WHERE THE POOL EQUIPMENT IS
 FED FROM,SHOW WIRE SIZE,CONDUIT TYPE AND
 SIZE AND OCP.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392