Plan Review Details - Permit 02031324
Plan Review Stops For Permit 02031324
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-06-08 Cont ID  
Sent By jgomez Date 2002-06-08 Time 16:46 Rev Time 1.00
Received By jgomez Date 2002-06-08 Time 16:46 Sent To  
Notes
2002-06-08 00:00:00APPROVED WITH PROVISO: SEE COMMENTS ON
 PERMIT #02031318.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-05-15 Cont ID  
Sent By jgomez Date 2002-05-15 Time 16:18 Rev Time 1.00
Received By jgomez Date 2002-05-15 Time 16:18 Sent To  
Notes
2002-05-15 00:00:00CHECKLIST:
 SEE COMMENTS ON PERMIT #02031318.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-22 Cont ID  
Sent By jwitmer Date 2002-04-22 Time 13:29 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-22 00:00:00SAME COMMENTS AS 02031318

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-28 Cont ID  
Sent By btrobaug Date 2002-03-28 Time 13:05 Rev Time 0.00
Received By btrobaug Date 2002-03-28 Time 13:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-04-04 Cont ID  
Sent By mcarsill Date 2002-04-04 Time 11:18 Rev Time 0.00
Received By mcarsill Date 2002-04-04 Time 11:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-05-22 Cont ID  
Sent By pkrauss Date 2002-05-22 Time 13:49 Rev Time 1.00
Received By pkrauss Date 2002-05-22 Time 13:49 Sent To  
Notes
2002-05-22 00:00:00MECHANICAL PERMIT 02031344
 LTR SUBMITTED ON DRYER EXHAUST (LESS
 THAN 200 CFM)

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-05-13 Cont ID  
Sent By pkrauss Date 2002-05-13 Time 15:40 Rev Time 0.35
Received By pkrauss Date 2002-05-13 Time 15:40 Sent To  
Notes
2002-05-13 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02031344
  
 COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED.
  
 1.SEER ON ENERGY CALCS STILL DO NOT
 MATCH SEER SHOWN ON EQUIPMENT SCHEDULE.
  
 2. O.A. CALCS. SHALL PROVIDE COMPLIANCE
 WITH 402.2 (4% OF THE FLOOR AREA BEING
 VENTILATED) OR TABLE 403.3 (MECHANICAL
 VENTILATION NOT INFILTRATION)
  
 3. DRYER CFM NOT PROVIDED.
  
 4. DRYER LENGTHS IN EXCESS OF CODE
 MINIMUM OF 25' PER 504.6. SUBMIT
 SPECIFIC MANUFACTURER SPECIFICATIONS OF
 ALLOWABLE LENGTH OF DUCT.
  
 5. SECONDARY DRAIN CONSPICUOUS POINT
 SHALL NOT BE BEHIND AHU CLOSET DOOR. IF
 NO SUITABLE CONSPICUOUS LOCATION IS
 AVAILABLE, A PAN WITH A FLOAT SWITCH PER
 307.2.4 IS ACCEPTABLE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-08 Cont ID  
Sent By ndenmark Date 2002-04-08 Time 13:33 Rev Time 0.25
Received By ndenmark Date 2002-04-08 Time 13:33 Sent To  
Notes
2002-04-08 00:00:00****************DENIED******************
  
 ADDITIONAL INFORMATION REQUIRED
 1. PROVIDE CFM REQUIREMENTS FOR DRYER TO
 DETERMINE COMPLIANCE PER 2001 FBC(M)
 504.5
 2. PROVIDE OUTSIDE AIR PER FBC(M) TABLE
 403.3
 3. SEER ON EQUIPMENT SCHEDULE DOES NOT
 MATCH SEER ON ENERGY CALCS
  
 NOTE: DRYER AND BATH EXHAUST DUCTS
 SHALL NOT PENETRATE RATED PARTYWALL OR
 ADJACENT ROOF

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-13 Cont ID  
Sent By kstevens Date 2002-05-13 Time 18:37 Rev Time 0.00
Received By kstevens Date 2002-05-13 Time 18:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-21 Cont ID  
Sent By kstevens Date 2002-04-21 Time 15:02 Rev Time 0.00
Received By kstevens Date 2002-04-21 Time 15:02 Sent To  
Notes
2002-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) SEE COMMENTS FOR PERMIT #02031318
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-27 Cont ID  
Sent By sgraham Date 2002-03-27 Time 09:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***