Plan Review Stops For Permit 02031320 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-06-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2002-06-08 |
Time |
16:32 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2002-06-08 |
Time |
16:32 |
Sent To |
|
|
Notes |
2002-06-08 00:00:00 | APPROVED WITH PROVISO. SEE COMMENTS ON | | PERMIT #02031318. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-05-15 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2002-05-15 |
Time |
15:59 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2002-05-15 |
Time |
15:59 |
Sent To |
|
|
Notes |
2002-05-15 00:00:00 | CHECKLIST: | | SEE COMMENTS ON PERMIT #02031318. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-04-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-04-22 |
Time |
13:12 |
Rev Time |
1.25 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-22 00:00:00 | SAME COMMENTS AS 02031318 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-03-28 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-03-28 |
Time |
13:00 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-03-28 |
Time |
13:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-04-04 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-04-04 |
Time |
11:18 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-04-04 |
Time |
11:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-22 |
Time |
13:41 |
Rev Time |
1.00 |
Received By |
pkrauss |
Date |
2002-05-22 |
Time |
13:41 |
Sent To |
|
|
Notes |
2002-05-22 00:00:00 | MECHANICAL PERMIT 02031335 | | LTR SUBMITTED FOR DRYER(LESS THAN 200 | | CFM) |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2002-05-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-13 |
Time |
15:09 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-05-13 |
Time |
15:08 |
Sent To |
|
|
Notes |
2002-05-13 00:00:00 | ******************DENIED**************** | | | | MECHANICAL PERMIT 02031335 | | | | SEER ON ENERGY CALCS OKAY. | | | | OTHER COMMENTS NOT ADDRESSED FROM PREVIO | | US REVIEW. | | | | 1. O.A. CALCS | | 2. DRYER CFM NOT PROVIDED | | 3. DRYER LENGTHS IN EXCESS OF CODE MIN. | | 25'OR PROVIDE MANUFACTURER SPECS | | INDICATING SPECIFIC ALLOWABLE LENGTH. | | 4. SECONDARY DRAIN CONSPICUOUS POINT | | SHALL NOT BE BEHIND AHU UNIT DOOR. IF | | NO SUITABLE CONSPICUOUS LOCATION IS | | AVAILABLE, A PAN WITH A FLOAT SWITCH | | PER 307.2.4 IS ACCEPTABLE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-04-08 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-04-08 |
Time |
13:26 |
Rev Time |
0.25 |
Received By |
ndenmark |
Date |
2002-04-08 |
Time |
13:26 |
Sent To |
|
|
Notes |
2002-04-08 00:00:00 | **************DENIED******************** | | | | ADDITIONAL INFORMATION REQUIRED | | 1. PROVIDE CFM REQUIREMENTS FOR DRYER TO | | DETERMINE COMPLIANCE PER 2001 FBC(M) | | 504.5 | | 2. PROVIDE OUTSIDE AIR PER FBC(M) TABLE | | 403.3 | | 3. SEER ON EQUIPMENT SCHEDULE DOES NOT | | MATCH SEER ON ENERGY CALCS | | | | NOTE: DRYER AND BATH EXHAUST DUCTS SHALL | | NOT PENETRATE RATED PARTYWALL OR | | ADJACENT ROOF |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-05-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-13 |
Time |
18:36 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-13 |
Time |
18:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-04-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-21 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-21 |
Time |
14:44 |
Sent To |
|
|
Notes |
2002-04-21 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FHA AMEND-98 DESIGN MANUAL | | | | 1) SEE COMMENTS FOR PERMIT #02031318 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-03-27 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-03-27 |
Time |
09:16 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|