Plan Review Stops For Permit 02031322 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-06-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2002-06-08 |
Time |
16:37 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2002-06-08 |
Time |
16:37 |
Sent To |
|
|
Notes |
2002-06-08 00:00:00 | APPROVED WITH PROVISO: | | SEE COMMENTS ON PERMIT #02031318. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-05-15 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2002-05-15 |
Time |
16:12 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2002-05-15 |
Time |
16:12 |
Sent To |
|
|
Notes |
2002-05-15 00:00:00 | CHECKLIST: SEE COMMENTS ON PERMIT | | #02031318. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-04-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-04-22 |
Time |
13:15 |
Rev Time |
1.25 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-22 00:00:00 | SAME COMMENTS AS 02031318, WRONG ADDRESS | | ON APPLICATION |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-03-28 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-03-28 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-03-28 |
Time |
13:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-04-04 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-04-04 |
Time |
11:18 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-04-04 |
Time |
11:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-22 |
Time |
13:47 |
Rev Time |
1.00 |
Received By |
pkrauss |
Date |
2002-05-22 |
Time |
13:47 |
Sent To |
|
|
Notes |
2002-05-22 00:00:00 | MECHANICAL PERMIT 02031339 | | SUBMITTED LTR ON DRYER EXHAUST (LESS | | THAN 200 CFM) |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2002-05-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-13 |
Time |
15:34 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-05-13 |
Time |
15:33 |
Sent To |
|
|
Notes |
2002-05-13 00:00:00 | MECHANICAL PERMIT 02031339 | | | | SEER ON ENERGY CALCS OKAY. | | | | OTHER COMMENTS NOT ADDRESSED FROM | | PREVIOUS REVIEW. | | | | 1. O.A. CALCS. SHALL PROVIDE COMPLIANCE | | WITH 402.2 (4% OF THE FLOOR AREA BEING | | VENTILATED) OR TABLE 403.3 (MECHANICAL | | VENTILATION NOT INFILTRATION) | | | | 2. DRYER CFM NOT PROVIDED. | | | | 3. DRYER LENGTHS IN EXCESS OF CODE | | MINIMUM OF 25' PER 504.6. SUBMIT | | SPECIFIC MANUFACTURER SPECIFICATIONS OF | | ALLOWABLE LENGTH OF DUCT. | | | | 4. SECONDARY DRAIN CONSPICUOUS POINT | | SHALL NOT BE BEHIND AHU CLOSET DOOR. IF | | NO SUITABLE CONSPICUOUS LOCATION IS | | AVAILABLE, A PAN WITH A FLOAT SWITCH PER | | 307.2.4 IS ACCEPTABLE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-04-08 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-04-08 |
Time |
13:30 |
Rev Time |
0.25 |
Received By |
ndenmark |
Date |
2002-04-08 |
Time |
13:30 |
Sent To |
|
|
Notes |
2002-04-08 00:00:00 | ***************DENIED******************* | | | | ADDITIONAL INFORATION REQUIRED | | 1. PROVIDE CFM REQUIREMENTS FOR DRYER TO | | DETERMINE COMPLIANCE PER 2001 FBC(M) | | 403.3 | | 2. PROVIDE OUTSIDE AIR PER FBC(M) TABLE | | 403.3 | | 3. SEER ON EQUIPMENT SCHEDULE DOES NOT | | MATCH SEER ON ENERGY CALCS | | | | NOTE: DRYER AND BATH EXHAUST DUCT SHALL | | NOT PENETRATE RATED PARTYWALL OR | | ADJACENT ROOF |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-05-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-13 |
Time |
18:36 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-13 |
Time |
18:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-04-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-21 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-21 |
Time |
14:59 |
Sent To |
|
|
Notes |
2002-04-21 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FHA AMEND-98 DESIGN MANUAL | | | | 1) SEE COMMENTS FOR PERMIT #02031318 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-03-27 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-03-27 |
Time |
09:16 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|